Mitsubishi Electronics FR-A500L instruction manual Changing the control logic

Page 21

INSTALLATION AND WIRING

(3) Changing the control logic

The input signals are set to sink logic for the NA version, and to source logic for the EC version.

To change the control logic, the connector on the back of the control circuit terminal block must be moved to the other position.

(The output signals may be used in either the sink or source logic independently of the connector position.)

1)Loosen the two mounting screws in both ends of the control circuit terminal block. (The screws cannot be removed.)

With both hands, pull down the terminal block from the back of the control circuit terminals.

2)Remove the connector in the sink logic position on the back surface of the control circuit terminal block and fit it to the source logic position.

EC version

CON3

CON2

SOURCE

SINK

NA version

CON3

CON2

SINK

SOURCE

 

CON3 SINK

CON2 SOURCE

3)Using care not to bend the pins of the control circuit connector, reinstall the control circuit terminal block and fix it with the mounting screws.

Note: 1. Make sure that the control circuit connector is fitted correctly.

2.While power is on, never disconnect the control circuit terminal block.

3.The sink-source logic change-over connector must be fitted in only one of those positions. If it is fitted in both positions at the same time, the inverter may be damaged.

13

Image 21
Contents FR-A500L This section is specifically about safety matters Electric Shock Prevention Fire PreventionInjury Prevention Wiring Transportation and installationAdditional instructions Trial runOperation Maintenance, inspection and parts replacementEmergency stop Disposing of the inverterContents Chapter Outline Installation Precautions for operationWiring Pre-Operation InformationBasic configuration Basic ConfigurationNFB ELB Name DescriptionChapter Instructions for installation InstallationAt 5cm 1.97 inch Terminal connection diagram WiringDescription of main circuit terminals Symbol Terminal Name DescriptionDescription of control circuit terminals Terminal Name Description,B,C RUNIPF Wiring instructions Wiring of the main circuit800 2300 Terminal block layoutP1, P, N Connection procedure Connection of the power supply and motorNA version(OR Version) Wiring of the control circuitChanging the control logic RUN DC24V How to use terminals STOP, CS and PC For RS-485 communication Connection to the PU connectorDesign information Chapter Operation Chapter Parameters Parameters Parameter ListDU/PU main display data selection F4 fourth frequency voltage 173 201 Can be accessed when Pr = Protective Functions Error alarm definitions Errors AlarmsOperation Parameter Unit Name DescriptionOLT OHTSTP OPTMB7 CTEMain circuit error E,15 details Charge AlarmName Details Correspondences between digital and actual characters To know the operating status at the occurrence of alarmResetting the inverter Alarm code outputAlarm Code Alarm Output across B-C FR-DU04 Operation PanelTroubleshooting Checking the operation panel display at alarm stopOperation Panel Check Point Remedy Display Check Point Remedy Speed greatly differs from the setting Faults and check pointsMotor remains stopped Motor rotates in opposite directionPower lamp is not lit Operation mode is not changed properlyMotor current is large Speed does not increasePrecautions for maintenance and inspection Precautions for Maintenance and InspectionCheck items Periodic inspectionDielectric strength test Insulation resistance test using meggerDescription Method Criterion Instrument Daily Daily and Periodic InspectionPreparation Checking methodModule device numbers and terminals to be checked Cooling fan Replacement of partsSmoothing capacitors RelaysMeasurement of voltages and currents Measurement of main circuit voltages, currents and powerMeasuring Point Measuring Instrument 10VDC5VDC Chapter Specifications Model specifications Standard specificationCommon specifications FR-PU04 AlarmFR-A540L-450K, 375K Outline drawingsFR-A540L-540K~800K P5S RDB RDA SDB SDAAppendices Appendix AppendixFront Wiring between cooling fan and terminals is as follows Check the air flow directionEF-40ETB R G Converter EF-30ETB Control Inverter MT-BR5MT-BR5 TH1 TH2 PR PR E Resistor Temperature Abnormal SignalsShipment case example