Carrier PSV, PSD006-070, 50PSH instruction manual Rated MIN FAN, Unit Airflow CFM Speed Size, Fpm

Page 31

Table 12 — PSC Blower Motor Performance Data

50PS

RATED

MIN

FAN

 

 

 

 

AIRFLOW (cfm) AT EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

UNIT

AIRFLOW

CFM

SPEED

0.00

0.05

0.10

0.15

 

0.20

0.25

0.30

0.35

0.40

0.45

0.50

0.60

0.70

0.80

0.90

1.00

SIZE

 

 

 

 

HI

704

708

711

702

 

693

692

690

683

675

658

640

598

515

 

 

 

 

 

 

MED

602

601

599

590

 

581

583

585

579

573

560

547

492

 

 

 

 

018

600

450

LO

531

529

527

522

 

517

512

506

501

495

479

462

 

 

 

 

 

 

 

 

HS HI

894

886

877

859

 

841

827

812

786

760

744

728

659

 

 

 

 

 

 

 

HS MED

765

760

755

747

 

738

725

711

690

668

654

640

602

 

 

 

 

 

 

 

HS LO

683

672

661

649

 

636

616

596

584

571

560

549

 

 

 

 

 

 

 

 

HI

965

960

954

943

 

931

923

914

898

882

862

842

794

725

635

 

 

 

 

 

MED

841

833

825

817

 

809

800

790

777

763

747

731

686

623

 

 

 

024

850

600

LO

723

715

707

703

 

698

689

680

668

656

642

627

 

 

 

 

 

 

 

 

HS HI

1271

1250

1229

1207

 

1185

1164

1143

1118

1093

1061

1029

953

875

753

 

 

 

 

 

HS MED

1048

1037

1025

1016

 

1007

994

981

962

943

915

886

822

731

626

 

 

 

 

 

HS LO

890

887

884

879

 

874

865

855

842

829

809

789

726

660

 

 

 

 

 

 

HI

1271

1250

1229

1207

 

1185

1164

1143

1118

1093

1061

1029

953

875

753

 

 

 

 

 

MED

1048

1037

1025

1016

 

1007

994

981

962

943

915

886

822

 

 

 

 

030

950

750

LO

890

887

884

879

 

874

865

855

842

829

809

789

 

 

 

 

 

 

 

 

HS HI

1439

1411

1383

1355

 

1327

1297

1266

1232

1198

1160

1122

1041

943

830

 

 

 

 

 

HS MED

1186

1174

1162

1151

 

1140

1126

1112

1089

1065

1039

1013

946

870

762

 

 

 

 

 

HS LO

1039

1038

1036

1028

 

1020

1009

997

983

968

946

923

866

798

 

 

 

 

 

 

HI

1411

1407

1402

1390

 

1378

1370

1361

1326

1290

1248

1205

1083

942

 

 

 

 

 

 

MED

1171

1164

1156

1145

 

1133

1113

1092

1064

1035

997

958

 

 

 

 

 

036

1250

900

LO

983

967

950

943

 

936

936

 

 

 

 

 

 

 

 

 

 

 

 

 

HS HI

1648

1633

1617

1597

 

1576

1557

1537

1493

1448

1397

1345

1207

1051

957

 

 

 

 

 

HS MED

1344

1335

1325

1312

 

1299

1276

1253

1220

1186

1143

1099

1007

903

 

 

 

 

 

 

HS LO

1141

1128

1115

1106

 

1097

1077

1057

1031

1005

966

926

 

 

 

 

 

 

 

 

HI

1634

1626

1618

1606

 

1594

1583

1571

1539

1507

1464

1420

1265

1078

 

 

 

 

 

 

MED

1332

1323

1314

1298

 

1282

1263

1243

1206

1169

1115

1060

 

 

 

 

 

042

1400

1050

LO

1130

1109

1088

1086

 

1084

1066

1048

1052

1055

 

 

 

 

 

 

 

 

 

 

HS HI

1798

1781

1764

1738

 

1711

1688

1665

1630

1595

1555

1514

1420

1239

 

 

 

 

 

 

HS MED

1384

1382

1379

1375

 

1371

1356

1341

1318

1294

1261

1227

 

 

 

 

 

 

 

 

HS LO

1091

1088

1084

1081

 

1078

1069

1060

 

 

 

 

 

 

 

 

 

 

 

 

HI

1798

1781

1764

1738

 

1711

1688

1665

1630

1595

1555

1514

1420

1239

 

 

 

 

 

 

MED

1384

1382

1379

1375

 

1371

1356

1341

1318

1294

1261

1227

 

 

 

 

 

048

1600

1200

LO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HS HI

2011

1977

1942

1923

 

1903

1841

1778

1755

1732

1689

1645

1520

1431

1307

1211

 

 

 

 

HS MED

1881

1858

1834

1807

 

1780

1746

1711

1676

1640

1604

1567

1469

1378

1286

 

 

 

 

 

HS LO

1738

1716

1694

1673

 

1651

1634

1617

1584

1551

1508

1465

1390

1321

1228

 

 

 

 

 

HI

2311

2306

2300

2290

 

2279

2268

2257

2233

2209

2175

2140

2088

1990

1901

1856

1752

 

 

 

MED

2058

2049

2039

2028

 

2016

2000

1983

1966

1949

1935

1920

1874

1807

1750

1670

1582

060

1950

1500

LO

1868

1863

1858

1858

 

1858

1848

1838

1822

1806

1799

1792

1749

1699

1636

1570

 

 

 

 

HS HI

2510

2498

2486

2471

 

2455

2440

2424

2401

2377

2348

2318

2247

2161

2078

1986

1855

 

 

 

HS MED

2171

2167

2162

2162

 

2162

2158

2153

2135

2117

2101

2085

2024

1971

1891

1823

1691

 

 

 

HS LO

2010

2008

2006

2006

 

2006

2006

2006

1992

1977

1962

1947

1892

1851

1782

1705

1600

070

2100

1800

HI

2510

2498

2486

2471

 

2455

2440

2424

2401

2377

2348

2318

2247

2161

2078

1986

1855

MED

2171

2167

2162

2162

 

2162

2158

2153

2135

2117

2101

2085

2024

1971

1891

1823

 

 

 

 

LO

2010

2008

2006

2006

 

2006

2006

2006

1992

1977

1962

1947

1892

1851

 

 

 

LEGEND

NOTES:

ESP — External Static Pressure

1.

Shaded areas denote ESP where operation is not recommended.

2.

Units factory shipped on medium speed. Other speeds require field

HS — High Static

 

selection.

 

 

 

3.

All airflow is rated and shown above at the lower voltage if unit is dual

 

 

voltage rated, e.g., 208 v for 208/230 v units.

 

4.

Only two-speed fan (high and medium) available on 575 v units.

 

5.

Data for units 006-012 not available at time of printing.

Table 13 — PSC Blower Motor Performance Data for 50PS Units with HWR

COIL

 

 

UNITS WITH REHEAT ESP LOSS

 

 

FACE VELOCITY

018

024,030

 

036

 

042,048

060,070

FPM

in. wg

in. wg

 

in. wg

 

in. wg

in. wg

200

0.037

0.033

 

0.031

 

0.028

0.026

250

0.052

0.046

 

0.042

 

0.038

0.034

300

0.077

0.066

 

0.059

 

0.051

0.044

350

0.113

0.096

 

0.085

 

0.073

0.061

400

0.181

0.160

 

0.145

 

0.131

0.117

450

0.242

0.226

 

0.215

 

0.205

0.194

500

0.360

0.345

 

0.335

 

0.326

0.316

LEGEND

ESP — External Static Pressure

HWR — Hot Water Reheat

NOTES:

1.For units with HWR coil applications, calculate face velocity of the enter- ing air. From the data table, find ESP for reheat application. The loss includes wet coil loss.

2.Data for units 006-012 not available at time of printing.

31

Image 31
Contents Contents Installation, Start-Up, Service InstructionsInstallation Safety ConsiderationsGeneral Physical Data 50PSH, PSV, PSD018-070 Units Typical Installation 50PSH Unit Code Return Discharge CSP ASPBSP CAP50PSV Dimensional Data HWR Hot Water Reheat Left Hand Right Hand A50-7846efBack Discharge Side DischargeMount the Unit Install Condensate DrainTrap Condensate Drain Connection Open Loop and Recirculating Well Water Quality GuidelinesMaterial Metal Hose Minimum Bend Radii Typical Ground-Water Piping InstallationSupply/Return Hose Kit Wire Field Power SupplyAstat Complete C Controller Fault CodesDescription of Operation LED Alarm Relay TransYellow RED Wire NumberBMC ComprLWT ECMUnits with ECM, Complete C and LON Controller 460 A50-8363Units with ECM, Deluxe D and LON Controller 460 A50-8364Hpws SATMves WHSP-OPEN 8354 A508356 LWT Wshp Open Control A50-838050PSH, PSV, PSD Electrical Data PSC High-Static Motor 50PSH, PSV, PSD Electrical Data PSC Motor50PSH, PSV, PSD Electrical Data, ECM Motor Low Voltage Field Wiring Wire Field ControlsField-Supplied Sensors for Wshp Open Controller Rnet Wiring SpecificationsA50-8441 A50-8442A50-8443 Rnet WiringWire Terminal Operate ECM Interface BoardECM Blower Motor Performance Data Setting SizeFPM Rated MIN FANUnit Airflow CFM Speed Size Coil Units with Reheat ESP Loss Face VelocityField Selectable Inputs Complete C Control Jumper SettingsDeluxe D Control Jumper Settings PRE-START-UPVAC DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options Humidistat/Dehumidistat Logic Deluxe D DIP Switch SettingsA50-8145 HWR Operating ModesOperating Limits 50PSH, PSV, PSD Units Unit Start-Up Cooling ModeSTART-UP Operating LimitsWater Flow Temp Unit Start-Up Heating ModeWater Temperature Change Through Heat Exchanger Cooling Heating Water Flow Rate GPM Rise F Drop FGPM/ton Pressure Heat Cooling Rise Drop Psig Flow Flow BACview6 Display Interface Unit Start-Up with Wshp Open ControlsGPM 50PSH, PSV, PSD Water Water Temperature F Flow50PSH, PSV, PSD Coaxial Water Pressure Drop Unit SizeUnits with Aquazone Complete C Control Approximate Fluid Volume gal Per 100 Ft of PipeAntifreeze Percentages by Volume OperationUnits with Wshp Open Multiple Protocol Units with HWR OptionPage Page Complete C and Deluxe D Board System Test LED Status Description of Operation Alarm RelayOff Description Status LED Test LED Complete C Control LED Code Fault DescriptionsLED Code Fault Description Aquazone Deluxe D Control LED IndicaService Replacing the Wshp Open Controller’s Bat TroubleshootingRefrigerant Charging Air Coil Fan Motor RemovalFP1 and FP2 Thermistor Location Page Fault Description Solution ECM TroubleshootingA50-8448 ECM Pin ConnectorsA50-8447 ECM Troubleshooting Flow DiagramTXV Wshp TroubleshootingFault Heating Cooling Possible Cause Solution Good PracticesCode Condensate FaultCode 7 Auto Resetting No Fault Code ShownLow Discharge Air Temperature in HeatingHigh Head Pressure Low Suction PressureAppendix a Wshp Open Screen Configuration Appendix a Wshp Open Screen Configuration Schedules 1 Set PointsWeekly Schedule ExceptionService Appendix a Wshp Screen Open ConfigurationTest Point Name Password Editable Range Default Level Configuration ServiceScreen Name Linkage AlarmPage Page Copyright 2009 Carrier Corporation II. START-UP 50PSH,PSV,PSD START-UP ChecklistA50-8495 Heating Cycle AnalysisCooling Cycle Analysis A50-8494