Table 39 — WSHP Troubleshooting (cont)
| FAULT |
| HEATING | COOLING | POSSIBLE CAUSE | SOLUTION |
Condensate Fault — |
| X | X | Blocked drain | Check for blockage and clean drain. | |
Code 6 |
|
|
|
|
|
|
|
| X | X | Improper trap | Check trap dimensions and location ahead of vent. | |
|
|
| ||||
|
|
|
| X | Poor drainage | Check for piping slope away from unit. |
|
|
|
|
|
| Check slope of unit toward outlet. |
|
|
|
|
|
| Poor venting. Check vent location. |
|
|
|
| X | Moisture on sensor | Check for moisture shorting to air coil. |
Over/Under Voltage — |
| X | X | Under voltage | Check power supply and 24 vac voltage before and during | |
Code 7 (Auto Resetting) |
|
|
|
| operation. | |
|
|
|
|
|
| Check power supply wire size. |
|
|
|
|
|
| Check compressor starting. |
|
|
|
|
|
| Check 24 vac and unit transformer tap for correct power supply |
|
|
|
|
|
| voltage. |
|
|
| X | X | Over voltage | Check power supply voltage and 24 vac before and during operation. |
|
|
|
|
|
| Check 24 vac and unit transformer tap for correct power supply |
|
|
|
|
|
| voltage. |
Performance Monitor — |
| X |
| Heating mode FP2>125 F | Check for poor airflow or overcharged unit. | |
Code 8 |
|
|
|
|
|
|
|
|
| X | Cooling mode FP1>125 F OR | Check for poor water flow or airflow. | |
|
|
|
| |||
|
|
|
|
| FP2< 40 F |
|
FP1 and FP2 Thermistors |
| X |
| FP1 temperature is higher | Swap FP1 and FP2 thermistors. | |
— Code 9 |
|
|
| than FP2 temperature. |
| |
|
|
|
| X | FP2 temperature is higher | Swap FP1 and FP2 thermistors. |
|
|
|
|
| than FP1 temperature. |
|
No Fault Code Shown |
| X | X | No compressor operation | See Scroll Compressor Rotation section. | |
|
|
| X | X | Compressor overload | Check and replace if necessary. |
|
|
| X | X | Control board | Reset power and check operation. |
Swapped Thermistor — |
| X | X | FP1 and FP2 swapped | Reverse position of thermistors. | |
Code 9 |
|
|
|
|
|
|
Unit Short Cycles |
| X | X | Dirty air filter | Check and clean air filter. | |
|
|
| X | X | Unit in 'Test Mode' | Reset power or wait 20 minutes for auto exit. |
|
|
| X | X | Unit selection | Unit may be oversized for space. Check sizing for actual load of space. |
|
|
| X | X | Compressor overload | Check and replace if necessary. |
Only Fan Runs |
| X | X | Thermostat position | Ensure thermostat set for heating or cooling operation. | |
|
|
| X | X | Unit locked out | Check for lockout codes. Reset power. |
|
|
| X | X | Compressor overload | Check compressor overload. Replace if necessary. |
|
|
| X | X | Thermostat wiring | Check Y and W wiring at heat pump. Jumper Y and R for compressor |
|
|
|
|
|
| operation in Test mode. |
Only Compressor Runs |
| X | X | Thermostat wiring | Check G wiring at heat pump. Jumper G and R for fan operation. | |
|
|
|
|
|
| Check Y and W wiring at heat pump. Jumper Y and R for compressor |
|
|
|
|
|
| operation in test mode. |
|
|
| X | X | Fan motor relay | Jumper G and R for fan operation. Check for line voltage across BR |
|
|
|
|
|
| contacts. |
|
|
|
|
|
| Check fan power enable relay operation (if present). |
|
|
| X | X | Fan motor | Check for line voltage at motor. Check capacitor. |
Unit Does Not Operate in |
|
| X | Reversing valve | Set for cooling demand and check 24 vac on RV coil and at control. | |
Cooling |
|
|
|
|
| |
|
|
|
| If RV is stuck, run high pressure up by reducing water flow and while | ||
|
|
|
|
|
| |
|
|
|
|
|
| operating, engage and disengage RV coil voltage to push valve. |
|
|
|
| X | Thermostat setup | Check for 'O' RV setup not 'B'. |
|
|
|
| X | Thermostat wiring | Check O wiring at heat pump. Jumper O and R for RV coil 'Click'. |
Insufficient Capacity/ |
| X | X | Dirty filter | Replace or clean. | |
Not Cooling or Heating |
|
|
|
|
| |
| X |
| Reduced or no airflow in | Check for dirty air filter and clean or replace. | ||
Properly |
|
| ||||
|
|
| heating | Check fan motor operation and airflow restrictions. | ||
|
|
|
|
| ||
|
|
|
|
|
| |
|
|
|
|
|
| External static too high. Check blower performance per |
|
|
|
|
|
| Tables |
|
|
|
| X | Reduced or no airflow in | Check for dirty air filter and clean or replace. |
|
|
|
|
| cooling | Check fan motor operation and airflow restrictions. |
|
|
|
|
|
| |
|
|
|
|
|
| External static too high. Check blower performance per |
|
|
|
|
|
| Tables |
|
|
| X | X | Leaky ductwork | Check supply and return air temperatures at the unit and at distant duct |
|
|
|
|
|
| registers if significantly different, duct leaks are present. |
|
|
| X | X | Low refrigerant charge | Check superheat and subcooling per Tables |
|
|
| X | X | Restricted metering device | Check superheat and subcooling per Tables |
|
|
|
| X | Defective reversing valve | Set for cooling demand and check 24 vac on RV coil and at control. |
|
|
|
|
|
| If RV is stuck, run high pressure up by reducing water flow and while |
|
|
|
|
|
| operating, engage and disengage RV coil voltage to push valve. |
|
|
| X | X | Thermostat improperly located | Check location and for air drafts behind thermostat. |
|
|
| X | X | Unit undersized | Recheck loads and sizing check sensible cooling load and heat pump |
|
|
|
|
|
| capacity. |
|
|
| X | X | Scaling in water heat exchanger | Perform condenser cleaning. |
|
|
| X | X | Inlet water too hot or cold | Check load, loop sizing, loop backfill, ground moisture. |
| LEGEND |
|
|
|
| |
LED | — |
|
|
|
| |
RV | — Reversing Valve |
|
|
|
| |
TXV | — Thermostatic Expansion Valve |
|
|
|
56