| LEGEND | ||||
AL | — Alarm Relay Contacts | RVS | — Reversing Valve Solenoid | |||||||||
ASTAT | — Aquastat | TRANS | — Transformer | |||||||||
BM | — Blower Motor | UPS | — Unit Performance Sentinel | |||||||||
BR | — Blower Relay |
|
|
|
|
|
|
|
|
|
| Factory Low Voltage Wiring |
CB | — Circuit Breaker |
|
|
|
|
|
|
|
|
|
| Factory Line Voltage Wiring |
CC | — Compressor Contactor |
|
|
|
|
|
|
|
|
|
| Field Low Voltage Wiring |
CO | — Condensate Overflow Sensor |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| Field Line Voltage Wiring | ||
COMPR — Compressor |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| Printed Circuit Trace | ||
DTS | — Discharge Temp Switch |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| Optional Wiring | ||
ECM | — Electronically Commutated Motor |
|
|
|
|
|
|
|
|
|
| |
FP1 | — Water Coil Freeze Protection Sensor |
|
|
|
|
|
|
|
|
|
| Relay/Contactor Coil |
FP2 | — Air Coil Freeze Protection Sensor |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| ||
HP | — |
|
|
|
|
|
|
|
|
|
|
|
HWG | — Hot Water Generator |
|
|
|
|
|
|
|
|
|
| Thermistor |
JW | — Jumper Wire |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
LOC | — Loss of Charge Pressure Switch |
|
|
|
|
|
|
|
|
|
| Condensate Pan |
LWT | — Leaving Water Temperature |
|
|
|
|
|
|
|
|
|
|
|
MV | — Motorized Valve |
|
|
|
|
|
|
|
|
|
| Circuit Breaker |
NEC | — National Electric Code |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| ||
P1 | — Field Wiring Terminal Block |
|
|
|
|
|
|
|
|
|
| Ground |
*Optional.
G
Solenoid Coil
Relay Contacts - N.C.
Relay Contacts - N.O.
Capacitor
Temperature Switch
Low Pressure Switch
High Pressure Switch
Wire Nut
Splice Cap
LED
NOTES:
1.Compressor and blower motor thermally protected internally.
2.All wiring to the unit must comply with NEC and local codes.
3.208/230 v transformer will be connected for 208 v operation. For 230 v operation, disconnect RED lead at L1 and attach ORANGE lead to L1. Insulate open end of RED lead. Transformer is energy limiting or may have circuit breaker.
4.FP1 thermistor provides freeze protection for water. When using antifreeze solutions, cut JW3 jumper.
5.Check installation wiring information for specific thermostat hookup. Refer to thermostat installation instructions for wiring to the unit. Thermostat wiring must be “Class 1” and voltage rating equal to or greater than unit supply voltage.
6.
7.Transformer secondary ground via Complete C board standoffs and screws to control box. (Ground available from top two standoffs as shown.)
8.Aquastat is supplied with unit and must be wired in series with the hot leg to the pump. Aquastat is rated for voltage up to 277 v.
COMPLETE C CONTROLLER FAULT CODES
DESCRIPTION OF OPERATION | LED | ALARM RELAY | |
Normal Mode | ON | Open | |
Normal Mode with UPS Warning | ON | Cycle (Closed 5 Sec. | |
Open 25 Sec.) | |||
|
| ||
Complete C is | OFF | Open | |
Fault Retry | Slow Flash | Open | |
Lockout | Fast Flash | Closed | |
Over/Under Voltage Shutdown | Slow Flash | Open | |
(Closed After 15 Min.) | |||
|
| ||
Test | Flashing Code 1 | Cycling Code 1 | |
Test | Flashing Code 2 | Cycling Code 2 | |
Test | Flashing Code 3 | Cycling Code 3 | |
Test | Flashing Code 4 | Cycling Code 4 | |
Test | Flashing Code 5 | Cycling Code 5 | |
Test | Flashing Code 6 | Cycling Code 6 | |
Test | Flashing Code 7 | Cycling Code 7 | |
in Memory | |||
|
| ||
Test | Flashing Code 8 | Cycling Code 8 | |
Swapped FP1/FP2 Lockout | Flashing Code 9 | Cycling Code 9 |
Fig. 17 — Units with Complete C ECM Blower, Three-Phase (208/230 V)
16