GE IC3645SP4U400N3, IC3645SR4U404N2 operation manual Function 10 Field Current for Regen

Page 58

ADJUSTABLE FEATURES

SX TRANSISTOR CONTROLS

Page 58

FUNCTION 6

FW RATIO

 

(Push 6)

This function sets the ratio between armature and field current when operating below the Field Weakening Start point. The setting represents the quantity of field current changed for each 1 amp of armature current changed.

Max Fld Ref

Set

Resolution Per Unit Value

40

0 to 10

0.029 amps

The ratio value (VAL) is the set value divided by 10 and rounded to the whole number.

Example: Setting of 45 = 45/10 = 4.5 = 4 VAL

IFIELD = VAL (IMOTOR x 0.029)

FUNCTION 7 MIN FIELD CURRENT ( Push 7 )

This function allows the adjustment of the field weakening level in order to set the top speed of the motor.

Min

Max

Set

Resolution Per Unit Value

0

40

51 to 255

0.185

MIN IF = (VAL-51) X 0.185

Important Note: This function is used to optimize motor and control performance, and this setting will be determined by GE and OEM engineers at the time of vehicle development. This setting must not be changed by field personnel without the permission of the OEM.

FUNCTION 8 MAX FIELD CURRENT ( Push 8 )

This function allows for the adjustment of the maximum field current in order to obtain the maximum torque of the motor.

Min

Max

Set

Resolution Per Unit Value

0

40

51 to 255

0.185

MAX IF = (VAL-51) X 0.185

Important Note: This function is used to optimize motor and control performance, and this setting will be determined by GE and OEM engineers at the time of vehicle development. This setting must not be changed by field personnel without the permission of the OEM.

FUNCTION 9 REGEN BRAKING C/L (Push 9)

This function allows for the adjustment of the Regen braking current limit. High current correlates to shorter stopping distance.

 

 

 

Resolution

Example

Min

Max

Set

Per unit value

If set at 20

52A

468A

0 to 255

1.63 amps

84.6 amps

REGEN BRAKE IA = (VAL X 1.63) + 52

FUNCTION 10 FIELD CURRENT FOR REGEN

( Push 10 )

This function allows for the adjustment of the field current to be used during the regen braking mode.

 

 

 

Resolution

Example

Min

Max

Set

Per unit value

If set at 71

0

40

51 to 255

0.185 amps

3.7 amps

IF = (VAL-51) X 0.185

Important Note: This function is used to optimize motor and control performance and this setting will be determined by GE and OEM engineers at the time of vehicle development. This setting must not be changed by field personnel without the permission of the OEM.

FUNCTION 11 TURN SPEED LIMIT (Push 11)

This function allows for the adjustment of the speed limit (maximum battery volts to the motor) when the SL1 signal is calculated from the turn angle potentiometer by the control card.

Range

100% to 0% battery volts

Set

51 to 180

Resolution

0.78% per set unit

Example

Setting of 71 = 84.4% of battery volts

Note: To disable speed limit, and assure no 1A hold off, set this function to a value of zero.

FUNCTION 12 MAX ARMATURE PERCENT ON ( Push 12 )

Same as function 11, this function allows for the adjustment of the motor speed limit (maximum battery volts to the motor). The dash display mode selection enables the speed limit as well as setting the level of speed limit.

January 2000

Image 58
Contents Installation and Operation Table of Contents 46-52 20-4041-45 57-62Basic Operation and Features Motor CharacteristicsFlexible System Application More Features with Fewer ComponentsSolid-State Reversing Slows with the increase of current in the field2 Current Limit 1.b Creep Speed1.c Control Acceleration 3.c Pedal Position Plug Braking4.c Proportional Operation for Dual Motor Vehicles 6 Steer Pump Contactor Time Delay4.b Speed Limits 5 Ramp Operation 5a Ramp StartSystem Protective Override 1 Static Return to Off SRO Diagnostics 1 Systems Diagnostics7 On-Board Coil Drivers & Internal Coil Suppression 2 Accelerator Volts Hold Off3 Hourmeter Readings 3.a Maintenance Alert & Speed Limit4 Battery Discharge Indication BDI 4.a Internal Resistance CompensationBasic Operation and Features Part Number Outline DRAWINGS, Elementary Drawings and INPUTS/OUTPUTSArgument Outline SX-3 and SR-3 Package Size Drawings and INPUTS/OUTPUTS DRAWINGS, Elementary Drawings and INPUTS/OUTPUTS Control SectionConnections to Main Plug 23 PIN and Y Plug 12 PIN PINDiagnostic Status Codes 2.d. High Power Signals Level HP High-Level Signals Level HMedium-Power Signals Level MP Cable Spacing GuidelinesReconnect plugs Cleaner328A1777G1 General Troubleshooting Instructions Traction No seat switch or deadman switchTraction Control Codes Status CodeReverse directional switch is closed on Description of Status Cause of Status IndicationAccelerator depressed with no Start switch fails to closeDirection selected KEY Negative Both the forward and reverse Directional switches are closed atSame time Start switch closed on power up after Initial key switch closureDischarged battery Reverse direction Motor field current is high on start upForward direction Run mode Volts DC Power supply is less than 10 voltsMotor field current is too high during Traction Controller Slave/auxiliary control Transistor over temperature Open thermal protector TP orArmature transistor did not turn off Motor armature offset voltage is tooLow ProperlyArmature transistor did not turn on Than 12% of battery voltsLook Ahead test for A2 volts less Capacitor volts are low before the line Motor field current is too low duringContactor closes Input too low during running Controller motor current sensorLine driver input P2-17 is less Description Armature current exceeds Armature transistor limitVerify connection between the master control P21 Traction Status Code Symptom Temperature TMM Status CodesSteer Plug P5 pump is shorted to positive Plug P8 pump is shorted to positive Corrective Actions TROUBLE-SHOOTING Diagram YES Pump SymptomPossible Cause Transistor is over temperature Open thermal protector TP1 orSensor input is missing No power to pump motorPump Controller motor current Control rangeTurn off properly Power Transistor Q1 did notPower Transistor Q1 did not turn on With no pump contactor, controlCapacitor volts are low after the line Contactor closesSensor input voltage polarity Controller motor currentCheck Battery voltage is less than Voltage at capacitor 1C is less than VoltsTMM7A 3 TMM Pump Control Connections TMM7A Outline DrawingsAdjustable Features START-UP Display SequenceAction Accessing Stored Status Codes With GE HandsetRemarks Function Function 10 Field Current for Regen Internal Resistance Compensation Battery VoltsBattery volts Set units Function 16 Stall Trip Point with % ON-TIME PushFunction 25 Monitor Function 19 Maintenance Code Tens and Units Hours SETFunction 26 Base Ratio Function 51 Mode 1 MAX Armature % on Function 49 Mode 1 Field Weakening Start PushFunction 28 Stored Status Code Count Pointer Push Function 57 Mode 3 Field Weakening Start Function 52 Mode 2 Armature Controlled AccelerationFunction 55 Mode 2 MAX Armature % on Function 59 Mode 3 MAX Armature % onSummary of Current Limit Adjustments Field CurrentFunction 14 not Applicable Function Current LimitFunction 16 Speed / Torque Compensation Function 49 Mode 1 Speed Limit 2 SL2 Push Speed / Torque Compensation Table Voltage SettingFunction 48 Mode 1 Controlled Acceleration Push Function 50 Mode 1 Speed Limit 3 SL3Function 55 not Applicable Function 53 Mode 2 Speed Limit 2 SL2Function 54 Mode 2 Speed Limit 3 SL3 Function 59 not ApplicableStandard Dash Displays Dash DisplaysApplication ConnectionsStart-Up Display Sequence Outline DrawingsSetup Turn Angle Potentiometer InstallationOperation Degree Potentiometer for Steer Angle Input Degree Potentiometer Left Right Traction Control RS-232 Memory MAP TablesRestrictions Function Reset to Zero Only HoursTens/Ones Reset to Zero Only Stored Status Code #5Reset to Zero Only Stored Status Code #6 Reset to Zero Only HoursThou/HunNone Dash Display Ratio2-1 Reset to Zero Only Stored Status Code #16Reset to Zero Only Dash Display CA-1 Dash Display FWS-1 None