ADJUSTABLE FEATURES

TRANSISTOR PUMP CONTROLS

Page 64

Section 6.6 Setup Functions for Hydraulic Pump Control

FUNCTION 1:

NOT APPLICABLE

This function is not applicable to this type of control and should not be adjusted.

FUNCTION 2: INTERNAL RESISTANCE COMPENSATION START (Push 2)

This function allows for the adjustment of the current level at which the internal resistance compensation feature (Function 16) will take effect.

Range

0 to 1325 amps

Setting

52 to 255

Resolution

6.5 amps per set unit

Example: Setting of 72 = (72-52) x 6.5 = 130 amps

FUNCTION 3: CONTROLLED ACCELERATION (Push 3)

This function allows for the adjustment of the rate of time it takes for the control to accelerate to 96% applied battery voltage to the motor on hard acceleration.

Range

0.1 to 5.5 seconds

Setting

0 to 255

Resolution

0.021 seconds per set unit

Example: Setting of 20 = 0.52 seconds C/A

FUNCTION 4:

CURRENT LIMIT

 

(Push 4)

This function allows for the adjustment of the current limit of the control. The rating of the control will determine the range of adjustment for this function. Please refer to the OEM operating instructions for the control used in your vehicle.

Range

See OEM control C/L curves

Setting

0 to 255

Example: 0 = min. current, 255 = max. current

FUNCTION 7: INTERNAL RESISTANCE COMPENSATION RATE (Push 7)

This function allows for the adjustment of the rate of time it takes for the control to add the internal resistance compensation voltage that is applied to the motor. This function will add 0.375 volts to the motor at the rate of time

adjusted until the total IR compensation voltage has been added.

Range

0.0015 to 0.383 seconds

Setting

0 to 255

Resolution

0.0015 seconds per set unit

Example: Setting of 20 = 0.032 seconds

For example, if you had selected 2.08 volts from Function 16 to be added to the motor, it would take 0.18 seconds to add a total of 2.08 volts. (2.08/0.375)=0.032

FUNCTION 11: SPEED LIMIT 1 (SL1) (Push 11)

This function allows for the adjustment of the speed limit (maximum battery volts to the motor) when the SL1 limit switch input signal is received by the control card. SL1 limit switch is a normally open switch connected to battery negative, the switch closing enables speed limit.

Range

0% to 100% battery volts

Setting

0 to 255

Resolution

0.375 volts per set unit

Example: Setting of 50=18.75 volts

FUNCTION 12: SPEED LIMIT 2 (SL2) (Push 12)

Same as Function 11 except using SL2 limit switch for input.

FUNCTION 13: SPEED LIMIT 3 (SL3) (Push 13)

Same as Function 11 except using SL3 limit switch for input.

FUNCTION 14: NOT APPLICABLE

This function is not applicable to this type of control and should not be adjusted.

Note: The following functions have function numbers larger than the numbers on the Handset keyboard. To access these functions, push the CONT key and the number shown in the following instructions at the same time. THE KEY SWITCH MUST BE OPEN.

FUNCTION 16: SPEED / TORQUE COMPENSATION

(Push CONT 1)

This function is used to stabilize pump speed at heavy loads. The voltage selected will be added to the motor at each 100 amp increment starting at the value set in Function 2. The voltage compensation selected will be added in increments of 0.375 volts until the entire voltage is added. For example, a setting of 2 will be added in 30 steps

January 2000

Image 64
Contents Installation and Operation Table of Contents 20-40 41-4546-52 57-62Basic Operation and Features Motor CharacteristicsMore Features with Fewer Components Solid-State ReversingFlexible System Application Slows with the increase of current in the field1.b Creep Speed 1.c Control Acceleration2 Current Limit 3.c Pedal Position Plug Braking6 Steer Pump Contactor Time Delay 4.b Speed Limits4.c Proportional Operation for Dual Motor Vehicles 5 Ramp Operation 5a Ramp StartDiagnostics 1 Systems Diagnostics 7 On-Board Coil Drivers & Internal Coil SuppressionSystem Protective Override 1 Static Return to Off SRO 2 Accelerator Volts Hold Off3.a Maintenance Alert & Speed Limit 4 Battery Discharge Indication BDI3 Hourmeter Readings 4.a Internal Resistance CompensationBasic Operation and Features Part Number Outline DRAWINGS, Elementary Drawings and INPUTS/OUTPUTSArgument Outline SX-3 and SR-3 Package Size Drawings and INPUTS/OUTPUTS DRAWINGS, Elementary Drawings and INPUTS/OUTPUTS Control SectionConnections to Main Plug 23 PIN and Y Plug 12 PIN PINDiagnostic Status Codes High-Level Signals Level H Medium-Power Signals Level MP2.d. High Power Signals Level HP Cable Spacing GuidelinesReconnect plugs Cleaner328A1777G1 General Troubleshooting Instructions No seat switch or deadman switch Traction Control CodesTraction Status CodeReverse directional switch is closed on Description of Status Cause of Status IndicationAccelerator depressed with no Start switch fails to closeDirection selected KEY Negative Both the forward and reverse Directional switches are closed atSame time Start switch closed on power up after Initial key switch closureDischarged battery Reverse direction Motor field current is high on start upForward direction Run mode Volts DC Power supply is less than 10 voltsMotor field current is too high during Traction Controller Slave/auxiliary control Transistor over temperature Open thermal protector TP orMotor armature offset voltage is too LowArmature transistor did not turn off ProperlyArmature transistor did not turn on Than 12% of battery voltsLook Ahead test for A2 volts less Capacitor volts are low before the line Motor field current is too low duringContactor closes Input too low during running Controller motor current sensorLine driver input P2-17 is less Description Armature current exceeds Armature transistor limitVerify connection between the master control P21 Traction Status Code Symptom Temperature TMM Status CodesSteer Plug P5 pump is shorted to positive Plug P8 pump is shorted to positive Corrective Actions TROUBLE-SHOOTING Diagram YES Pump SymptomPossible Cause Transistor is over temperature Open thermal protector TP1 orNo power to pump motor Pump Controller motor currentSensor input is missing Control rangePower Transistor Q1 did not Power Transistor Q1 did not turn onTurn off properly With no pump contactor, controlCapacitor volts are low after the line Contactor closesSensor input voltage polarity Controller motor currentCheck Battery voltage is less than Voltage at capacitor 1C is less than VoltsTMM7A 3 TMM Pump Control Connections TMM7A Outline DrawingsAdjustable Features START-UP Display SequenceAction Accessing Stored Status Codes With GE HandsetRemarks Function Function 10 Field Current for Regen Battery Volts Battery volts Set unitsInternal Resistance Compensation Function 16 Stall Trip Point with % ON-TIME PushFunction 25 Monitor Function 19 Maintenance Code Tens and Units Hours SETFunction 26 Base Ratio Function 51 Mode 1 MAX Armature % on Function 49 Mode 1 Field Weakening Start PushFunction 28 Stored Status Code Count Pointer Push Function 52 Mode 2 Armature Controlled Acceleration Function 55 Mode 2 MAX Armature % onFunction 57 Mode 3 Field Weakening Start Function 59 Mode 3 MAX Armature % onSummary of Current Limit Adjustments Field CurrentFunction 14 not Applicable Function Current LimitFunction 16 Speed / Torque Compensation Speed / Torque Compensation Table Voltage Setting Function 48 Mode 1 Controlled Acceleration PushFunction 49 Mode 1 Speed Limit 2 SL2 Push Function 50 Mode 1 Speed Limit 3 SL3Function 53 Mode 2 Speed Limit 2 SL2 Function 54 Mode 2 Speed Limit 3 SL3Function 55 not Applicable Function 59 not ApplicableDash Displays ApplicationStandard Dash Displays ConnectionsStart-Up Display Sequence Outline DrawingsSetup Turn Angle Potentiometer InstallationOperation Degree Potentiometer for Steer Angle Input Degree Potentiometer Left Right Traction Control RS-232 Memory MAP TablesRestrictions Function Reset to Zero Only Stored Status Code #5 Reset to Zero Only Stored Status Code #6Reset to Zero Only HoursTens/Ones Reset to Zero Only HoursThou/HunReset to Zero Only Stored Status Code #16 Reset to Zero Only Dash Display CA-1 Dash Display FWS-1None Dash Display Ratio2-1 None