Carrier PSD006-070, PSV, 50PSH instruction manual ECM Blower Motor Performance Data, Setting Size

Page 30

DEHUMIDIFICATION MODE — The dehumidification mode setting provides field selection of humidity control. When oper- ating in the normal mode, the cooling airflow settings are deter- mined by the cooling tap setting in Table 11. When dehumidifi- cation is enabled, there is a reduction in airflow in cooling to in- crease the moisture removal of the heat pump. The Dehumidification mode can be enabled in two ways:

1.Constant Dehumidification mode: When the Dehumidifi- cation mode is selected via DIP switch, the ECM will operate with a multiplier applied to the cooling CFM settings (approximately 20 to 25% lower airflow). Any time the unit is running in the Cooling mode, it will oper- ate at the lower airflow to improve latent capacity. The “DEHUM” LED will be illuminated at all times. Heating airflow is not affected.

NOTE: Do not select Dehumidification mode if cooling setting is tap 1.

2.Automatic (humidistat-controlled) Dehumidification mode: When the Dehumidification mode is selected via DIP switch AND a humidistat is connected to termi- nal DH, the cooling airflow will only be reduced when the humidistat senses that additional dehumidification is required. The DH terminal is reverse logic. Therefore, a humidistat (not dehumidistat) is required. The “DEHUM” LED will be illuminated only when the humi- distat is calling for Dehumidification mode. Heating airflow is not affected.

NOTE: Do not select Dehumidification mode if cooling setting is tap 1.

Table 11 — ECM Blower Motor Performance Data

50PS

MAX

FAN

TAP

COOLING MODE

 

DEHUMIDIFICATION MODE

HEATING MODE

 

UNIT

ESP

MOTOR

 

(cfm)

 

 

(cfm)

 

 

(cfm)

 

SETTING

 

 

 

 

 

 

SIZE

(in. wg)

(hp)

Stage 1

Stage 2

 

Fan

Stage 1

Stage 2

Fan

Stage 1

Stage 2

 

Fan

 

 

 

 

 

 

4

750

620

 

380

590

480

380

750

620

 

380

018

0.50

1/2

3

700

570

 

350

550

450

350

700

570

 

350

 

 

 

2

620

510

 

310

480

400

310

620

510

 

310

 

 

 

1

530

430

 

270

530

430

 

270

 

 

 

4

950

780

 

470

740

610

470

1060

870

 

470

024

0.50

1/2

3

850

700

 

420

660

540

420

950

780

 

420

 

 

 

2

730

600

 

360

570

470

360

820

670

 

360

 

 

 

1

610

500

 

300

690

570

 

300

 

 

 

4

1130

920

 

560

880

720

560

1230

1000

 

560

030

0.50

1/2

3

1000

820

 

500

780

640

500

1100

900

 

500

 

 

 

2

880

720

 

440

680

560

440

980

800

 

440

 

 

 

1

750

620

 

380

850

700

 

380

 

 

 

4

1400

1150

 

700

1090

900

700

1400

1150

 

700

036

0.50

1/2

3

1250

1020

 

630

980

800

630

1250

1020

 

630

 

 

 

2

1080

890

 

540

840

690

540

1080

890

 

540

 

 

 

1

900

740

 

450

900

740

 

450

 

 

 

4

1580

1290

 

790

1230

1010

790

1580

1290

 

790

042

0.50

1/2

3

1400

1150

 

700

1100

900

700

1400

1150

 

700

 

 

 

2

1230

1000

 

610

960

790

610

1230

1000

 

610

 

 

 

1

1050

860

 

530

1050

860

 

530

 

 

 

4

1730

1420

 

870

1350

1110

870

1850

1520

 

870

048

0.75

1

3

1550

1270

 

780

1210

990

780

1650

1350

 

780

 

 

 

2

1330

1090

 

670

1040

850

670

1430

1180

 

670

 

 

 

1

1120

920

 

560

1200

980

 

560

 

 

 

4

2050

1680

 

1030

1600

1310

1030

2280

1870

 

1030

060

0.75

1

3

1825

1500

 

910

1420

1170

910

2050

1680

 

910

 

 

 

2

1580

1300

 

790

1230

1010

790

1750

1430

 

790

 

 

 

1

1320

1080

 

660

1470

1210

 

660

 

 

 

4

2230

1780

 

1100

1710

1400

1100

2230

1780

 

1100

070

0.75

1

3

1950

1600

 

980

1520

1250

980

2100

1680

 

980

 

 

 

2

1700

1400

 

850

1330

1090

850

1840

1470

 

850

 

 

 

1

1450

1200

 

730

1520

1220

 

730

LEGEND

ESP — External Static Pressure

NOTES:

1.Factory setting is Tap Setting 2.

2.Airflow is controlled within 5% up to the Max ESP shown with wet coil.

3.Do not select Dehumidification mode if Tap Setting is on Setting 1.

4.All units are ARI/ISO (Air Conditioning & Refrigeration Institute/ International Organization for Standardization) 13256-1 rated Tap Setting 3.

5.Airflow in cfm with wet coil and clean air filter.

6.Units have an ECM (electronically commuted motor) fan motor as a standard feature. The small additional pressure drop of the reheat coil causes the ECM motor to slightly increase rpm to overcome the added pressure drop and maintain selected cfm up to maximum ESP (external static pressure).

7.Unit sizes 006-012 are not available with ECM motors.

30

Image 30
Contents Installation, Start-Up, Service Instructions ContentsSafety Considerations InstallationGeneral Physical Data 50PSH, PSV, PSD018-070 Units Typical Installation 50PSH Unit CAP ASPBSP Code Return Discharge CSP50PSV Dimensional Data A50-7846ef HWR Hot Water Reheat Left Hand Right HandSide Discharge Back DischargeInstall Condensate Drain Mount the UnitTrap Condensate Drain Connection Water Quality Guidelines Open Loop and Recirculating WellMaterial Typical Ground-Water Piping Installation Metal Hose Minimum Bend RadiiWire Field Power Supply Supply/Return Hose KitTrans Complete C Controller Fault CodesDescription of Operation LED Alarm Relay AstatCompr Wire NumberBMC Yellow REDECM LWTA50-8363 Units with ECM, Complete C and LON Controller 460A50-8364 Units with ECM, Deluxe D and LON Controller 460SAT HpwsMves WHSP-OPEN A50 83548356 LWT A50-8380 Wshp Open Control50PSH, PSV, PSD Electrical Data PSC Motor 50PSH, PSV, PSD Electrical Data PSC High-Static Motor50PSH, PSV, PSD Electrical Data, ECM Motor Wire Field Controls Low Voltage Field WiringA50-8442 Rnet Wiring SpecificationsA50-8441 Field-Supplied Sensors for Wshp Open ControllerOperate ECM Interface Board Rnet WiringWire Terminal A50-8443Setting Size ECM Blower Motor Performance DataCoil Units with Reheat ESP Loss Face Velocity Rated MIN FANUnit Airflow CFM Speed Size FPMPRE-START-UP Complete C Control Jumper SettingsDeluxe D Control Jumper Settings Field Selectable InputsHumidistat/Dehumidistat Logic Deluxe D DIP Switch Settings DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options VACHWR Operating Modes A50-8145Operating Limits Unit Start-Up Cooling ModeSTART-UP Operating Limits 50PSH, PSV, PSD UnitsCooling Heating Water Flow Rate GPM Rise F Drop F Unit Start-Up Heating ModeWater Temperature Change Through Heat Exchanger Water Flow TempGPM/ton Pressure Heat Cooling Rise Drop Psig Flow Flow Unit Start-Up with Wshp Open Controls BACview6 Display InterfaceUnit Size 50PSH, PSV, PSD Water Water Temperature F Flow50PSH, PSV, PSD Coaxial Water Pressure Drop GPMOperation Approximate Fluid Volume gal Per 100 Ft of PipeAntifreeze Percentages by Volume Units with Aquazone Complete C ControlUnits with HWR Option Units with Wshp Open Multiple ProtocolPage Page LED Status Description of Operation Alarm Relay Complete C and Deluxe D Board System TestOff Aquazone Deluxe D Control LED Indica Complete C Control LED Code Fault DescriptionsLED Code Fault Description Description Status LED Test LEDService Air Coil Fan Motor Removal TroubleshootingRefrigerant Charging Replacing the Wshp Open Controller’s BatFP1 and FP2 Thermistor Location Page ECM Troubleshooting Fault Description SolutionECM Pin Connectors A50-8448ECM Troubleshooting Flow Diagram A50-8447Good Practices Wshp TroubleshootingFault Heating Cooling Possible Cause Solution TXVNo Fault Code Shown Condensate FaultCode 7 Auto Resetting CodeLow Suction Pressure Temperature in HeatingHigh Head Pressure Low Discharge AirAppendix a Wshp Open Screen Configuration Appendix a Wshp Open Screen Configuration Exception Set PointsWeekly Schedule Schedules 1Appendix a Wshp Screen Open Configuration ServiceTest Configuration Service Point Name Password Editable Range Default LevelScreen Name Alarm LinkagePage Page Copyright 2009 Carrier Corporation 50PSH,PSV,PSD START-UP Checklist II. START-UPA50-8494 Heating Cycle AnalysisCooling Cycle Analysis A50-8495