Carrier PSV A50-8441, A50-8442, Field-Supplied Sensors for Wshp Open Controller, SPT Sensors

Page 28

C

Y1

a50-8441

 

 

 

2

AMV

1

3

TACO VALVE

 

HEATER SWITCH

 

C

Y1

 

THERMOSTAT

 

Fig. 30 — AMV Valve Wiring

a50-8442

Fig. 31 — Taco SBV Valve Wiring

WSHP OPEN WIRING — The WSHP Open controller will be factory mounted to the unit control panel and wired to the Complete C or Deluxe D control board, however, the system wiring will need to be completed utilizing WSHP Open con- troller wiring diagrams and the Third Party Integration (TPI) Guide. Factory installation includes harness, LWT (leaving water temperature), supply air, and condensate sensor.

WARNING

Disconnect all power to the unit before performing mainte- nance or service. Unit may automatically start if power is not disconnected. Failure to follow this warning could cause personal injury, death, and/or equipment damage.

Wiring Sensors to Inputs — Sensors can be wired to the WSHP Open controller’s inputs. See Table 7.

All field control wiring that connects to the WSHP Open con- troller must be routed through the raceway built into the corner post. The raceway provides the UL required clearance between high and low-voltage wiring.

1.Pass control wires through hole provided in corner post.

2.Feed the wires through the raceway to the WSHP Open controller.

3.Connect the wires to the removable Phoenix connectors.

4.Reconnect the connectors to the board.

Field-Supplied Sensor Hardware — The WSHP Open con- troller is configurable with the following field-supplied sen- sors. See Table 7.

Table 7 — Field-Supplied Sensors for

WSHP Open Controller

SENSOR

NOTES

Space Temperature Sensor

Field Installed (Must be used with

(SPT)

WSHP Open controller.)

Outdoor Air

Network Sensor

Temperature Sensor

 

Indoor Air Quality Sensor

Required only for demand

(Separate Sensor)

control ventilation.

Space Relative

Separate Sensor

Humidity Sensor

 

NOTE: BACview6 Handheld or Virtual BACview can be used as the user interface.

For specific details about sensors, refer to the literature sup- plied with the sensor.

Wiring a SPT Sensor — A WSHP Open controller is connect- ed to a wall-mounted space temperature (SPT) sensor to moni- tor room temperature using a Molex plug.

The WSHP Open system offers the following SPT sensors. See Table 8.

Table 8 — SPT Sensors

SENSOR

PART

FEATURES

NUMBER

 

 

SPT

SPS

• Local access port

Standard

• No operator control

 

 

 

• Slide potentiometer to adjust set point

SPT Plus

SPPL

• Manual on button to override schedule

• LED to show occupied status

 

 

 

 

• Local access port

 

 

• LCD display

 

 

• Manual on button to override schedule

SPT Pro

 

• Warmer and cooler buttons to adjust set point

SPP

• Info button to cycle through zone and outside

 

 

air temperatures, set points, and local override

 

 

time

 

 

• Local access port

 

 

• LCD display

 

 

• Manual on button to override schedule

SPT Pro

 

• Warmer and cooler buttons to adjust set point

SPPF

• Info button to cycle through zone and outside

Plus

air temperatures, set points, and local override

 

 

 

time

 

 

• Local access port

 

 

• Fan speed*

*The SPT Pro Plus fan speed adjustment has no effect in this application.

Wire SPT sensors to the WSHP Open controller’s Rnet port. An Rnetbus can consist of any of the following combinations of devices wired in a daisy-chain configuration:

1 SPT Plus, SPT Pro, or SPT Pro Plus sensor

1 to 4 SPT Standard sensors

1 to 4 SPT Standard sensors and 1 SPT Plus, SPT Pro, or SPT Pro Plus sensor

Any of the above combinations, plus up to 2 BACview6 Handheld but no more than 6 total devices

NOTE: If the Rnetbus has multiple SPT Standard sensors, each sensor must be given a unique address on the Rnetbus. See the Carrier Open Sensor Installation Guide.

Use the specified type of wire and cable for maximum signal integrity. See Table 9.

Table 9 — Rnet Wiring Specifications

RNET WIRING SPECIFICATIONS

 

Description

 

4 conductor, unshielded, CMP,

 

 

plenum rated cable

 

 

 

 

Conductor

 

18 AWG

 

Maximum Length

 

500 ft

 

Recommended Coloring

 

Jacket: white

 

 

Wiring: black, white, green, red

 

 

 

 

UL Temperature

 

32 to 167 F

 

Voltage

 

300-vac, power limited

 

Listing

 

UL: NEC CL2P, or better

 

LEGEND

 

AWG — American Wire Gage

 

CMP

Communications Plenum Cable

 

NEC

National Electrical Code

 

UL

Underwriters Laboratories

 

To wire the SPT sensor to the controller:

1.Partially cut , then bend and pull off the outer jacket of the Rnet cable(s), being careful not to nick the inner insulation.

2.Strip about 1/4 in. of the inner insulation from each wire. See Fig. 32.

28

Image 28
Contents Installation, Start-Up, Service Instructions ContentsInstallation Safety ConsiderationsGeneral Physical Data 50PSH, PSV, PSD018-070 Units Typical Installation 50PSH Unit ASP BSPCAP Code Return Discharge CSP50PSV Dimensional Data A50-7846ef HWR Hot Water Reheat Left Hand Right HandSide Discharge Back DischargeInstall Condensate Drain Mount the UnitTrap Condensate Drain Connection Open Loop and Recirculating Well Water Quality GuidelinesMaterial Typical Ground-Water Piping Installation Metal Hose Minimum Bend RadiiWire Field Power Supply Supply/Return Hose KitComplete C Controller Fault Codes Description of Operation LED Alarm RelayTrans AstatWire Number BMCCompr Yellow REDECM LWTA50-8363 Units with ECM, Complete C and LON Controller 460A50-8364 Units with ECM, Deluxe D and LON Controller 460Hpws SATMves WHSP-OPEN A50 83548356 LWT A50-8380 Wshp Open Control50PSH, PSV, PSD Electrical Data PSC Motor 50PSH, PSV, PSD Electrical Data PSC High-Static Motor50PSH, PSV, PSD Electrical Data, ECM Motor Wire Field Controls Low Voltage Field WiringRnet Wiring Specifications A50-8441A50-8442 Field-Supplied Sensors for Wshp Open ControllerRnet Wiring Wire TerminalOperate ECM Interface Board A50-8443Setting Size ECM Blower Motor Performance DataRated MIN FAN Unit Airflow CFM Speed SizeCoil Units with Reheat ESP Loss Face Velocity FPMComplete C Control Jumper Settings Deluxe D Control Jumper SettingsPRE-START-UP Field Selectable InputsDIP Switch Block S2 Accessory 1 Relay Options DIP Switch Block S2 Accessory 2 Relay OptionsHumidistat/Dehumidistat Logic Deluxe D DIP Switch Settings VACHWR Operating Modes A50-8145Unit Start-Up Cooling Mode START-UPOperating Limits Operating Limits 50PSH, PSV, PSD UnitsUnit Start-Up Heating Mode Water Temperature Change Through Heat ExchangerCooling Heating Water Flow Rate GPM Rise F Drop F Water Flow TempGPM/ton Pressure Heat Cooling Rise Drop Psig Flow Flow Unit Start-Up with Wshp Open Controls BACview6 Display Interface50PSH, PSV, PSD Water Water Temperature F Flow 50PSH, PSV, PSD Coaxial Water Pressure DropUnit Size GPMApproximate Fluid Volume gal Per 100 Ft of Pipe Antifreeze Percentages by VolumeOperation Units with Aquazone Complete C ControlUnits with HWR Option Units with Wshp Open Multiple ProtocolPage Page Complete C and Deluxe D Board System Test LED Status Description of Operation Alarm RelayOff Complete C Control LED Code Fault Descriptions LED Code Fault DescriptionAquazone Deluxe D Control LED Indica Description Status LED Test LEDService Troubleshooting Refrigerant ChargingAir Coil Fan Motor Removal Replacing the Wshp Open Controller’s BatFP1 and FP2 Thermistor Location Page ECM Troubleshooting Fault Description SolutionECM Pin Connectors A50-8448ECM Troubleshooting Flow Diagram A50-8447Wshp Troubleshooting Fault Heating Cooling Possible Cause SolutionGood Practices TXVCondensate Fault Code 7 Auto ResettingNo Fault Code Shown CodeTemperature in Heating High Head PressureLow Suction Pressure Low Discharge AirAppendix a Wshp Open Screen Configuration Appendix a Wshp Open Screen Configuration Set Points Weekly ScheduleException Schedules 1Service Appendix a Wshp Screen Open ConfigurationTest Point Name Password Editable Range Default Level Configuration ServiceScreen Name Alarm LinkagePage Page Copyright 2009 Carrier Corporation 50PSH,PSV,PSD START-UP Checklist II. START-UPHeating Cycle Analysis Cooling Cycle AnalysisA50-8494 A50-8495