Mitsubishi Electronics FR-A500L instruction manual F4 fourth frequency voltage

Page 30

PARAMETERS

Func-

Parameter

 

 

Minimum

Factory Setting

Refer To

Name

Setting Range

Setting

Page:

tion

Number

 

 

Increments

 

<Note9>

 

 

 

 

 

flexiblepoint-5V/F characteristics

107

V/F4 (fourth frequency voltage)

0 to 1000V

0.1V

0

98

(Note 1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

108

V/F5 (fifth frequency) (Note 1)

0 to 400Hz, 9999

0.01Hz

9999

98

 

 

 

 

 

 

 

 

109

V/F5 (fifth frequency voltage)

0 to 1000V

0.1V

0

98

 

(Note 1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

110

Third acceleration/deceleration time

0 to 3600 sec/

0.1 sec/

9999

99

 

0 to 360 sec, 9999

0.01 sec

 

 

 

 

 

functions

111

Third deceleration time

0 to 3600 sec/

0.1 sec/

9999

99

0 to 360 sec, 9999

0.01 sec

 

 

 

 

 

 

 

112

Third torque boost (Note 1)

0 to 30.0%, 9999

0.1%

9999

99

Third

113

Third V/F (base frequency) (Note 1)

0 to 400Hz, 9999

0.01Hz

9999

99

*114

Third stall prevention operation current

0 to 150%

0.1%

150%

99

 

115

Third stall prevention operation frequency

0 to 400Hz

0.01Hz

0

99

 

116

Third output frequency detection

0 to 400Hz, 9999

0.01Hz

9999

99

functions

117

Station number

0 to 31

1

0

99

 

 

10, 11 (data length 7)

 

 

 

 

118

Communication speed

48, 96, 192

1

192

99

 

119

Stop bit length/data length

0, 1 (data length 8)

1

1

99

 

 

Communication

 

 

 

 

 

 

120

Parity check presence/absence

0, 1, 2

1

2

99

 

 

121

Number of communication retries

0 to 10, 9999

1

1

99

 

122

Communication check time interval

0, 0.1 to 999.8 sec,

0.1

0<9999>

99

 

9999

 

 

 

 

 

 

 

123

Waiting time setting

0 to 150ms, 9999

10ms

9999

99

 

124

CR, LF presence/absence selection

0,1,2

1

1

99

 

128

PID action selection

10, 11, 20, 21

1

10

109

control

129

PID proportional band

0.1 to 1000%, 9999

0.1%

100%

109

131

Upper limit

0 to 100%, 9999

0.1%

9999

109

 

130

PID integral time

0.1 to 3600 sec, 9999

0.1 sec

1 sec

109

PID

 

 

 

 

 

 

132

Lower limit

0 to 100%, 9999

0.1%

9999

109

 

 

133

PID action set point for PU operation

0 to 100%

0.01%

0%

109

 

134

PID differential time

0.01 to 10.00 sec, 9999

0.01 sec

9999

109

Commercialpower supply- inverterswitch-over

 

Commercial power supply-inverter

 

 

 

 

135

switch-over sequence output terminal

0, 1, 2

1

0

116

 

selection

 

 

 

 

136

MC switch-over interlock time

0 to 100.0 sec

0.1 sec

1.0 sec

116

 

supply switch-over frequency

 

 

 

 

 

137

Start waiting time

0 to 100.0 sec

0.1 sec

0.5 sec

116

 

138

Commercial power supply-inverter

0, 1

1

0

116

 

switch-over selection at alarm occurrence

 

 

 

 

 

 

 

139

Automatic inverter-commercial power

0 to 60.00Hz, 9999

0.01Hz

9999

116

 

 

 

 

 

 

 

 

 

 

140

Backlash acceleration stopping

0 to 400Hz

0.01Hz

1.00Hz

119

 

frequency (Note 7)

 

 

 

 

 

 

Backlash

141

Backlash acceleration stopping time

0 to 360 sec

0.1 sec

0.5 sec

119

(Note 7)

 

 

 

 

 

 

 

 

142

Backlash deceleration stopping

0 to 400Hz

0.01Hz

1.00Hz

119

 

frequency (Note 7)

 

 

 

 

 

 

 

143

Backlash deceleration stopping time

0 to 360 sec

0.1 sec

0.5 sec

119

 

(Note 7)

 

 

 

 

 

 

Display

144

Speed setting switch-over

0, 2, 4, 6, 8, 10, 102,

1

4

119

 

 

104, 106, 108, 110

 

 

 

 

 

 

 

 

 

 

 

 

 

Additional functions

*149

Stall prevention level at 10V input

0 to 150%

0.1%

150%

58

 

*148

Stall prevention level at 0V input

0 to 150%

0.1%

120%

58

 

 

 

 

 

 

 

20

Image 30
Contents FR-A500L This section is specifically about safety matters Electric Shock Prevention Fire PreventionInjury Prevention Additional instructions Transportation and installationWiring Trial runEmergency stop Maintenance, inspection and parts replacementOperation Disposing of the inverterContents Chapter Outline Wiring Precautions for operationInstallation Pre-Operation InformationNFB ELB Basic ConfigurationBasic configuration Name DescriptionChapter Installation Instructions for installationAt 5cm 1.97 inch Wiring Terminal connection diagramDescription of control circuit terminals Symbol Terminal Name DescriptionDescription of main circuit terminals Terminal Name Description,B,C RUNIPF Wiring of the main circuit Wiring instructionsTerminal block layout 800 2300P1, P, N Connection of the power supply and motor Connection procedureWiring of the control circuit NA version(OR Version)Changing the control logic RUN DC24V How to use terminals STOP, CS and PC Connection to the PU connector For RS-485 communicationDesign information Chapter Operation Chapter Parameters Parameter List ParametersDU/PU main display data selection F4 fourth frequency voltage 173 201 Can be accessed when Pr = Protective Functions Operation Parameter Errors AlarmsError alarm definitions Unit Name DescriptionSTP OHTOLT OPTCTE MB7Main circuit error E,15 details Charge AlarmName Details To know the operating status at the occurrence of alarm Correspondences between digital and actual charactersAlarm Code Alarm Output across B-C FR-DU04 Alarm code outputResetting the inverter Operation PanelTroubleshooting Checking the operation panel display at alarm stopOperation Panel Check Point Remedy Display Check Point Remedy Motor remains stopped Faults and check pointsSpeed greatly differs from the setting Motor rotates in opposite directionMotor current is large Operation mode is not changed properlyPower lamp is not lit Speed does not increaseCheck items Precautions for Maintenance and InspectionPrecautions for maintenance and inspection Periodic inspectionInsulation resistance test using megger Dielectric strength testDaily and Periodic Inspection Description Method Criterion Instrument DailyPreparation Checking methodModule device numbers and terminals to be checked Smoothing capacitors Replacement of partsCooling fan RelaysMeasurement of main circuit voltages, currents and power Measurement of voltages and currentsMeasuring Point Measuring Instrument 10VDC5VDC Chapter Specifications Standard specification Model specificationsCommon specifications Alarm FR-PU04Outline drawings FR-A540L-450K, 375KFR-A540L-540K~800K SDA P5S RDB RDA SDBAppendices Appendix AppendixFront Wiring between cooling fan and terminals is as follows Check the air flow directionEF-40ETB R G Converter EF-30ETB Control Inverter Resistor Temperature Abnormal Signals MT-BR5MT-BR5 TH1 TH2 PR PR EShipment case example