GE IC3645SP4U400N3 Function 19 Maintenance Code Tens and Units Hours SET, Function 25 Monitor

Page 60

ADJUSTABLE FEATURES

SX TRANSISTOR CONTROLS

vehicle manufacturer. Card type selection must be made within the capabilities of the control panel used and the supporting electro mechanical devices. Failure to comply with proper application standards could result in mis- operation or damage to the control and/or motors.

FUNCTION 18 STEER PUMP TIME DELAY ( Push CONT 3 )

This function allows for the selection of steer pump contactor pick up input, either seat switch or directional switch closing, and adjustment of the time delay for the contactor drop out.

Pick up steer pump contactor on seat switch closure and time delay drop out of steer pump contactor on seat switch opening:

Range

1.5 to 65 seconds

Setting

Between 0 and 128

Resolution

0.5 seconds per set unit

Example: Setting of 20 = (20 x 0.5) + 1.5 = 11.5 seconds

Pick up steer pump contactor on directional switch closure and time delay drop out of steer pump contactor on directional switch opening:

Range

0.5 to 63 seconds

Setting

Between 129 and 255

Resolution

0.5 seconds per set unit

Example: Setting of 149 = ((149-129) x 0.5) + 1.5 = 11.5 seconds

Note: Contactor drop out will be 1.5 seconds after the seat switch opens.

FUNCTION 19 MAINTENANCE CODE TENS AND UNITS HOURS SET

( Push CONT 4 )

This function allows for the adjustment of the tens and units hours of the maintenance code activation time.

Range

0 to 99

Set

0 to 99

Example

9999 Hours

FUNCTION 20 MAINTENANCE CODE THOUSANDS AND HUNDREDS HOURS SET

( Push CONT 5 )

This function allows for the adjustment of the thousands and hundreds hours of the maintenance code activation time.

Page 60

Range

0 to 240

Set

0 to 240

Example

9999 Hours

FUNCTION 21 AUTO REGEN BRAKING C/L (Push CONT 6)

This function allows for the adjustment of the Regen braking current limit. High current value correlates to shorter stopping distance.

Setting greater than 143 disables this function.

AUTO REGEN = REGEN C/L -

FNT 21--51

(

6.50

[

C/L AMPS

VAL

[(

VAL

 

 

 

 

FUNCTION 24 FIELD WEAKENING START ( Push CONT 9)

This function allows for setting the armature current at which minimum field current will achieved .

Range

0 to 414 Amps

Setting

0 to 255

Resolution

1.625 per set unit

I MOTOR FWS = VAL. x 1.625

Example: Setting of 20 = 32.5 amps

FUNCTION 25 MONITOR

( Push CONT 10)

This function allows the monitoring of certain control functions by looking directly at the RAM of the microprocessor. Because absolute memory locations need to be known, this function should not be used without detailed instructions from the GE application engineer.

This function should only be adjusted by the vehicle OEM. To ensure optimum operation of the control, this function must be left with zero stored in this register.

FUNCTION 26 BASE RATIO

( Push CONT 11)

This function sets the ratio between armature and field current when operating below the maximum field current and above the Field Weakening Start point. The setting represents the quantity of field current changed for each 1 amp of armature current changed.

Max Fld Ref

Set

Resolution Per Unit Value

40

0 to 10

0.029 amps

January 2000

Image 60
Contents Installation and Operation Table of Contents 20-40 41-4546-52 57-62Basic Operation and Features Motor CharacteristicsMore Features with Fewer Components Solid-State ReversingFlexible System Application Slows with the increase of current in the field1.b Creep Speed 1.c Control Acceleration2 Current Limit 3.c Pedal Position Plug Braking6 Steer Pump Contactor Time Delay 4.b Speed Limits4.c Proportional Operation for Dual Motor Vehicles 5 Ramp Operation 5a Ramp StartDiagnostics 1 Systems Diagnostics 7 On-Board Coil Drivers & Internal Coil SuppressionSystem Protective Override 1 Static Return to Off SRO 2 Accelerator Volts Hold Off3.a Maintenance Alert & Speed Limit 4 Battery Discharge Indication BDI3 Hourmeter Readings 4.a Internal Resistance CompensationBasic Operation and Features Outline DRAWINGS, Elementary Drawings and INPUTS/OUTPUTS Part NumberArgument Outline SX-3 and SR-3 Package Size Drawings and INPUTS/OUTPUTS DRAWINGS, Elementary Drawings and INPUTS/OUTPUTS Control SectionConnections to Main Plug 23 PIN and Y Plug 12 PIN PINDiagnostic Status Codes High-Level Signals Level H Medium-Power Signals Level MP2.d. High Power Signals Level HP Cable Spacing GuidelinesCleaner Reconnect plugs328A1777G1 General Troubleshooting Instructions No seat switch or deadman switch Traction Control CodesTraction Status CodeReverse directional switch is closed on Description of Status Cause of Status IndicationStart switch fails to close Accelerator depressed with noDirection selected KEY Negative Directional switches are closed at Both the forward and reverseSame time Start switch closed on power up after Initial key switch closureDischarged battery Motor field current is high on start up Reverse directionForward direction Volts DC Power supply is less than 10 volts Run modeMotor field current is too high during Traction Controller Slave/auxiliary control Transistor over temperature Open thermal protector TP orMotor armature offset voltage is too LowArmature transistor did not turn off ProperlyThan 12% of battery volts Armature transistor did not turn onLook Ahead test for A2 volts less Motor field current is too low during Capacitor volts are low before the lineContactor closes Controller motor current sensor Input too low during runningLine driver input P2-17 is less Description Armature current exceeds Armature transistor limitVerify connection between the master control P21 Traction Status Code Symptom Temperature TMM Status CodesSteer Plug P5 pump is shorted to positive Plug P8 pump is shorted to positive Corrective Actions TROUBLE-SHOOTING Diagram YES Symptom PumpPossible Cause Transistor is over temperature Open thermal protector TP1 orNo power to pump motor Pump Controller motor currentSensor input is missing Control rangePower Transistor Q1 did not Power Transistor Q1 did not turn onTurn off properly With no pump contactor, controlCapacitor volts are low after the line Contactor closesController motor current Sensor input voltage polarityCheck Battery voltage is less than Voltage at capacitor 1C is less than VoltsTMM7A 3 TMM Pump Control Connections TMM7A Outline DrawingsAdjustable Features START-UP Display SequenceAccessing Stored Status Codes With GE Handset ActionRemarks Function Function 10 Field Current for Regen Battery Volts Battery volts Set unitsInternal Resistance Compensation Function 16 Stall Trip Point with % ON-TIME PushFunction 19 Maintenance Code Tens and Units Hours SET Function 25 MonitorFunction 26 Base Ratio Function 49 Mode 1 Field Weakening Start Push Function 51 Mode 1 MAX Armature % onFunction 28 Stored Status Code Count Pointer Push Function 52 Mode 2 Armature Controlled Acceleration Function 55 Mode 2 MAX Armature % onFunction 57 Mode 3 Field Weakening Start Function 59 Mode 3 MAX Armature % onSummary of Current Limit Adjustments Field CurrentFunction Current Limit Function 14 not ApplicableFunction 16 Speed / Torque Compensation Speed / Torque Compensation Table Voltage Setting Function 48 Mode 1 Controlled Acceleration PushFunction 49 Mode 1 Speed Limit 2 SL2 Push Function 50 Mode 1 Speed Limit 3 SL3Function 53 Mode 2 Speed Limit 2 SL2 Function 54 Mode 2 Speed Limit 3 SL3Function 55 not Applicable Function 59 not ApplicableDash Displays ApplicationStandard Dash Displays ConnectionsStart-Up Display Sequence Outline DrawingsTurn Angle Potentiometer Installation SetupOperation Degree Potentiometer for Steer Angle Input Degree Potentiometer Left Right RS-232 Memory MAP Tables Traction ControlRestrictions Function Reset to Zero Only Stored Status Code #5 Reset to Zero Only Stored Status Code #6Reset to Zero Only HoursTens/Ones Reset to Zero Only HoursThou/HunReset to Zero Only Stored Status Code #16 Reset to Zero Only Dash Display CA-1 Dash Display FWS-1None Dash Display Ratio2-1 None