PROTECTIVE FUNCTIONS

 

 

Measuring Points and Instruments

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

Measuring Point

Measuring Instrument

 

 

 

 

 

 

 

 

Remarks

 

 

 

 

 

(Reference Measured Value)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Across R-S, S-T and T-R

 

Commercial power supply

 

 

Power supply voltage V1

Moving-iron type AC voltmeter

Within

permissible

AC voltage

 

<Across L1-L2, L2-L3and L3-L1>

 

 

 

fluctuationRefer to Page 40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply side

R, S and T line currents

 

Moving-iron type AC ammeter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

current I1

<L1, L2, and L3 line currents>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

At R, S and T, and across R-S,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply side power

S-T and T-R

 

 

 

 

 

 

 

 

Electrodynamic type single-

P1 = W11 +

W12 + W13

 

 

 

 

 

P1

<At L1, L2 and L3, and across L1-

phase wattmeter

(3-wattmeter method)

 

 

 

 

 

 

L2, L2-L3and L3-L1>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply side power

Calculate after measuring power supply voltage, power supply side current and power supply side power.

 

P1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

factor Pf1

 

 

 

 

×

100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pf1 = 3 V1 I1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rectifier type AC voltmeter

Difference between phases is

 

 

Output side voltage V2

Across U-V, V-Wand W-U

within ± 1% of maximum output

 

 

(Note 1) (Not moving-iron type)

 

 

 

 

 

 

 

 

 

 

 

 

voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current should be equal to or less

 

Output side current I2

U, V and W line currents

Moving-iron type AC ammeter

than rated inverter current.

 

 

Difference between phases is 10%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or lower.

 

 

 

 

 

 

 

 

 

 

 

 

 

At U, V and W, and across U-V

Electrodynamic type single-

P2 = W21 +

W22

 

 

 

 

 

Output side power P2

2-wattmeter method (or 3-

 

 

and V-W

 

 

 

 

 

 

 

 

phase wattmeter

 

 

 

 

 

 

 

 

 

 

 

wattmeter method)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output side power factor

Calculate in similar manner to power supply side power factor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pf2

 

 

 

 

×

100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pf2 = 3 V2 I2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER lamp lit

 

 

 

 

 

Converter output

Across P-N< Across + and - >

Moving-coil type (such as

1.35 ×

 

 

 

V1

 

 

 

 

 

 

 

 

 

 

 

 

tester)

Maximum 760V during

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

regenerative operation

 

 

 

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Across 2 ( )

 

5

 

 

 

 

 

 

0 to 5V/0 to 10VDC

 

 

“5”is common.

 

Frequency setting power

+

 

 

 

 

 

 

 

 

 

±

 

 

 

 

 

 

±

 

 

 

 

 

 

 

 

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency setting signal

Across 1 ( )

 

5

 

 

 

 

 

 

0 to

 

5V/0 to

 

 

10VDC

 

 

 

 

 

 

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Across 4 ( )

 

5

 

 

 

 

 

 

4 to 20mADC

 

 

 

 

 

 

 

 

 

 

Across 10 ( )

 

5

 

 

 

 

5VDC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

supply

 

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Across 10E ( )

 

5

 

 

 

10VDC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Approximately. 5VDC at

 

 

 

 

 

 

 

 

 

 

 

 

 

 

maximum frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(without frequency meter)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

 

 

 

 

 

 

 

 

 

 

DC8V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moving-coil type (Tester, etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Across FM (

)

 

 

SD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency meter signal

 

 

 

 

 

 

 

 

 

may be used) (Internal

 

 

 

 

 

 

 

 

 

T2

 

 

 

 

 

 

common.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

resistance: 50kΩ or larger)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pulse width T1:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adjusted by Pr.900

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pulse cycle T2: Set by Pr.55

 

is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Valid for frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

monitoring only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

 

 

 

 

 

 

 

Approximately 10DVC at

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Across AM ( )

 

 

5

 

 

 

 

maximum frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(without frequency meter)

 

 

 

Start signal

Across STF, STR, RH, RM, RL,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Select signal

RT, AU, STOP, CS ( )

SD

 

20 to 30VDC when open.

 

 

 

 

 

 

 

 

 

 

+

 

 

 

 

 

 

 

 

+

 

 

 

 

 

 

ON voltage: 1V or less

 

 

 

Reset

Across RES ( )

 

SD

 

 

 

 

 

 

 

 

 

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output stop

Across MRS ( )

 

SD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Across A-C

 

 

 

 

 

 

 

 

Moving-coil type

Continuity check (Note 2)

 

 

Alarm signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<At OFF>

<At ON>

 

 

Across B-C

 

 

 

 

 

 

 

 

(such as tester)

Across A-C:

Discontinuity Continuity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Across B-C:

Continuity

Discontinuity

 

Note 1. Accurate data will not be obtained by a tester.

2.When Pr. 195 "A, B, C terminal function selection" setting is positive logic.

40

Image 51
Contents FR-A500L This section is specifically about safety matters Electric Shock Prevention Fire PreventionInjury Prevention Trial run Transportation and installationWiring Additional instructionsDisposing of the inverter Maintenance, inspection and parts replacementOperation Emergency stopContents Chapter Outline Pre-Operation Information Precautions for operationInstallation WiringName Description Basic ConfigurationBasic configuration NFB ELBChapter Instructions for installation InstallationAt 5cm 1.97 inch Terminal connection diagram WiringTerminal Name Description Symbol Terminal Name DescriptionDescription of main circuit terminals Description of control circuit terminals,B,C RUNIPF Wiring instructions Wiring of the main circuit800 2300 Terminal block layoutP1, P, N Connection procedure Connection of the power supply and motorNA version(OR Version) Wiring of the control circuitChanging the control logic RUN DC24V How to use terminals STOP, CS and PC For RS-485 communication Connection to the PU connectorDesign information Chapter Operation Chapter Parameters Parameters Parameter ListDU/PU main display data selection F4 fourth frequency voltage 173 201 Can be accessed when Pr = Protective Functions Unit Name Description Errors AlarmsError alarm definitions Operation ParameterOPT OHTOLT STPMB7 CTEMain circuit error E,15 details Charge AlarmName Details Correspondences between digital and actual characters To know the operating status at the occurrence of alarmOperation Panel Alarm code outputResetting the inverter Alarm Code Alarm Output across B-C FR-DU04Troubleshooting Checking the operation panel display at alarm stopOperation Panel Check Point Remedy Display Check Point Remedy Motor rotates in opposite direction Faults and check pointsSpeed greatly differs from the setting Motor remains stoppedSpeed does not increase Operation mode is not changed properlyPower lamp is not lit Motor current is largePeriodic inspection Precautions for Maintenance and InspectionPrecautions for maintenance and inspection Check itemsDielectric strength test Insulation resistance test using meggerDescription Method Criterion Instrument Daily Daily and Periodic InspectionPreparation Checking methodModule device numbers and terminals to be checked Relays Replacement of partsCooling fan Smoothing capacitorsMeasurement of voltages and currents Measurement of main circuit voltages, currents and powerMeasuring Point Measuring Instrument 10VDC5VDC Chapter Specifications Model specifications Standard specificationCommon specifications FR-PU04 AlarmFR-A540L-450K, 375K Outline drawingsFR-A540L-540K~800K P5S RDB RDA SDB SDAAppendices Appendix AppendixFront Wiring between cooling fan and terminals is as follows Check the air flow directionEF-40ETB R G Converter EF-30ETB Control Inverter MT-BR5MT-BR5 TH1 TH2 PR PR E Resistor Temperature Abnormal SignalsShipment case example