Section 6.4 Setup Functions for Traction Controller

FUNCTION 1 MOTOR VOLTS TO ENABLE AUTO REGEN (Push 1)

This function allows for the adjustment of motor volts to enable AutoRegen.

For a setting value of less than 25 (corresponding to a soft release of auto regen and normal regen), the motor voltage to enable regen is calculated by multiplying the value of the setting by 0.375. For example, a setting of 16 will be multiplied by 0.375 to enable regen at 6 motor volts.

Vm = VAL(setting) X .375

For a setting value of greater than 25, the motor voltage to enable auto regen is calculated by subtracting 25 from the setting value and multiplying that number by 0.375. For example, a setting of 33, the motor volts necessary to enable auto regen is (33 - 25) x 0.375, or 3 volts.

FUNCTION 2

CREEP SPEED

 

(Push 2)

This function allows for the adjustment of the creep speed of the vehicle. Creep speed can be adjusted when an accelerator input voltage between 3.9 and 3.3 volts or an

accelerator ohm input between 6.0K and 4.0K ohms is provided.

Range

2% to 15% on-time

Set

0 to 255

Resolution

0.05% per set unit

Example

Setting of 20 = 3% on-time

Important Note: This function is used to optimize motor and control performance, and this setting will be determined by GE and OEM engineers at the time of vehicle development. This setting must not be changed by field personnel without the permission of the OEM.

FUNCTION 3 ARMATURE CONTROLLED ACCELERATION

(Push 3)

This function allows for the adjustment of the rate of time it takes for the control to accelerate to 100% applied battery voltage to the motor on hard acceleration.

Range

0.025 to 6.3 seconds

Set

0 to 255

Resolution

0.025 seconds per set unit

Example:

Setting of 20 = 0.5 seconds

FUNCTION 4 ARMATURE CURRENT LIMIT (Push 4)

This function allows for the adjustment of the armature current limit of the control. The rating of the control will determine the range of adjustment for this function. Please refer to the specification sheets and current limit curves for the control used in your vehicle.

Range

See control C/L curves

Set

0 to 255

Example:

0 = min. current, 255 = max.

 

current

FUNCTION 5 PLUGGING DISTANCE (CURRENT) (Push 5)

This function allows for the adjustment of the plugging distance of the vehicle. The larger the current setting, the shorter the stopping distance.

Min

Max

Set

Resolution

Example

 

 

 

Per Unit Value

If Set at 20

55

455

0 to 255

1.57 amps

86.4 amps

Warning: Plug settings must be made in accordance with control operating instructions. Too high of a setting could cause damage to the control system or traction motor.

January 2000

Image 57
Contents Installation and Operation Table of Contents 41-45 20-4046-52 57-62Motor Characteristics Basic Operation and FeaturesSolid-State Reversing More Features with Fewer ComponentsFlexible System Application Slows with the increase of current in the field1.c Control Acceleration 1.b Creep Speed2 Current Limit 3.c Pedal Position Plug Braking4.b Speed Limits 6 Steer Pump Contactor Time Delay4.c Proportional Operation for Dual Motor Vehicles 5 Ramp Operation 5a Ramp Start7 On-Board Coil Drivers & Internal Coil Suppression Diagnostics 1 Systems DiagnosticsSystem Protective Override 1 Static Return to Off SRO 2 Accelerator Volts Hold Off4 Battery Discharge Indication BDI 3.a Maintenance Alert & Speed Limit3 Hourmeter Readings 4.a Internal Resistance CompensationBasic Operation and Features Outline DRAWINGS, Elementary Drawings and INPUTS/OUTPUTS Part NumberArgument Outline SX-3 and SR-3 Package Size Drawings and INPUTS/OUTPUTS Section DRAWINGS, Elementary Drawings and INPUTS/OUTPUTS ControlPIN Connections to Main Plug 23 PIN and Y Plug 12 PINDiagnostic Status Codes Medium-Power Signals Level MP High-Level Signals Level H2.d. High Power Signals Level HP Cable Spacing GuidelinesCleaner Reconnect plugs328A1777G1 General Troubleshooting Instructions Traction Control Codes No seat switch or deadman switchTraction Status CodeDescription of Status Cause of Status Indication Reverse directional switch is closed onStart switch fails to close Accelerator depressed with noDirection selected KEY Negative Directional switches are closed at Both the forward and reverseSame time Initial key switch closure Start switch closed on power up afterDischarged battery Motor field current is high on start up Reverse directionForward direction Volts DC Power supply is less than 10 volts Run modeMotor field current is too high during Traction Controller Slave/auxiliary control Open thermal protector TP or Transistor over temperatureLow Motor armature offset voltage is tooArmature transistor did not turn off ProperlyThan 12% of battery volts Armature transistor did not turn onLook Ahead test for A2 volts less Motor field current is too low during Capacitor volts are low before the lineContactor closes Controller motor current sensor Input too low during runningLine driver input P2-17 is less Description Armature transistor limit Armature current exceedsVerify connection between the master control P21 Traction Status Code Symptom TMM Status Codes TemperatureSteer Plug P5 pump is shorted to positive Plug P8 pump is shorted to positive Corrective Actions TROUBLE-SHOOTING Diagram YES Symptom PumpPossible Cause Open thermal protector TP1 or Transistor is over temperaturePump Controller motor current No power to pump motorSensor input is missing Control rangePower Transistor Q1 did not turn on Power Transistor Q1 did notTurn off properly With no pump contactor, controlContactor closes Capacitor volts are low after the lineController motor current Sensor input voltage polarityCheck Voltage at capacitor 1C is less than Volts Battery voltage is less thanTMM7A TMM7A Outline Drawings 3 TMM Pump Control ConnectionsSTART-UP Display Sequence Adjustable FeaturesAccessing Stored Status Codes With GE Handset ActionRemarks Function Function 10 Field Current for Regen Battery volts Set units Battery VoltsInternal Resistance Compensation Function 16 Stall Trip Point with % ON-TIME PushFunction 19 Maintenance Code Tens and Units Hours SET Function 25 MonitorFunction 26 Base Ratio Function 49 Mode 1 Field Weakening Start Push Function 51 Mode 1 MAX Armature % onFunction 28 Stored Status Code Count Pointer Push Function 55 Mode 2 MAX Armature % on Function 52 Mode 2 Armature Controlled AccelerationFunction 57 Mode 3 Field Weakening Start Function 59 Mode 3 MAX Armature % onField Current Summary of Current Limit AdjustmentsFunction Current Limit Function 14 not ApplicableFunction 16 Speed / Torque Compensation Function 48 Mode 1 Controlled Acceleration Push Speed / Torque Compensation Table Voltage SettingFunction 49 Mode 1 Speed Limit 2 SL2 Push Function 50 Mode 1 Speed Limit 3 SL3Function 54 Mode 2 Speed Limit 3 SL3 Function 53 Mode 2 Speed Limit 2 SL2Function 55 not Applicable Function 59 not ApplicableApplication Dash DisplaysStandard Dash Displays ConnectionsOutline Drawings Start-Up Display SequenceTurn Angle Potentiometer Installation SetupOperation Degree Potentiometer for Steer Angle Input Degree Potentiometer Left Right RS-232 Memory MAP Tables Traction ControlRestrictions Function Reset to Zero Only Stored Status Code #6 Reset to Zero Only Stored Status Code #5Reset to Zero Only HoursTens/Ones Reset to Zero Only HoursThou/HunReset to Zero Only Dash Display CA-1 Dash Display FWS-1 Reset to Zero Only Stored Status Code #16None Dash Display Ratio2-1 None