Mitsubishi Electronics FR-A500L instruction manual Installation, Instructions for installation

Page 11

2.1Installation

INSTALLATION AND WIRING

2.1.1 Instructions for installation

1)Handle the unit carefully.

The inverter uses plastic parts. Handle it gently to protect it from damage. Also, hold the unit with even strength and do not apply too much strength to the front cover alone.

2)Install the inverter where it is not subjected to vibration. Note the vibration of a cart, press, etc.

3)Note on ambient temperature

The inverter life is under great influence of ambient temperature. In the place of installation, ambient temperature must be within the permissible range (-10°C to +40° C (14° F to 104° F) ). Check that the ambient temperature is within that range in the positions shown in figure 3).

*For FR-A540L-375/450K at constant torque (CT) rating maximum ambient temperature can be 50° C (122° F).

4)Install the inverter on a non-combustible surface.

The inverter will be very hot (maximum. about 150° C (302° F) ). Install it on a non-combustible surface (e.g. metal). Also leave sufficient clearances around the inverter.

5)Avoid high temperature and high humidity.

Avoid places where the inverter is subjected to direct sunlight, high temperature and high humidity.

Note: The cooling section outside the enclosure has the cooling fan. Do not use the inverter in any environment where it is exposed to waterdrops, oil mist, dust, etc.

6)Avoid places where the inverter is exposed to oil mist, flammable gases, fluff, dust, dirt, etc.

Install the inverter in a clean place or inside a "totally enclosed" panel which does not accept any suspended matter.

7)Note the cooling method when the inverter is installed in an enclosure.

When an inverter is mounted in an enclosure, the ventilation fans of the inverter and enclosure must be carefully positioned to keep the ambient temperature of the inverter below the permissible value. If they are installed in improper positions, the rise in ambient temperature will result in reduced performance of the inverter.

8)Secure the inverter vertically, with bolts.

Install the inverter on an installation surface securely and vertically with screws or bolts.

3

Image 11
Contents FR-A500L This section is specifically about safety matters Injury Prevention Electric Shock PreventionFire Prevention Trial run Transportation and installationWiring Additional instructionsDisposing of the inverter Maintenance, inspection and parts replacementOperation Emergency stopContents Chapter Outline Pre-Operation Information Precautions for operationInstallation WiringName Description Basic ConfigurationBasic configuration NFB ELBChapter Instructions for installation InstallationAt 5cm 1.97 inch Terminal connection diagram WiringTerminal Name Description Symbol Terminal Name DescriptionDescription of main circuit terminals Description of control circuit terminalsIPF ,B,CRUN Wiring instructions Wiring of the main circuit800 2300 Terminal block layoutP1, P, N Connection procedure Connection of the power supply and motorNA version(OR Version) Wiring of the control circuitChanging the control logic RUN DC24V How to use terminals STOP, CS and PC For RS-485 communication Connection to the PU connectorDesign information Chapter Operation Chapter Parameters Parameters Parameter ListDU/PU main display data selection F4 fourth frequency voltage 173 201 Can be accessed when Pr = Protective Functions Unit Name Description Errors AlarmsError alarm definitions Operation ParameterOPT OHTOLT STPMB7 CTEName Details Main circuit error E,15 detailsCharge Alarm Correspondences between digital and actual characters To know the operating status at the occurrence of alarmOperation Panel Alarm code outputResetting the inverter Alarm Code Alarm Output across B-C FR-DU04Operation Panel Check Point Remedy Display TroubleshootingChecking the operation panel display at alarm stop Check Point Remedy Motor rotates in opposite direction Faults and check pointsSpeed greatly differs from the setting Motor remains stoppedSpeed does not increase Operation mode is not changed properlyPower lamp is not lit Motor current is largePeriodic inspection Precautions for Maintenance and InspectionPrecautions for maintenance and inspection Check itemsDielectric strength test Insulation resistance test using meggerDescription Method Criterion Instrument Daily Daily and Periodic InspectionModule device numbers and terminals to be checked PreparationChecking method Relays Replacement of partsCooling fan Smoothing capacitorsMeasurement of voltages and currents Measurement of main circuit voltages, currents and power5VDC Measuring Point Measuring Instrument10VDC Chapter Specifications Model specifications Standard specificationCommon specifications FR-PU04 AlarmFR-A540L-450K, 375K Outline drawingsFR-A540L-540K~800K P5S RDB RDA SDB SDAAppendices Front AppendixAppendix EF-40ETB R G Converter EF-30ETB Control Inverter Wiring between cooling fan and terminals is as followsCheck the air flow direction MT-BR5MT-BR5 TH1 TH2 PR PR E Resistor Temperature Abnormal SignalsShipment case example