Carrier PSV, PSD006-070, 50PSH instruction manual Wire Field Power Supply, Supply/Return Hose Kit

Page 13

Optional pressure-rated hose assemblies designed specifi- cally for use with Carrier units are available. Similar hoses can be obtained from alternate suppliers. Supply and return hoses are fitted with swivel-joint fittings at one end to prevent kink- ing during installation.

CAUTION

Backup wrench is required when tightening water connec- tions to prevent water line damage. Failure to use a backup wrench could result in equipment damage.

Refer to Fig. 14 for an illustration of a supply/return hose kit. Male adapters secure hose assemblies to the unit and risers. Install hose assemblies properly and check them regularly to avoid system failure and reduced service life.

Step 8 — Wire Field Power Supply

WARNING

To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation.

CAUTION

Use only copper conductors for field-installed electrical wiring. Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors could result in equipment damage.

All field-installed wiring, including the electrical ground, MUST comply with the National Electrical Code (NEC) as well as applicable local codes. In addition, all field wiring must conform to the Class II temperature limitations described in the NEC.

Refer to unit wiring diagrams Fig. 15-25 for a schematic of the field connections, which must be made by the installing (or electrical) contractor. Refer to Tables 4-6 for fuse sizes.

Consult the unit wiring diagram located on the inside of the compressor access panel to ensure proper electrical hookup. The installing (or electrical) contractor must make the field connections when using field-supplied disconnect.

Operating voltage must be the same voltage and phase as shown in electrical data shown in Tables 4-6.

Make all final electrical connections with a length of flexi- ble conduit to minimize vibration and sound transmission to the building.

POWER CONNECTION — Make line voltage connection by connecting the incoming line voltage wires to the line side of the compressor contactor terminal as shown in Fig. 26. See Tables 4-6 for amperage ratings to provide cor- rect wire and maximum overcurrent protection sizing.

SUPPLY VOLTAGE — Operating voltage to unit must be within voltage range indicated on unit nameplate.

On 3-phase units, voltages under load between phases must be balanced within 2%. Use the following formula to deter- mine the percentage voltage imbalance:

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

 

average voltage

Example: Supply voltage is 460-3-60.

AB = 452 volts BC = 464 volts AC = 455 volts

Average Voltage = 452 + 464 + 455 3

= 1371 3

= 457

Determine maximum deviation from average voltage:

(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v. Determine percent voltage imbalance.

% Voltage Imbalance =

100 x

7

457

=

1.53%

 

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electri- cal components.

NOTE: If more than 2% voltage imbalance is present, contact your local electric utility.

208-VOLT OPERATION — All 208-230 volt units are factory wired for 208 volts. The transformers may be switched to 230-volt operation by switching the red (208 volt) wire with the orange (230 volt) wire at the L1 terminal.

460-VOLT OPERATION — Units using 460-v and an ECM (electronically commutated motor) fan motor, modulat- ing HWR, and/or internal secondary pump will require a neutral wire from the supply side in order to feed accessory with 265-v.

A50-7734

Swivel

 

Brass

 

Brass

 

Rib Crimped

Fitting

 

Fitting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Length

(2 ft Length Standard)

MPT

Fig. 14 — Supply/Return Hose Kit

13

Image 13
Contents Contents Installation, Start-Up, Service InstructionsInstallation Safety ConsiderationsGeneral Physical Data 50PSH, PSV, PSD018-070 Units Typical Installation 50PSH Unit BSP ASPCAP Code Return Discharge CSP50PSV Dimensional Data HWR Hot Water Reheat Left Hand Right Hand A50-7846efBack Discharge Side DischargeMount the Unit Install Condensate DrainTrap Condensate Drain Connection Open Loop and Recirculating Well Water Quality GuidelinesMaterial Metal Hose Minimum Bend Radii Typical Ground-Water Piping InstallationSupply/Return Hose Kit Wire Field Power SupplyDescription of Operation LED Alarm Relay Complete C Controller Fault CodesTrans AstatBMC Wire NumberCompr Yellow REDLWT ECMUnits with ECM, Complete C and LON Controller 460 A50-8363Units with ECM, Deluxe D and LON Controller 460 A50-8364Hpws SATMves WHSP-OPEN 8354 A508356 LWT Wshp Open Control A50-838050PSH, PSV, PSD Electrical Data PSC High-Static Motor 50PSH, PSV, PSD Electrical Data PSC Motor50PSH, PSV, PSD Electrical Data, ECM Motor Low Voltage Field Wiring Wire Field ControlsA50-8441 Rnet Wiring SpecificationsA50-8442 Field-Supplied Sensors for Wshp Open ControllerWire Terminal Rnet WiringOperate ECM Interface Board A50-8443ECM Blower Motor Performance Data Setting SizeUnit Airflow CFM Speed Size Rated MIN FANCoil Units with Reheat ESP Loss Face Velocity FPMDeluxe D Control Jumper Settings Complete C Control Jumper SettingsPRE-START-UP Field Selectable InputsDIP Switch Block S2 Accessory 2 Relay Options DIP Switch Block S2 Accessory 1 Relay OptionsHumidistat/Dehumidistat Logic Deluxe D DIP Switch Settings VACA50-8145 HWR Operating ModesSTART-UP Unit Start-Up Cooling ModeOperating Limits Operating Limits 50PSH, PSV, PSD UnitsWater Temperature Change Through Heat Exchanger Unit Start-Up Heating ModeCooling Heating Water Flow Rate GPM Rise F Drop F Water Flow TempGPM/ton Pressure Heat Cooling Rise Drop Psig Flow Flow BACview6 Display Interface Unit Start-Up with Wshp Open Controls50PSH, PSV, PSD Coaxial Water Pressure Drop 50PSH, PSV, PSD Water Water Temperature F FlowUnit Size GPMAntifreeze Percentages by Volume Approximate Fluid Volume gal Per 100 Ft of PipeOperation Units with Aquazone Complete C ControlUnits with Wshp Open Multiple Protocol Units with HWR OptionPage Page Complete C and Deluxe D Board System Test LED Status Description of Operation Alarm RelayOff LED Code Fault Description Complete C Control LED Code Fault DescriptionsAquazone Deluxe D Control LED Indica Description Status LED Test LEDService Refrigerant Charging TroubleshootingAir Coil Fan Motor Removal Replacing the Wshp Open Controller’s BatFP1 and FP2 Thermistor Location Page Fault Description Solution ECM TroubleshootingA50-8448 ECM Pin ConnectorsA50-8447 ECM Troubleshooting Flow DiagramFault Heating Cooling Possible Cause Solution Wshp TroubleshootingGood Practices TXVCode 7 Auto Resetting Condensate FaultNo Fault Code Shown CodeHigh Head Pressure Temperature in HeatingLow Suction Pressure Low Discharge AirAppendix a Wshp Open Screen Configuration Appendix a Wshp Open Screen Configuration Weekly Schedule Set PointsException Schedules 1Service Appendix a Wshp Screen Open ConfigurationTest Point Name Password Editable Range Default Level Configuration ServiceScreen Name Linkage AlarmPage Page Copyright 2009 Carrier Corporation II. START-UP 50PSH,PSV,PSD START-UP ChecklistCooling Cycle Analysis Heating Cycle AnalysisA50-8494 A50-8495