APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)
SCREEN NAME | POINT NAME | PASSWORD | EDITABLE | RANGE | DEFAULT | NOTES | ||
LEVEL | ||||||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| Auto= Intermittant operation during both | |
|
|
|
|
|
|
| occupied and unoccupied periods/ | |
|
|
|
|
| Auto/Continuous/ |
| Continuous = Intermittant during unoccupied | |
|
| Fan Mode |
| X | Continuous | periods and continuous during occupied | ||
|
|
| Always On | |||||
|
|
|
|
|
| periods/Always on = fan operates | ||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| continuously during both occupied and | |
|
|
|
|
|
|
| unoccupied periods | |
|
| Fan On Delay |
| X | 0 - 30 sec | 10 sec | Defines the delay time before the fan begins | |
|
|
| to operate after heating or cooling is started | |||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| Defines the amount of time the fan will | |
|
| Fan Off Delay |
| X | 0 - 180 sec | 45 sec | continue to operate after heating or | |
|
|
|
|
|
|
| cooling is stopped | |
|
| Heating Enable |
| X | Disable/Enable | Enable | Provides capability to manually | |
|
|
| disable heating operation | |||||
|
|
|
|
|
|
| ||
|
| Cooling Enable |
| X | Disable/Enable | Enable | Provides capability to manually | |
|
|
| disable cooling operation | |||||
|
|
|
|
|
|
| ||
|
| Minimum SAT in |
| X | 40 - 60 ° F | 50 ° F | Defines the minimum acceptable operating | |
|
| Cooling |
| temperature for the Supply Air | ||||
Configuration |
|
|
|
| ||||
Maximum SAT in |
| X | 80 - 140 ° F | 110 ° F | Defines the maximum acceptable operating | |||
|
|
| ||||||
| → | Heating |
| temperature for the Supply Air | ||||
| Admin Password |
|
|
| ||||
|
|
|
|
| Normally set to 100% if 2 position damper | |||
|
| Damper Ventilation | level access only |
|
|
| ||
|
| X | 0 - 100% | 100% | type or set to minimum ventilation position if | |||
| Unit | Position |
| |||||
|
|
|
|
| damper type = DCV | |||
Configuration |
|
|
|
|
| |||
DCV Maximum Vent |
| X | 0 - 100% | 100% | Usually set at 100% - Used to limit maximum | |||
|
|
| ||||||
|
| Position |
| damper opening in DCV mode | ||||
|
|
|
|
|
| |||
|
| Filter Alarm Timer |
| X | 0 - 9999 hrs | 0 hrs | Disables Filter Alarm if set to 0 | |
|
| Pushbutton Override |
| X | Disable/Enable | Enable | Enables Override Feature on Rnet sensor | |
|
| SPT Sensor Set Point |
| X | Disable/Enable | Enable | Enables Set Point adjustment capability | |
|
| Adjustment |
| on Rnet Sensor | ||||
|
|
|
|
|
| |||
|
| Lockout Cooling if |
|
| Cooling is locked out when OAT is less than | |||
|
|
| X | configured value and OAT is actively being | ||||
|
| OAT < |
| |||||
|
|
|
|
|
| broadcast | ||
|
|
|
|
|
|
| ||
|
| Lockout Heating if |
|
| 35 - 150 ° F | 150 ° F | Heating is locked out when OAT is greater | |
|
|
| X | than configured value and OAT is actively | ||||
|
| OAT > |
| |||||
|
|
|
|
|
| being broadcast | ||
|
|
|
|
|
|
| ||
|
| Power Fail Restart |
| X | 0 - 600 sec | 60 sec | Delay before equipment starts | |
|
| Delay |
| |||||
|
|
|
|
|
|
| ||
|
| Occupancy Schedules |
| X | Disable/Enable | Enable | Enables unit occupied | |
|
| Set Point Separation |
| X | 2 - 9 ° F | 4 ° F | Used to enforce minimum | |
|
|
| set point separation | |||||
|
|
|
|
|
|
| ||
|
| Test Mode |
| X | Disable/Enable | Disable | Used to enable test mode. Will automatically | |
|
|
| reset to disable after 1 hour | |||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| Used to test all fan speeds. Sequences fan | |
|
| Fan Test |
| X | Disable/Enable | Disable | from low to high and operates each speed for | |
|
|
|
|
|
|
| 1 minute. Resets to disable on completion | |
|
| Fan Speed |
|
| Off/Low Speed/Medium |
| Displays current fan operation | |
|
|
|
| Speed/High Speed/On |
| |||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| Used to test compressor cooling and heating | |
|
|
|
|
|
|
| operation. Sequences cooling stage 1, then | |
|
| Compressor Test |
| X | Disable/Enable | Disable | stage 2, then heating stage 2 and reduces | |
|
|
|
|
|
|
| capacity to stage 1. Operates for 1 minute per | |
|
|
|
|
|
|
| step. Resets to disable on completion. | |
Configuration |
|
|
|
|
| Used to test dehumification mode - | ||
| → | Dehumidification Test |
| X | Disable/Enable | Disable | Operates for 2 minutes. Resets to | |
|
|
|
|
|
| disable on completion. | ||
|
|
|
|
|
|
| ||
|
|
| Admin Password |
| Inactive/Heating/Cooling/ |
|
| |
| Service | Testing Compressor |
| Dehumidify/TimeGard |
| Displays compressor test mode | ||
| level access only |
|
| |||||
| → |
|
| Wait |
|
| ||
|
|
|
|
|
| |||
|
|
|
|
|
| Used to test auxiliary heat. | ||
|
| Aux Heating Test |
| X | Disable/Enable | Disable | Sequences fan on and enables | |
| Test |
| heating coil for 1 minute. Resets to | |||||
|
|
|
|
|
| |||
|
|
|
|
|
| disable on completion | ||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| Used to test entering/return air water loop | |
|
| H2O Economizer Test |
| X | Disable/Enable | Disable | economizer coil operation. Sequences fan on | |
|
|
| and opens economizer coil water valve for 1 | |||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| minute. Resets to disable on completion | |
|
| Preposition OA |
| X | Disable/Enable | Disable | Used to preposition OA damper | |
|
| Damper |
| actuator to set proper preload | ||||
|
|
|
|
|
| |||
|
| Open Vent |
| X | Disable/Enable | Disable | Used to test OA damper operation | |
|
| Damper 100% |
| |||||
|
|
|
|
|
|
| ||
|
| SAT |
|
| ° F |
| Displays SAT | |
|
| LCWT |
|
| ° F |
| Displays Leaving Condenser | |
|
|
|
|
| Water Temperature | |||
|
|
|
|
|
|
| ||
| LEGEND |
|
|
|
|
| ||
BAS — Building Automation System |
|
|
|
|
| |||
DCV | — Demand Controlled Ventilation |
|
|
|
| |||
IAQ | — Indoor Air Quality |
|
|
|
|
| ||
OAT | — Outdoor Air Temperature |
|
|
|
|
| ||
RH | — Relative Humidity |
|
|
|
|
| ||
SAT — Supply Air Temperature |
|
|
|
|
| |||
SPT | — Space Temperature |
|
|
|
|
| ||
TPI | — Third Party Integration |
|
|
|
|
|
61