LEGEND

AL

Alarm Relay Contacts

P1

 

 

 

Field Wiring Terminal Block

ASTAT

Aquastat

RVS

 

 

 

Reversing Valve Solenoid

BM

Blower Motor

TRANS

 

 

 

Transformer

BMC

Blower Motor Capacitor

 

 

 

 

 

 

 

 

 

 

 

Factory Low Voltage Wiring

BR

Blower Relay

 

 

 

 

 

 

 

 

 

 

 

Factory Line Voltage Wiring

CB

Circuit Breaker

 

 

 

 

 

 

 

 

 

 

 

Field Low Voltage Wiring

CC

Compressor Contactor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Field Line Voltage Wiring

CO

Condensate Overflow Sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Printed Circuit Trace

COMPR

Compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Optional Wiring

DTS

Discharge Temp Switch

 

 

 

 

 

 

 

 

 

 

 

FP1

Water Coil Freeze Protection Sensor

 

 

 

 

 

 

 

 

 

 

 

Relay/Contactor Coil

FP2

Air Coil Freeze Protection Sensor

 

 

 

 

 

 

 

 

 

 

 

HP

High-Pressure Switch

 

 

 

 

 

 

 

 

 

 

 

 

HWG

Hot Water Generator

 

 

 

 

 

 

 

 

 

 

 

Thermistor

JW

Jumper Wire

 

 

 

 

 

 

 

 

 

 

 

LOC

Loss of Charge Pressure Switch

 

 

 

 

 

 

 

 

 

 

 

Condensate Pan

MV

Motorized Valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NEC

National Electric Code

 

 

 

 

 

 

 

 

 

 

 

Circuit Breaker

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Optional.

Ground

Solenoid Coil

Relay Contacts - N.C.

Relay Contacts - N.O.

Capacitor

Temperature Switch

Low Pressure Switch

High Pressure Switch

Wire Nut

Splice Cap

GLED

NOTES:

1.Compressor and blower motor thermally protected internally.

2.All wiring to the unit must comply with NEC and local codes.

3.Transformer is wired to 460 v (BLK/RED) lead for 460/60/3 units,

575 v (GRY) lead for 575/60/3. Transformer is energy limiting or may have circuit breaker.

4.FP1 thermistor provides freeze protection for water. When using anti- freeze solutions, cut JW3 jumper.

5.Check installation wiring information for specific thermostat hookup. Refer to thermostat installation instructions for wiring to the unit. Thermostat wiring must be “Class 1” and voltage rating equal to or greater than unit supply voltage.

6.24-v alarm signal shown. For dry alarm contact, cut JW4 jumper and dry contact will be available between AL1 and AL2.

7.Transformer secondary ground via Deluxe D board standoffs and screws to control box. (Ground available from top two standoffs as shown.)

8.Aquastat is supplied with unit and must be wired in series with the hot leg to the pump. Aquastat is rated for voltage up to 277 v.

9.Blower motor is factory wired for high and low speeds. No other com-

bination is available.

10.The 460-v units using an ECM (electronically commutated motor) fan motor, modulating HWR, and/or an internal secondary pump will require a neutral wire from the supply side in order to feed the acces- sory with 265-v.

TABLE 1

 

WIRE NUMBER

 

Blower

1

2

3

4

5

Speeds

 

 

 

 

 

Factory

BM(H) to

BM(R) to

BM(M) to

Not Used

BR2(6) to

HI + MED

BR2(6)

BR2(3)

BR2(7)

 

BR2(4)

HI + LOW

BM(H) to

BM(R) to

Not Used

BM(L) to

BR2(6) to

 

BR2(6)

BR2(3)

 

BR2(7)

BR2(4)

MED + LOW

BM(H) to

BM(R) to

BM(M) to

BM(L) to

BR2(2) to

 

BR2(3)

BR2(3)

BR2(6)

BR2(7)

BR2(4)

DELUXE D CONTROLLER FAULT CODES

OPERATION

STATUS LED

TEST LED

FAULT LED

ALARM

(GREEN)

(YELLOW)

(RED)

RELAY

 

Normal Mode

ON

OFF

Note 2

Open

Deluxe D is Non-Functional

OFF

OFF

OFF

Open

Test Mode

ON

Note 2

Cycle (Note 3)

Night Setback

Flashing Code 2

Note 2

Emergency Shut Down

Flashing Code 3

Note 2

Invalid Thermostat Inputs

Flashing Code 4

Note 2

No Fault in Memory

ON

OFF

Flashing Code 1

Open

HP Fault/(Lockout) Note 1

Slow Flash/

OFF

Flashing Code 2

Open/(Closed)

(Fast Flash)

 

 

 

 

LP Fault/(Lockout) Note 1

Slow Flash/

OFF

Flashing Code 3

Open/(Closed)

(Fast Flash)

 

 

 

 

FP1 Fault/(Lockout) Note 1

Slow Flash/

OFF

Flashing Code 4

Open/(Closed)

(Fast Flash)

 

 

 

 

FP2 Fault/(Lockout) Note 1

Slow Flash/

OFF

Flashing Code 5

Open/(Closed)

(Fast Flash)

 

 

 

 

CC Fault/(Lockout) Note 1

Slow Flash/

OFF

Flashing Code 6

Open/(Closed)

(Fast Flash)

 

 

 

 

Over-Under Voltage

Slow Flash

OFF

Flashing Code 7

Open (Note 4)

Normal Mode with UPS

ON

OFF

Flashing Code 8

Cycle (Note 5)

Swapped FP1/FP2 Lockout

Fast Flash

OFF

Flashing Code 9

Closed

NOTES:

1.Status LED (GREEN) Slow Flash - Controller In - Fault Retry Mode. Fast Flash - Controller in Lock- out Mode. Slow Flash = 1 Flash per every 2 seconds. Fast Flash = 2 Flashes per every 1 second.

2.Fault LED (RED) flashes a code representing last fault in memory. If no fault in memory code 1 is flashed.

3.Cycles appropriate code, by cycling alarm relay in the same sequence as fault LED.

4.Alarm relay closes after 15 minutes.

5.Alarm relay cycles. Closed for 5 seconds and open for 25 seconds.

Fig. 16 — Units with Deluxe D Controller, Three-Phase (460/575 V)

15

Image 15
Contents Contents Installation, Start-Up, Service InstructionsSafety Considerations InstallationGeneral Physical Data 50PSH, PSV, PSD018-070 Units Typical Installation 50PSH Unit Code Return Discharge CSP ASPBSP CAP50PSV Dimensional Data HWR Hot Water Reheat Left Hand Right Hand A50-7846efBack Discharge Side DischargeMount the Unit Install Condensate DrainTrap Condensate Drain Connection Water Quality Guidelines Open Loop and Recirculating WellMaterial Metal Hose Minimum Bend Radii Typical Ground-Water Piping InstallationSupply/Return Hose Kit Wire Field Power SupplyAstat Complete C Controller Fault CodesDescription of Operation LED Alarm Relay TransYellow RED Wire NumberBMC ComprLWT ECMUnits with ECM, Complete C and LON Controller 460 A50-8363Units with ECM, Deluxe D and LON Controller 460 A50-8364SAT HpwsMves WHSP-OPEN 8354 A508356 LWT Wshp Open Control A50-838050PSH, PSV, PSD Electrical Data PSC High-Static Motor 50PSH, PSV, PSD Electrical Data PSC Motor50PSH, PSV, PSD Electrical Data, ECM Motor Low Voltage Field Wiring Wire Field ControlsField-Supplied Sensors for Wshp Open Controller Rnet Wiring SpecificationsA50-8441 A50-8442A50-8443 Rnet WiringWire Terminal Operate ECM Interface BoardECM Blower Motor Performance Data Setting SizeFPM Rated MIN FANUnit Airflow CFM Speed Size Coil Units with Reheat ESP Loss Face VelocityField Selectable Inputs Complete C Control Jumper SettingsDeluxe D Control Jumper Settings PRE-START-UPVAC DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options Humidistat/Dehumidistat Logic Deluxe D DIP Switch SettingsA50-8145 HWR Operating ModesOperating Limits 50PSH, PSV, PSD Units Unit Start-Up Cooling ModeSTART-UP Operating LimitsWater Flow Temp Unit Start-Up Heating ModeWater Temperature Change Through Heat Exchanger Cooling Heating Water Flow Rate GPM Rise F Drop FGPM/ton Pressure Heat Cooling Rise Drop Psig Flow Flow BACview6 Display Interface Unit Start-Up with Wshp Open ControlsGPM 50PSH, PSV, PSD Water Water Temperature F Flow50PSH, PSV, PSD Coaxial Water Pressure Drop Unit SizeUnits with Aquazone Complete C Control Approximate Fluid Volume gal Per 100 Ft of PipeAntifreeze Percentages by Volume OperationUnits with Wshp Open Multiple Protocol Units with HWR OptionPage Page LED Status Description of Operation Alarm Relay Complete C and Deluxe D Board System TestOff Description Status LED Test LED Complete C Control LED Code Fault DescriptionsLED Code Fault Description Aquazone Deluxe D Control LED IndicaService Replacing the Wshp Open Controller’s Bat TroubleshootingRefrigerant Charging Air Coil Fan Motor RemovalFP1 and FP2 Thermistor Location Page Fault Description Solution ECM TroubleshootingA50-8448 ECM Pin ConnectorsA50-8447 ECM Troubleshooting Flow DiagramTXV Wshp TroubleshootingFault Heating Cooling Possible Cause Solution Good PracticesCode Condensate FaultCode 7 Auto Resetting No Fault Code ShownLow Discharge Air Temperature in HeatingHigh Head Pressure Low Suction PressureAppendix a Wshp Open Screen Configuration Appendix a Wshp Open Screen Configuration Schedules 1 Set PointsWeekly Schedule ExceptionAppendix a Wshp Screen Open Configuration ServiceTest Configuration Service Point Name Password Editable Range Default LevelScreen Name Linkage AlarmPage Page Copyright 2009 Carrier Corporation II. START-UP 50PSH,PSV,PSD START-UP ChecklistA50-8495 Heating Cycle AnalysisCooling Cycle Analysis A50-8494