Unit Start-Up with WSHP Open Controls
The WSHP Open is a
NOTE: If the WSHP Open control has lost its programming, all display pixels will be displayed on the SPT sensor. See the WSHP Third Party Integration Guide.
When the unit is OFF, the SPT sensor will indicate OFF. When power is applied, the SPT sensor will indicate tempera- ture in the space at 78 F.
To
1.To plug in the BACview6 handheld display into a SPT sensor, point the two ears on the connector up and tilt the bottom of the plug toward you. Insert the plug up into the SPT sensor while pushing the bottom of the plug away from you.
2.BACview6 should respond with "Establishing Connec- tion." The Home screen will then appear on the display showing operating mode and space temperature. Press any button to continue.
See Appendix A — WSHP Open Screen Configuration for the hierarchal structure of the WSHP Open controller. All functions of the controller can be set from the Home screen.
3.When the Login is requested, type 1111 and push the OK softkey. The Logout will then be displayed to indicate the password was accepted.
4.To set the Clock if it is not already displayed:
a.Select System Settings from the Home screen, then press Clockset.
b.Scroll to hour, minute and second using the arrow keys. Use the number keypad to set actual time.
c.Scroll to day, month and year using arrow keys. Use number keypad to set date.
5.To set Daylight Savings Time (DST):
a.Push the DST softkey. The display will indicate 02:00:060 which is equal to 2:00AM.
b.To program the beginning and end dates, scroll down to the beginning month and press the enter key. The softkeys (INCR and DECR) will activate to increment the month in either direction, Jan, Feb, March, etc.
c.Use number keys to select the day of month and year.
d.Push the OK softkey to finalize the data.
6.To view configuration settings:
a.Select the Config softkey.
b.Select the Service Config softkey. Scroll through the factory settings by using the up and down arrow keys. See below for factory settings.
Only the following settings will need to be checked.
•# of Fan Speeds — This should be set to "1" for units with PSC motors and set to "3" for units with ECM motors.
•Compressor Stages — This should be set to "1."
•Factory Dehumidification Reheat Coil — This should be set to "none" unless the modulating hot water reheat option is supplied in the unit, then set to "installed."
•The condenser water limit needs to be verified depending on design parameters and application, whether geothermal or boiler/tower.
7.To view unit configuration settings:
a.Select the Unit Configuration softkey, then select Unit.
b.Scroll through the unit settings by using the up and down arrow keys. Unit settings include:
•Fan Mode: Default Continuous
•Fan Delay:
•Minimum SAT Cooling: Default 50 F
•Maximum SAT Heating: Default 110 F
•Filter Service Alarm: Must be set from 0 to 9999 hr
8.To set local schedules:
a.Select the Schedule softkey from the Configuration screen, then press enter.
b.Select Weekly, then press enter (7 schedules available).
c.Select day and press enter.
d.Press enter again and select ADD or DEL (DECR or INCR) set schedule.
e.Enter ON/OFF time, then press continue.
Fig. 35 — BACview6 Display Interface