Carrier PSV, PSD006-070 instruction manual Typical Installation 50PSH Unit

Page 4

Before installing any of the system components, be sure to examine each pipe, fitting, and valve, and remove any dirt or foreign material found in or on these components.

CAUTION

DO NOT store or install units in corrosive environments or in locations subject to temperature or humidity extremes (e.g., attics, garages, rooftops, etc.). Corrosive conditions and high temperature or humidity can significantly reduce performance, reliability, and service life. Always move units in an upright position. Tilting units on their sides may cause equipment damage.

INSPECT UNIT — To prepare the unit for installation, com- plete the procedures listed below:

1.Compare the electrical data on the unit nameplate with ordering and shipping information to verify that the correct unit has been shipped.

2.Do not remove the packaging until the unit is ready for installation.

3.Verify that the unit’s refrigerant tubing is free of kinks or dents, and that it does not touch other unit components.

4.Inspect all electrical connections. Be sure connections are clean and tight at their terminations.

5.Loosen compressor bolts until the compressor rides freely on springs. Remove shipping restraints.

6.Remove the four 1/4 in. shipping bolts from compressor support plate (two bolts on each side) to maximize vibra- tion and sound alternation.

CAUTION

Failure to remove shipping brackets from spring-mounted compressors will cause excessive noise and could cause component failure due to added vibration.

7.Remove any blower support cardboard from inlet of the blower.

8.Locate and verify any accessory kit located in compressor and/or blower section.

9.Remove any access panel screws that may be difficult to remove once unit is installed.

3/8” threaded rods

(by others)

FilterAccess

Field-supplied transition to minimize pressure loss

Supply Air

 

Flexible

Insulated supply duct with

Connection

 

at least one 90 degree elbow

Field-Supplied

to reduce air noise

Electric Heat

(field-supplied)

(if applicable)

 

Return Air (Ductwork not shown)

Power Wiring

Unit Power

Unit Power Disconnect (by others)

Thermostat

Wiring

Stainless steel braid hose with integral “J” swivel

Balancing Valve (field- installed accessory)

Low Pressure Drop Water Control Valve (optional) (field-installed accessory)

Building

Loop

Water Out

Water In

Aux Electric

Heat Disconnect

3/8” Threaded Rod (by others)

Vibration Isolator (white-compressor end and red-blower end)

Washer (by others)

Double Hex Nuts (by others)

Unit Hanger (factory- supplied)

 

Ball Valve with optional

(field-installed

integral P/Tplug (typical for supply

accessory)

and return piping) (field-installed accessory)

Integral hanger support- pre-attached in factory

A50-7728

UNIT HANGER ISOLATION DETAIL

Fig. 1 — Typical Installation — 50PSH Unit

4

Image 4
Contents Installation, Start-Up, Service Instructions ContentsInstallation Safety ConsiderationsGeneral Physical Data 50PSH, PSV, PSD018-070 Units Typical Installation 50PSH Unit ASP BSPCAP Code Return Discharge CSP50PSV Dimensional Data A50-7846ef HWR Hot Water Reheat Left Hand Right HandSide Discharge Back DischargeInstall Condensate Drain Mount the UnitTrap Condensate Drain Connection Open Loop and Recirculating Well Water Quality GuidelinesMaterial Typical Ground-Water Piping Installation Metal Hose Minimum Bend RadiiWire Field Power Supply Supply/Return Hose KitComplete C Controller Fault Codes Description of Operation LED Alarm RelayTrans AstatWire Number BMCCompr Yellow REDECM LWTA50-8363 Units with ECM, Complete C and LON Controller 460A50-8364 Units with ECM, Deluxe D and LON Controller 460Hpws SATMves WHSP-OPEN A50 83548356 LWT A50-8380 Wshp Open Control50PSH, PSV, PSD Electrical Data PSC Motor 50PSH, PSV, PSD Electrical Data PSC High-Static Motor50PSH, PSV, PSD Electrical Data, ECM Motor Wire Field Controls Low Voltage Field WiringRnet Wiring Specifications A50-8441A50-8442 Field-Supplied Sensors for Wshp Open ControllerRnet Wiring Wire TerminalOperate ECM Interface Board A50-8443Setting Size ECM Blower Motor Performance DataRated MIN FAN Unit Airflow CFM Speed SizeCoil Units with Reheat ESP Loss Face Velocity FPMComplete C Control Jumper Settings Deluxe D Control Jumper SettingsPRE-START-UP Field Selectable InputsDIP Switch Block S2 Accessory 1 Relay Options DIP Switch Block S2 Accessory 2 Relay OptionsHumidistat/Dehumidistat Logic Deluxe D DIP Switch Settings VACHWR Operating Modes A50-8145Unit Start-Up Cooling Mode START-UPOperating Limits Operating Limits 50PSH, PSV, PSD UnitsUnit Start-Up Heating Mode Water Temperature Change Through Heat ExchangerCooling Heating Water Flow Rate GPM Rise F Drop F Water Flow TempGPM/ton Pressure Heat Cooling Rise Drop Psig Flow Flow Unit Start-Up with Wshp Open Controls BACview6 Display Interface50PSH, PSV, PSD Water Water Temperature F Flow 50PSH, PSV, PSD Coaxial Water Pressure DropUnit Size GPMApproximate Fluid Volume gal Per 100 Ft of Pipe Antifreeze Percentages by VolumeOperation Units with Aquazone Complete C ControlUnits with HWR Option Units with Wshp Open Multiple ProtocolPage Page Complete C and Deluxe D Board System Test LED Status Description of Operation Alarm RelayOff Complete C Control LED Code Fault Descriptions LED Code Fault DescriptionAquazone Deluxe D Control LED Indica Description Status LED Test LEDService Troubleshooting Refrigerant ChargingAir Coil Fan Motor Removal Replacing the Wshp Open Controller’s BatFP1 and FP2 Thermistor Location Page ECM Troubleshooting Fault Description SolutionECM Pin Connectors A50-8448ECM Troubleshooting Flow Diagram A50-8447Wshp Troubleshooting Fault Heating Cooling Possible Cause SolutionGood Practices TXVCondensate Fault Code 7 Auto ResettingNo Fault Code Shown CodeTemperature in Heating High Head PressureLow Suction Pressure Low Discharge AirAppendix a Wshp Open Screen Configuration Appendix a Wshp Open Screen Configuration Set Points Weekly ScheduleException Schedules 1Service Appendix a Wshp Screen Open ConfigurationTest Point Name Password Editable Range Default Level Configuration ServiceScreen Name Alarm LinkagePage Page Copyright 2009 Carrier Corporation 50PSH,PSV,PSD START-UP Checklist II. START-UPHeating Cycle Analysis Cooling Cycle AnalysisA50-8494 A50-8495