Step 9 — Wire Field Controls

THERMOSTAT CONNECTIONS — The thermostat should be wired directly to the ECM control board. See Fig. 27.

WATER FREEZE PROTECTION — The Aquazone™ con- trol allows the field selection of source fluid freeze protection points through jumpers. The factory setting of jumper JW3 (FP1) is set for water at 30 F. In earth loop applications, jumper JW3 should be clipped to change the setting to 10 F when us- ing antifreeze in colder earth loop applications. See Fig. 28.

NOTE: The extended range option should be selected with water temperatures below 60 F to prevent internal condensation.

AIR COIL FREEZE PROTECTION — The air coil freeze protection jumper JW2 (FP2) is factory set for 30 F and should not need adjusting.

ACCESSORY CONNECTIONS — Terminal A on the control is provided to control accessory devices such as water valves, electronic air cleaners, humidifiers, etc. This signal operates with the compressor terminal. See Fig. 29. Refer to the specific unit wiring schematic for details.

NOTE: The A terminal should only be used with 24-volt signals — not line voltage signals.

WATER SOLENOID VALVES — An external solenoid valve(s) should be used on ground water installations to shut off flow to the unit when the compressor is not operating. A slow closing valve may be required to help reduce water hammer. Figure 29 shows typical wiring for a 24-vac external solenoid valve. Figures 30 and 31 illustrate typical slow closing water control valve wiring for Taco 500 Series and Taco ESP Series valves. Slow closing valves take approximately 60 sec. to open (very little water will flow before 45 sec.). Once fully open, an end switch allows the compressor to be energized (only on valves with end switches). Only relay or triac based electronic thermostats should be used with slow closing valves. When wired as shown, the slow closing valve will operate properly with the following notations:

1.The valve will remain open during a unit lockout.

2.The valve will draw approximately 25 to 35 VA through the “Y” signal of the thermostat.

IMPORTANT: Connecting a water solenoid valve can overheat the anticipators of electromechanical thermo- stats. Only use relay based electronic thermostats.

COMPRESSOR CONTACTOR

CAPACITOR

COMPLETE C CONTROL

 

 

 

LINE

LOAD

 

TRANSFORMER

a50-8197

 

 

J1

 

 

Y

W

R

S1

CFM

 

 

SW1

O

 

SW2

G

SW3

 

 

SW4

 

 

SW5

Y2

G

SW6

 

SW7

 

 

 

 

 

 

SW8

 

Y1

G

SW9

 

OFF

ON

 

 

G

G

 

 

 

 

 

G

DEHUM

 

 

TB1

 

 

 

 

 

 

 

R

C

Y2 Y1 G

O

W

C

R DH AL1 A

 

A

AL1

THERMOSTAT CONNECTION

Fig. 27 — Low Voltage Field Wiring

TERMINAL STRIP P2

C

A

A50-6269

TYPICAL

24 VAC WATER VALVE

Fig. 29 — Typical Accessory Wiring

A50-7764

AQUAZONE CONTROL (Complete C Shown)

Fig. 28 — Typical Aquazone™ Control Board

Jumper Locations

27

Image 27
Contents Contents Installation, Start-Up, Service InstructionsSafety Considerations InstallationGeneral Physical Data 50PSH, PSV, PSD018-070 Units Typical Installation 50PSH Unit Code Return Discharge CSP ASPBSP CAP50PSV Dimensional Data HWR Hot Water Reheat Left Hand Right Hand A50-7846efBack Discharge Side DischargeMount the Unit Install Condensate DrainTrap Condensate Drain Connection Water Quality Guidelines Open Loop and Recirculating WellMaterial Metal Hose Minimum Bend Radii Typical Ground-Water Piping InstallationSupply/Return Hose Kit Wire Field Power SupplyAstat Complete C Controller Fault CodesDescription of Operation LED Alarm Relay TransYellow RED Wire NumberBMC ComprLWT ECMUnits with ECM, Complete C and LON Controller 460 A50-8363Units with ECM, Deluxe D and LON Controller 460 A50-8364SAT HpwsMves WHSP-OPEN 8354 A508356 LWT Wshp Open Control A50-838050PSH, PSV, PSD Electrical Data PSC High-Static Motor 50PSH, PSV, PSD Electrical Data PSC Motor50PSH, PSV, PSD Electrical Data, ECM Motor Low Voltage Field Wiring Wire Field ControlsField-Supplied Sensors for Wshp Open Controller Rnet Wiring SpecificationsA50-8441 A50-8442A50-8443 Rnet WiringWire Terminal Operate ECM Interface BoardECM Blower Motor Performance Data Setting SizeFPM Rated MIN FANUnit Airflow CFM Speed Size Coil Units with Reheat ESP Loss Face VelocityField Selectable Inputs Complete C Control Jumper SettingsDeluxe D Control Jumper Settings PRE-START-UPVAC DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options Humidistat/Dehumidistat Logic Deluxe D DIP Switch SettingsA50-8145 HWR Operating ModesOperating Limits 50PSH, PSV, PSD Units Unit Start-Up Cooling ModeSTART-UP Operating LimitsWater Flow Temp Unit Start-Up Heating ModeWater Temperature Change Through Heat Exchanger Cooling Heating Water Flow Rate GPM Rise F Drop FGPM/ton Pressure Heat Cooling Rise Drop Psig Flow Flow BACview6 Display Interface Unit Start-Up with Wshp Open ControlsGPM 50PSH, PSV, PSD Water Water Temperature F Flow50PSH, PSV, PSD Coaxial Water Pressure Drop Unit SizeUnits with Aquazone Complete C Control Approximate Fluid Volume gal Per 100 Ft of PipeAntifreeze Percentages by Volume OperationUnits with Wshp Open Multiple Protocol Units with HWR OptionPage Page LED Status Description of Operation Alarm Relay Complete C and Deluxe D Board System TestOff Description Status LED Test LED Complete C Control LED Code Fault DescriptionsLED Code Fault Description Aquazone Deluxe D Control LED IndicaService Replacing the Wshp Open Controller’s Bat TroubleshootingRefrigerant Charging Air Coil Fan Motor RemovalFP1 and FP2 Thermistor Location Page Fault Description Solution ECM TroubleshootingA50-8448 ECM Pin ConnectorsA50-8447 ECM Troubleshooting Flow DiagramTXV Wshp TroubleshootingFault Heating Cooling Possible Cause Solution Good PracticesCode Condensate FaultCode 7 Auto Resetting No Fault Code ShownLow Discharge Air Temperature in HeatingHigh Head Pressure Low Suction PressureAppendix a Wshp Open Screen Configuration Appendix a Wshp Open Screen Configuration Schedules 1 Set PointsWeekly Schedule ExceptionAppendix a Wshp Screen Open Configuration ServiceTest Configuration Service Point Name Password Editable Range Default LevelScreen Name Linkage AlarmPage Page Copyright 2009 Carrier Corporation II. START-UP 50PSH,PSV,PSD START-UP ChecklistA50-8495 Heating Cycle AnalysisCooling Cycle Analysis A50-8494