Carrier 50PSH Condensate Fault, Code 7 Auto Resetting, FP1 and FP2 Thermistors, Only Fan Runs

Page 56

Table 39 — WSHP Troubleshooting (cont)

 

FAULT

 

HEATING

COOLING

POSSIBLE CAUSE

SOLUTION

Condensate Fault —

 

X

X

Blocked drain

Check for blockage and clean drain.

Code 6

 

 

 

 

 

 

 

 

X

X

Improper trap

Check trap dimensions and location ahead of vent.

 

 

 

 

 

 

 

X

Poor drainage

Check for piping slope away from unit.

 

 

 

 

 

 

Check slope of unit toward outlet.

 

 

 

 

 

 

Poor venting. Check vent location.

 

 

 

 

X

Moisture on sensor

Check for moisture shorting to air coil.

Over/Under Voltage —

 

X

X

Under voltage

Check power supply and 24 vac voltage before and during

Code 7 (Auto Resetting)

 

 

 

 

operation.

 

 

 

 

 

 

Check power supply wire size.

 

 

 

 

 

 

Check compressor starting.

 

 

 

 

 

 

Check 24 vac and unit transformer tap for correct power supply

 

 

 

 

 

 

voltage.

 

 

 

X

X

Over voltage

Check power supply voltage and 24 vac before and during operation.

 

 

 

 

 

 

Check 24 vac and unit transformer tap for correct power supply

 

 

 

 

 

 

voltage.

Performance Monitor —

 

X

 

Heating mode FP2>125 F

Check for poor airflow or overcharged unit.

Code 8

 

 

 

 

 

 

 

 

 

X

Cooling mode FP1>125 F OR

Check for poor water flow or airflow.

 

 

 

 

 

 

 

 

 

FP2< 40 F

 

FP1 and FP2 Thermistors

 

X

 

FP1 temperature is higher

Swap FP1 and FP2 thermistors.

— Code 9

 

 

 

than FP2 temperature.

 

 

 

 

 

X

FP2 temperature is higher

Swap FP1 and FP2 thermistors.

 

 

 

 

 

than FP1 temperature.

 

No Fault Code Shown

 

X

X

No compressor operation

See Scroll Compressor Rotation section.

 

 

 

X

X

Compressor overload

Check and replace if necessary.

 

 

 

X

X

Control board

Reset power and check operation.

Swapped Thermistor —

 

X

X

FP1 and FP2 swapped

Reverse position of thermistors.

Code 9

 

 

 

 

 

 

Unit Short Cycles

 

X

X

Dirty air filter

Check and clean air filter.

 

 

 

X

X

Unit in 'Test Mode'

Reset power or wait 20 minutes for auto exit.

 

 

 

X

X

Unit selection

Unit may be oversized for space. Check sizing for actual load of space.

 

 

 

X

X

Compressor overload

Check and replace if necessary.

Only Fan Runs

 

X

X

Thermostat position

Ensure thermostat set for heating or cooling operation.

 

 

 

X

X

Unit locked out

Check for lockout codes. Reset power.

 

 

 

X

X

Compressor overload

Check compressor overload. Replace if necessary.

 

 

 

X

X

Thermostat wiring

Check Y and W wiring at heat pump. Jumper Y and R for compressor

 

 

 

 

 

 

operation in Test mode.

Only Compressor Runs

 

X

X

Thermostat wiring

Check G wiring at heat pump. Jumper G and R for fan operation.

 

 

 

 

 

 

Check Y and W wiring at heat pump. Jumper Y and R for compressor

 

 

 

 

 

 

operation in test mode.

 

 

 

X

X

Fan motor relay

Jumper G and R for fan operation. Check for line voltage across BR

 

 

 

 

 

 

contacts.

 

 

 

 

 

 

Check fan power enable relay operation (if present).

 

 

 

X

X

Fan motor

Check for line voltage at motor. Check capacitor.

Unit Does Not Operate in

 

 

X

Reversing valve

Set for cooling demand and check 24 vac on RV coil and at control.

Cooling

 

 

 

 

 

 

 

 

 

If RV is stuck, run high pressure up by reducing water flow and while

 

 

 

 

 

 

 

 

 

 

 

 

operating, engage and disengage RV coil voltage to push valve.

 

 

 

 

X

Thermostat setup

Check for 'O' RV setup not 'B'.

 

 

 

 

X

Thermostat wiring

Check O wiring at heat pump. Jumper O and R for RV coil 'Click'.

Insufficient Capacity/

 

X

X

Dirty filter

Replace or clean.

Not Cooling or Heating

 

 

 

 

 

 

X

 

Reduced or no airflow in

Check for dirty air filter and clean or replace.

Properly

 

 

 

 

 

heating

Check fan motor operation and airflow restrictions.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External static too high. Check blower performance per

 

 

 

 

 

 

Tables 11-13.

 

 

 

 

X

Reduced or no airflow in

Check for dirty air filter and clean or replace.

 

 

 

 

 

cooling

Check fan motor operation and airflow restrictions.

 

 

 

 

 

 

 

 

 

 

 

 

External static too high. Check blower performance per

 

 

 

 

 

 

Tables 11-13.

 

 

 

X

X

Leaky ductwork

Check supply and return air temperatures at the unit and at distant duct

 

 

 

 

 

 

registers if significantly different, duct leaks are present.

 

 

 

X

X

Low refrigerant charge

Check superheat and subcooling per Tables 20-30.

 

 

 

X

X

Restricted metering device

Check superheat and subcooling per Tables 20-30. Replace.

 

 

 

 

X

Defective reversing valve

Set for cooling demand and check 24 vac on RV coil and at control.

 

 

 

 

 

 

If RV is stuck, run high pressure up by reducing water flow and while

 

 

 

 

 

 

operating, engage and disengage RV coil voltage to push valve.

 

 

 

X

X

Thermostat improperly located

Check location and for air drafts behind thermostat.

 

 

 

X

X

Unit undersized

Recheck loads and sizing check sensible cooling load and heat pump

 

 

 

 

 

 

capacity.

 

 

 

X

X

Scaling in water heat exchanger

Perform condenser cleaning.

 

 

 

X

X

Inlet water too hot or cold

Check load, loop sizing, loop backfill, ground moisture.

 

LEGEND

 

 

 

 

LED

Light-Emitting Diode

 

 

 

 

RV

Reversing Valve

 

 

 

 

TXV

Thermostatic Expansion Valve

 

 

 

56

Image 56
Contents Installation, Start-Up, Service Instructions ContentsGeneral Safety ConsiderationsInstallation Physical Data 50PSH, PSV, PSD018-070 Units Typical Installation 50PSH Unit ASP BSPCAP Code Return Discharge CSP50PSV Dimensional Data A50-7846ef HWR Hot Water Reheat Left Hand Right HandSide Discharge Back DischargeInstall Condensate Drain Mount the UnitTrap Condensate Drain Connection Material Water Quality GuidelinesOpen Loop and Recirculating Well Typical Ground-Water Piping Installation Metal Hose Minimum Bend RadiiWire Field Power Supply Supply/Return Hose KitComplete C Controller Fault Codes Description of Operation LED Alarm RelayTrans AstatWire Number BMCCompr Yellow REDECM LWTA50-8363 Units with ECM, Complete C and LON Controller 460A50-8364 Units with ECM, Deluxe D and LON Controller 460Mves SATHpws WHSP-OPEN A50 83548356 LWT A50-8380 Wshp Open Control50PSH, PSV, PSD Electrical Data PSC Motor 50PSH, PSV, PSD Electrical Data PSC High-Static Motor50PSH, PSV, PSD Electrical Data, ECM Motor Wire Field Controls Low Voltage Field WiringRnet Wiring Specifications A50-8441A50-8442 Field-Supplied Sensors for Wshp Open ControllerRnet Wiring Wire TerminalOperate ECM Interface Board A50-8443Setting Size ECM Blower Motor Performance DataRated MIN FAN Unit Airflow CFM Speed SizeCoil Units with Reheat ESP Loss Face Velocity FPMComplete C Control Jumper Settings Deluxe D Control Jumper SettingsPRE-START-UP Field Selectable InputsDIP Switch Block S2 Accessory 1 Relay Options DIP Switch Block S2 Accessory 2 Relay OptionsHumidistat/Dehumidistat Logic Deluxe D DIP Switch Settings VACHWR Operating Modes A50-8145Unit Start-Up Cooling Mode START-UPOperating Limits Operating Limits 50PSH, PSV, PSD UnitsUnit Start-Up Heating Mode Water Temperature Change Through Heat ExchangerCooling Heating Water Flow Rate GPM Rise F Drop F Water Flow TempGPM/ton Pressure Heat Cooling Rise Drop Psig Flow Flow Unit Start-Up with Wshp Open Controls BACview6 Display Interface50PSH, PSV, PSD Water Water Temperature F Flow 50PSH, PSV, PSD Coaxial Water Pressure DropUnit Size GPMApproximate Fluid Volume gal Per 100 Ft of Pipe Antifreeze Percentages by VolumeOperation Units with Aquazone Complete C ControlUnits with HWR Option Units with Wshp Open Multiple ProtocolPage Page Off LED Status Description of Operation Alarm RelayComplete C and Deluxe D Board System Test Complete C Control LED Code Fault Descriptions LED Code Fault DescriptionAquazone Deluxe D Control LED Indica Description Status LED Test LEDService Troubleshooting Refrigerant ChargingAir Coil Fan Motor Removal Replacing the Wshp Open Controller’s BatFP1 and FP2 Thermistor Location Page ECM Troubleshooting Fault Description SolutionECM Pin Connectors A50-8448ECM Troubleshooting Flow Diagram A50-8447Wshp Troubleshooting Fault Heating Cooling Possible Cause SolutionGood Practices TXVCondensate Fault Code 7 Auto ResettingNo Fault Code Shown CodeTemperature in Heating High Head PressureLow Suction Pressure Low Discharge AirAppendix a Wshp Open Screen Configuration Appendix a Wshp Open Screen Configuration Set Points Weekly ScheduleException Schedules 1Test Appendix a Wshp Screen Open ConfigurationService Screen Name Configuration ServicePoint Name Password Editable Range Default Level Alarm LinkagePage Page Copyright 2009 Carrier Corporation 50PSH,PSV,PSD START-UP Checklist II. START-UPHeating Cycle Analysis Cooling Cycle AnalysisA50-8494 A50-8495