Carrier PSV, PSD006-070, 50PSH instruction manual HWR Operating Modes, A50-8145

Page 34

HWR APPLICATION CONSIDERATIONS — Unlike most hot gas reheat options, the HWR option will operate over a wide range of entering-water temperatures (EWTs). Special flow regulation (water regulating valve) is not required for low EWT conditions. However, below 55 F, supply-air temperatures cannot be maintained at 72 F because the cooling capacity exceeds the reheat coil capac- ity at low water temperatures. Below 55 F, essentially all water is diverted to the reheat coil (no heat of rejection to the building loop). Although the HWR option will work fine with low EWTs, overcooling of the space may result with well water systems or, on rare occasions, with ground loop (geothermal) systems (NOTE: Extended range units are required for well water and ground loop systems). Since dehumidification is generally only required in cooling, most ground loop systems will not experience overcooling of the supply-air temperature. If overcooling of the space is a con- cern (e.g., computer room well water application), auxiliary heating may be required to maintain space temperature when the unit is operating in the dehumidification mode. Water source heat pumps with HWR should not be used as makeup air units. These applications should use equipment specifically designed for makeup air.

HWR COMPONENT FUNCTIONS — The proportional controller operates on 24 VAC power supply and automatically adjusts the water valve based on the supply-air sensor. The supply-air sensor senses supply-air temperature at the blower inlet, providing the input signal necessary for the proportional control to drive the motorized valve during the reheat mode of operation. The motorized valve is a proportional actuator/three- way valve combination used to divert the condenser water from the coax to the hydronic reheat coil during the reheat mode of operation. The proportional controller sends a signal to the motorized valve based on the supply-air temperature reading from the supply air sensor.

The loop pump circulates condenser water through the hy- dronic reheat coil during the reheat mode of operation (refer to Fig. 34). In this application, the loop pump is only energized during the reheat mode of operation. The hydronic coil is uti- lized during the reheat mode of operation to reheat the air to the set point of the proportional controller. Condenser water is di- verted by the motorized valve and pumped through the hydron- ic coil by the loop pump in proportion to the control set point. The amount of reheating is dependent on the set point and how far from the set point the supply air temperature is. The factory set point is 70 to 75 F, generally considered "neutral" air.

Table 17 — HWR Operating Modes

MODE

 

 

INPUT

 

 

 

 

OUTPUT

 

 

O

G

Y1

Y2*

H

O

G

Y1

Y2*

Reheat

 

No Demand

On/Off

Off

Off

Off

Off

On/Off

Off

Off

Off

Off

Fan Only

On/Off

On

Off

Off

Off

On/Off

On

Off

Off

Off

Cooling Stage 1

On

On

On

Off

Off

On

On

On

Off

Off

Cooling Stage 2

On

On

On

On

Off

On

On

On

On

Off

Cooling and Dehumidistat

On

On

On

On/Off

On

On

On

On

On/Off

Off

Dehumidistat Only

On/Off

Off

Off

Off

On

On

On

On

On

On

Heating Stage 1

Off

On

On

Off

Off

Off

On

On

Off

Off

Heating Stage 2

Off

On

On

On

Off

Off

On

On

On

Off

Heating and Dehumidistat**

Off

On

On

On/Off

On

Off

On

On

On/Off

Off

*Not applicable for single stage units; Full load operation for dual capacity units.

†Cooling input takes priority over dehumidify input.

**Deluxe D is programmed to ignore the H demand when the unit is in heating mode.

NOTE: On/Off is either on or off.

Water Out

 

 

 

 

 

 

 

Refrigerant In

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(To Water Loop)

Mixing Valve

 

 

 

 

 

(Cooling)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Water In

 

Internal Pump

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COAX

 

 

 

 

 

 

 

 

 

 

 

 

(From Water Loop)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant Out

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Cooling)

Entering Air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: All components shown are

Evaporator Coil

internal to the heat pump unit.

 

a50-8145

Leaving

Air

Reheat

Coil

Fig. 34 — HWR Schematic

34

Image 34
Contents Installation, Start-Up, Service Instructions ContentsInstallation Safety ConsiderationsGeneral Physical Data 50PSH, PSV, PSD018-070 Units Typical Installation 50PSH Unit CAP ASPBSP Code Return Discharge CSP50PSV Dimensional Data A50-7846ef HWR Hot Water Reheat Left Hand Right HandSide Discharge Back DischargeInstall Condensate Drain Mount the UnitTrap Condensate Drain Connection Open Loop and Recirculating Well Water Quality GuidelinesMaterial Typical Ground-Water Piping Installation Metal Hose Minimum Bend RadiiWire Field Power Supply Supply/Return Hose KitTrans Complete C Controller Fault CodesDescription of Operation LED Alarm Relay AstatCompr Wire NumberBMC Yellow REDECM LWTA50-8363 Units with ECM, Complete C and LON Controller 460A50-8364 Units with ECM, Deluxe D and LON Controller 460Hpws SATMves WHSP-OPEN A50 83548356 LWT A50-8380 Wshp Open Control50PSH, PSV, PSD Electrical Data PSC Motor 50PSH, PSV, PSD Electrical Data PSC High-Static Motor50PSH, PSV, PSD Electrical Data, ECM Motor Wire Field Controls Low Voltage Field WiringA50-8442 Rnet Wiring SpecificationsA50-8441 Field-Supplied Sensors for Wshp Open ControllerOperate ECM Interface Board Rnet WiringWire Terminal A50-8443Setting Size ECM Blower Motor Performance DataCoil Units with Reheat ESP Loss Face Velocity Rated MIN FANUnit Airflow CFM Speed Size FPMPRE-START-UP Complete C Control Jumper SettingsDeluxe D Control Jumper Settings Field Selectable InputsHumidistat/Dehumidistat Logic Deluxe D DIP Switch Settings DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options VACHWR Operating Modes A50-8145Operating Limits Unit Start-Up Cooling ModeSTART-UP Operating Limits 50PSH, PSV, PSD UnitsCooling Heating Water Flow Rate GPM Rise F Drop F Unit Start-Up Heating ModeWater Temperature Change Through Heat Exchanger Water Flow TempGPM/ton Pressure Heat Cooling Rise Drop Psig Flow Flow Unit Start-Up with Wshp Open Controls BACview6 Display InterfaceUnit Size 50PSH, PSV, PSD Water Water Temperature F Flow50PSH, PSV, PSD Coaxial Water Pressure Drop GPMOperation Approximate Fluid Volume gal Per 100 Ft of PipeAntifreeze Percentages by Volume Units with Aquazone Complete C ControlUnits with HWR Option Units with Wshp Open Multiple ProtocolPage Page Complete C and Deluxe D Board System Test LED Status Description of Operation Alarm RelayOff Aquazone Deluxe D Control LED Indica Complete C Control LED Code Fault DescriptionsLED Code Fault Description Description Status LED Test LEDService Air Coil Fan Motor Removal TroubleshootingRefrigerant Charging Replacing the Wshp Open Controller’s BatFP1 and FP2 Thermistor Location Page ECM Troubleshooting Fault Description SolutionECM Pin Connectors A50-8448ECM Troubleshooting Flow Diagram A50-8447Good Practices Wshp TroubleshootingFault Heating Cooling Possible Cause Solution TXVNo Fault Code Shown Condensate FaultCode 7 Auto Resetting CodeLow Suction Pressure Temperature in HeatingHigh Head Pressure Low Discharge AirAppendix a Wshp Open Screen Configuration Appendix a Wshp Open Screen Configuration Exception Set PointsWeekly Schedule Schedules 1Service Appendix a Wshp Screen Open ConfigurationTest Point Name Password Editable Range Default Level Configuration ServiceScreen Name Alarm LinkagePage Page Copyright 2009 Carrier Corporation 50PSH,PSV,PSD START-UP Checklist II. START-UPA50-8494 Heating Cycle AnalysisCooling Cycle Analysis A50-8495