Carrier 50TFQ008-012 specifications Adjust Factory-Installed Options

Page 12

FIELD CONTROL WIRING — Install a Carrier-approved accessory thermostat assembly according to the installation instructions included with the accessory. Locate the thermostat assembly on a solid wall in the conditioned space to sense aver- age temperature in accordance with the thermostat installation instructions.

NOTE: If using a Carrier electronic thermostat, set the thermo- stat configuration for “non-heat pump operation.” This family of products does not require an O terminal to energize the reversing valve.

Route the thermostat cable or equivalent single leads of colored wire from the subbase terminals to the low-voltage connections on the unit (shown in Fig. 8A and 8B) as described in Steps 1 through 4 below.

NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 51 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.

1.If the unit is mounted on the roof curb and the accessory thru-the-curb service plate connection is used, route wire through the connection plate.

2.Pass control wires through the hole provided on the unit (see connection D in Connection Sizes table in Fig. 6).

3.Feed wire through the raceway built into the corner post to the 24-v barrier located on the left side of the control box. See Fig. 9. The raceway provides the UL required clear- ance between the high-voltage and low-voltage wiring.

4.Connect the thermostat wires to the screw terminals of the low-voltage connector (see Fig. 8A and 8B).

NOTE: If the unit is mounted on a roof curb and electrical power will be run up “thru-the-bottom,” use accessory kit number CRBTMPWR002A01. This kit, available from your local distributor, ensures a watertight seal. Refer to the acces- sory installation instructions for information on power wiring. Refer to Fig. 6 for drilling holes in basepan.

DEFROST BOARD — The defrost board timer cycle is set to 30 minutes. To change the cycle time, turn off power to the unit and install lockout tag. Remove the wire from defrost board connected to the 30 minute quick-connect. See Fig. 10. Connect the wire to the 50 or 90 minute quick-connects on the defrost board, depending on the desired defrost time.

HEAT ANTICIPATOR SETTINGS — For units with electric heat, set heat anticipator settings as shown in Table 4.

Step 6 — Adjust Factory-Installed Options

DISCONNECT SWITCH — The optional disconnect switch is non-fused. The switch can be locked in place for safety purposes.

 

CONTROL

THERMOSTAT CONTROL

CONNECTION

CONNECTION

 

BOARD

 

BOARD

R

24 VAC

R

R

G

RMTOCC

Y1

Y1

 

CMPSAFE

Y2

Y2

Y2

FSD

W1

W1

W1

SFS

W2

W2

 

NOT USED

G

G

C

C

C

C

X

X

X

 

Fig. 8B — Low Voltage Connections (Units with PremierLink™ Controls)

DISCONNECT

BOARD

COOL STAGE 1

Y1/W2

FAN

G

HEAT STAGE 1

W/W1

COOL STAGE 2

Y/Y2

HEAT STAGE 2

O/W2

24 VAC HOT

R

24 VAC COM

C

N/A

 

OUTDOOR AIR

S1

SENSOR

S2

R

G

Y1

Y2

W1

W2

C

IPD/X

WIRE CONNECTIONS TO LOW-VOLTAGE SECTION (CONNECTION BOARD)

DISCONNECT SWITCH (OPTIONAL)

RACEWAY

COMPRESSOR

NO. 2

CONVENIENCE OUTLET

THERMOSTAT DIPSWITCH SETTINGS

ON

OFF

A B C D

LEGEND

Field Wiring

NOTE: Underlined letter indicates active thermostat output when configured for A/C operation.

Fig. 8A — Low-Voltage Connections With or Without Economizer or Two-Position Damper

HOLE IN

END

PANEL

COMPRESSOR NO. 1

Fig. 9 — Typical Field Control Wiring Raceway

12

Image 12
Contents Contents Safety ConsiderationsInstallation Roof Curb Details Unit Leveling Tolerances Rigging Details Physical Data Unit Size 50TFQBase Unit Dimensions Make Electrical Connections Electric Heating Capacities Electrical Data Units Without Electrical Convenience OutletSIZE† Electrical Data Units With Electrical Convenience Outlet 81/2 TonsOFM IFM Heat SIZE† Unit Size Adjust Factory-Installed Options Heat Anticipator Settings 208/230 460 575Stage Outdoor-Air Hood Details PremierLink Sensor Usage PremierLink ControllerPremierLink Controller Installed For Differential EconoMi$er IV Component Locations Outdoor-Air Hood Construction EconoMi$er2 with 4 to 20 mA Control Wiring Supply Air Sensor Temperature Resistance Values EconoMi$er IV Sensor UsageEconoMi$er IV Controller Potentiometer LED Locations Enthalpy Changeover Set Points Page CO2 Sensor Standard Settings UrationTypical Belt-Drive Motor Mounting for Size Size 008 Fan Motor PerformanceFan Rpm at Motor Pulley Settings Electric Heater Static Pressure* in. wg 50TFQ008-012External Static Pressure in. wg Rpm Bhp Watts 2250 511 5382300 519 567 2400 534 630Rpm Bhp Watts 2250 511 538 591 697 660 864 2300 519 567 597 729 666 9002400 534 630 611 798 678 974 2500 550 698 624 872Airflow Rpm Bhp Watts 2550 557 733 631 910 38003900 4000 4100 4200 4250 Rpm Bhp Watts 25503100 646 1217 711 1428 770 1645 825 1869 3200 662 1324 726 1542 784 1765 838 19943300 679 1438 741 1663 798 1892 851 2126 3400 695 1558 756 1790 812 2025Rpm Bhp Watts 3000 556 604 623 748 684 891 3100 569 656 636 8053200 583 712 648 865 3300 597 770 661 9293600 639 967 700 1140 754 1312 805 1484 3700 654 1040 713 1218 767 1395 817 15713800 668 1116 726 1299 779 1481 828 1662 3900 683 1197 739 1385 792 1572 840 17583500 625 898 687 1066 742 1233 794 1400 3900 683 1197 739 1385 792 15724200 726 1462 780 1665 1132 3555 4500Rpm Bhp Watts 2250 465 459 555 621 2300 471 483 560 6482400 483 534 570 705 2500 495 588 581 767Rpm Bhp Watts 2250 465 459 555 621 629 786 2300 471 483 560 648 634 8172400 483 534 570 705 644 880 2500 495 588 581 767 653 948Airflow Rpm Bhp Watts 2550 501 617 586 799 658 983 3800 662 17053900 675 1828 Airflow Rpm Bhp Watts 3000 523 541 592 680 657 825 3100 536 587 603 730 666 8793200 549 637 614 783 676 936 3300 562 689 626 839Airflow General Notes for FAN Performance Data Tables PRE-START-UP START-UPOperating Sequence DX Cooling Temperature Control Example Service Cleaning Outdoor CoilLubrication Troubleshooting Cooling Charging Chart, 50TFQ009Page Typical Unit Wiring Schematic 208/203-3-60 Unit Shown Heating and Cooling Troubleshooting EconoMi$er IV Input/Output Logic Demand Control EnthalpyTerminal† Index Mounting Compressor UnitPage START-UP Checklist Preliminary InformationIII. START-UP