| PROTECTIVE FUNCTIONS |
|
|
|
|
|
|
Operation | Parameter |
|
|
|
Panel |
|
|
| |
Unit | Name | Description |
| |
Display |
| |||
|
|
|
| |
|
|
| ||
|
|
|
| |
|
|
| This function stops the inverter output if a ground fault occurs in the |
|
E. GF | Ground | Output side ground fault | inverter's output (load) side and a ground fault current flows. A ground |
|
Fault | overcurrent protection | fault occurring at low ground resistance may activate the overcurrent |
| |
|
| |||
|
|
| protection (OC1 to OC3). |
|
|
|
|
|
|
|
|
| If the external thermal relay designed for motor overheat protection or the |
|
|
| External thermal relay | internally mounted temperature relay in the motor switches on (relay |
|
E.OHT | OH Fault | contacts "open"), the inverter output can be stopped if those contacts had |
| |
operation (Note 3) |
| |||
|
| been entered into the inverter. If the relay contacts are reset |
| |
|
|
|
| |
|
|
| automatically, the inverter will not restart unless it is reset. |
|
|
|
|
|
|
|
|
| If a current not less than 150% (Note 4) of the rated inverter current flows |
|
|
|
| in the motor, this function lowers the frequency until the load current |
|
E.OLT |
| During acceleration | reduces to prevent the inverter from resulting in overcurrent |
|
| When the load current has reduced below 150%, this function increases |
| ||
(When |
|
| ||
|
|
| ||
|
| the frequency again to accelerate and operate the inverter up to the set |
| |
stall |
|
|
| |
|
| frequency. |
| |
prevention |
|
|
| |
|
|
|
| |
operation | Stll Prev |
| If a current not less than 150% (Note 4) of the rated inverter current flows |
|
has | STP | During | in the motor, this function lowers the frequency until the load current |
|
reduced | (OL shown | reduces to prevent overcurrent |
| |
operation |
| |||
the | during stall | reduced below 150%, this function increases the frequency up to the set |
| |
|
| |||
running | prevention |
| value. |
|
frequency | operation) |
| If the regenerative energy of the motor has increased above the brake |
|
to 0. OL |
|
| capability, this function increases the frequency to prevent overvoltage |
|
during stall |
|
|
| |
|
|
| ||
prevention |
|
|
| |
| During deceleration | current flows in the motor, this function increases the frequency until the |
| |
operation) |
|
| ||
|
| load current reduces to prevent the inverter from resulting in overcurrent |
| |
|
|
|
| |
|
|
|
| |
|
|
| decreases the frequency again. |
|
|
|
|
|
|
|
|
| ・Stops the inverter output if the dedicated inboard option used in the |
|
E.OPT | Option | Option alarm | inverter results in setting error or connection (connector) fault. |
|
Fault | ・When the high power factor converter connection is selected, this |
| ||
|
|
| ||
|
|
| alarm is displayed if AC power is connected to R, S, T. |
|
|
|
|
|
|
E.OP1 to | Option slot |
| Stops the inverter output if a functional fault (such as communication error |
|
alarm | Option slot alarm | of the communication option) occurs in the inboard option loaded in any |
| |
OP3 |
| |||
1 to 3 |
| slot. |
| |
|
|
| ||
|
|
|
|
|
E. PE | Corrupt | Parameter error | Stops the output if a fault occurs in E2PROM which stores parameter |
|
Memry | settings. |
| ||
|
|
| ||
|
|
|
|
|
|
|
| This function stops the inverter output if communication between inverter |
|
|
|
| and PU is suspended, e.g. the operation panel or parameter unit is |
|
|
|
| disconnected, when "2", "3", "16" or "17" is set in Pr. 75 "reset |
|
| PU Leave | PU disconnection | selection/PU disconnection detection/PU stop selection". This function |
|
E.PUE | stops the inverter output if the number of successive communication |
| ||
Out | occurrence |
| ||
| errors is greater than the number of permissible retries when Pr. 121 |
| ||
|
|
|
| |
|
|
| value is "9999" for |
|
|
|
| This function stops the inverter output if communication is broken for a |
|
|
|
| period of time set in Pr. 122. |
|
|
|
|
|
|
E.RET | Retry No | Retry count exceeded | If operation cannot be resumed within the number of retries set, this |
|
Over | function stops the inverter output. |
| ||
|
|
| ||
|
|
|
|
|
E.LF | | Open output phase | This function stops the inverter output when any of the three phases (U, |
|
protection | V, W) on the inverter's output side (load side) opens. |
| ||
|
|
| ||
|
|
|
|
|
|
|
| If the arithmetic operation of the |
|
E.CPU | CPU Fault | CPU error | predetermined period, the inverter |
|
|
|
| stops the output. |
|
|
|
|
|
|
|
|
| When 24VDC power output from the PC terminal is shorted, this function |
|
E.P24 | | 24VDC power output short | shuts off the power output. At this time, all external contact inputs switch |
|
circuit | off. The inverter cannot be reset by entering the RES signal. To reset, use |
| ||
|
|
| ||
|
|
| the operation panel or switch power off, then on again. |
|
|
|
|
|
|