| LEGEND | |||
AL | — | Alarm Relay Contacts | P1 |
|
|
| — Field Wiring Terminal Block | |||||||
ASTAT | — | Aquastat | RVS |
|
|
| — Reversing Valve Solenoid | |||||||
BM | — Blower Motor | TRANS |
|
|
| — Transformer | ||||||||
BMC | — Blower Motor Capacitor |
|
|
|
|
|
|
|
|
|
|
| Factory Low Voltage Wiring | |
BR | — Blower Relay |
|
|
|
|
|
|
|
|
|
|
| Factory Line Voltage Wiring | |
CB | — Circuit Breaker |
|
|
|
|
|
|
|
|
|
|
| Field Low Voltage Wiring | |
CC | — Compressor Contactor |
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| Field Line Voltage Wiring | |||
CO | — Condensate Overflow Sensor |
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| Printed Circuit Trace | |||
COMPR | — Compressor |
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| Optional Wiring | |||
DTS | — | Discharge Temp Switch |
|
|
|
|
|
|
|
|
|
|
| |
FP1 | — Water Coil Freeze Protection Sensor |
|
|
|
|
|
|
|
|
|
|
| Relay/Contactor Coil | |
FP2 | — Air Coil Freeze Protection Sensor |
|
|
|
|
|
|
|
|
|
|
| ||
HP | — |
|
|
|
|
|
|
|
|
|
|
|
| |
HWG | — Hot Water Generator |
|
|
|
|
|
|
|
|
|
|
| Thermistor | |
JW | — Jumper Wire |
|
|
|
|
|
|
|
|
|
|
| ||
LOC | — Loss of Charge Pressure Switch |
|
|
|
|
|
|
|
|
|
|
| Condensate Pan | |
MV | — Motorized Valve |
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| ||||
NEC | — National Electric Code |
|
|
|
|
|
|
|
|
|
|
| Circuit Breaker | |
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*Optional.
Ground
Solenoid Coil
Relay Contacts - N.C.
Relay Contacts - N.O.
Capacitor
Temperature Switch
Low Pressure Switch
High Pressure Switch
Wire Nut
Splice Cap
GLED
NOTES:
1.Compressor and blower motor thermally protected internally.
2.All wiring to the unit must comply with NEC and local codes.
3.Transformer is wired to 460 v (BLK/RED) lead for 460/60/3 units,
575 v (GRY) lead for 575/60/3. Transformer is energy limiting or may have circuit breaker.
4.FP1 thermistor provides freeze protection for water. When using anti- freeze solutions, cut JW3 jumper.
5.Check installation wiring information for specific thermostat hookup. Refer to thermostat installation instructions for wiring to the unit. Thermostat wiring must be “Class 1” and voltage rating equal to or greater than unit supply voltage.
6.
7.Transformer secondary ground via Deluxe D board standoffs and screws to control box. (Ground available from top two standoffs as shown.)
8.Aquastat is supplied with unit and must be wired in series with the hot leg to the pump. Aquastat is rated for voltage up to 277 v.
9.Blower motor is factory wired for high and low speeds. No other com-
bination is available.
10.The
TABLE 1 |
| WIRE NUMBER |
| |||
Blower | 1 | 2 | 3 | 4 | 5 | |
Speeds | ||||||
|
|
|
|
| ||
Factory | BM(H) to | BM(R) to | BM(M) to | Not Used | BR2(6) to | |
HI + MED | BR2(6) | BR2(3) | BR2(7) |
| BR2(4) | |
HI + LOW | BM(H) to | BM(R) to | Not Used | BM(L) to | BR2(6) to | |
| BR2(6) | BR2(3) |
| BR2(7) | BR2(4) | |
MED + LOW | BM(H) to | BM(R) to | BM(M) to | BM(L) to | BR2(2) to | |
| BR2(3) | BR2(3) | BR2(6) | BR2(7) | BR2(4) |
DELUXE D CONTROLLER FAULT CODES
OPERATION | STATUS LED | TEST LED | FAULT LED | ALARM | |
(GREEN) | (YELLOW) | (RED) | RELAY | ||
| |||||
Normal Mode | ON | OFF | Note 2 | Open | |
Deluxe D is | OFF | OFF | OFF | Open | |
Test Mode | — | ON | Note 2 | Cycle (Note 3) | |
Night Setback | Flashing Code 2 | — | Note 2 | — | |
Emergency Shut Down | Flashing Code 3 | — | Note 2 | — | |
Invalid Thermostat Inputs | Flashing Code 4 | — | Note 2 | — | |
No Fault in Memory | ON | OFF | Flashing Code 1 | Open | |
HP Fault/(Lockout) Note 1 | Slow Flash/ | OFF | Flashing Code 2 | Open/(Closed) | |
(Fast Flash) | |||||
|
|
|
| ||
LP Fault/(Lockout) Note 1 | Slow Flash/ | OFF | Flashing Code 3 | Open/(Closed) | |
(Fast Flash) | |||||
|
|
|
| ||
FP1 Fault/(Lockout) Note 1 | Slow Flash/ | OFF | Flashing Code 4 | Open/(Closed) | |
(Fast Flash) | |||||
|
|
|
| ||
FP2 Fault/(Lockout) Note 1 | Slow Flash/ | OFF | Flashing Code 5 | Open/(Closed) | |
(Fast Flash) | |||||
|
|
|
| ||
CC Fault/(Lockout) Note 1 | Slow Flash/ | OFF | Flashing Code 6 | Open/(Closed) | |
(Fast Flash) | |||||
|
|
|
| ||
Slow Flash | OFF | Flashing Code 7 | Open (Note 4) | ||
Normal Mode with UPS | ON | OFF | Flashing Code 8 | Cycle (Note 5) | |
Swapped FP1/FP2 Lockout | Fast Flash | OFF | Flashing Code 9 | Closed |
NOTES:
1.Status LED (GREEN) Slow Flash - Controller In - Fault Retry Mode. Fast Flash - Controller in Lock- out Mode. Slow Flash = 1 Flash per every 2 seconds. Fast Flash = 2 Flashes per every 1 second.
2.Fault LED (RED) flashes a code representing last fault in memory. If no fault in memory code 1 is flashed.
3.Cycles appropriate code, by cycling alarm relay in the same sequence as fault LED.
4.Alarm relay closes after 15 minutes.
5.Alarm relay cycles. Closed for 5 seconds and open for 25 seconds.
Fig. 16 — Units with Deluxe D Controller, Three-Phase (460/575 V)