OPTIONAL ECONOMI$ER IV AND ECONOMI$ER2 — See Fig. 19 for EconoMi$er IV component locations. See Fig. 20 for EconoMi$er2 component locations.
NOTE: These instructions are for installing the optional EconoMi$er IV and EconoMi$er2 only. Refer to the accessory EconoMi$er IV or EconoMi$er2 installation instructions when field installing an EconoMi$er IV or EconoMi$er2 accessory.
1.To remove the existing unit filter access panel, raise the panel and swing the bottom outward. The panel is now disengaged from the track and can be removed. See Fig. 21.
2.The box with the economizer hood components is shipped in the compartment behind the economizer. The EconoMi$er IV controller is mounted on top of the EconoMi$er IV in the position shown in Fig. 19. The optional EconoMi$er2 with 4 to 20 mA actuator signal control does not include the EconoMi$er IV controller. To remove the component box from its shipping position, remove the screw holding the hood box bracket to the top of the economizer. Slide the hood box out of the unit. See Fig. 22.
IMPORTANT: If the power exhaust accessory is to be installed on the unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter for use in the power exhaust hood assembly.
3.The indoor coil access panel will be used as the top of the hood. Remove the screws along the sides and bottom of the indoor coil access panel. See Fig. 23.
ECONOMI$ER IV
CONTROLLER
WIRING | OUTSIDE AIR | |
TEMPERATURE SENSOR | ||
HARNESS | ||
|
LOW AMBIENT
SENSOR
ACTUATOR
Fig. 19 — EconoMi$er IV Component Locations
| OUTDOOR | |
| AIR HOOD | |
ECONOMI$ER2 | HOOD | |
PLUG | ||
SHIPPING | ||
| BRACKET |
GEAR DRIVEN
BAROMETRICDAMPER RELIEF
DAMPER
Fig. 20 — EconoMi$er2 Component Locations
4.Swing out indoor coil access panel and insert the hood sides under the panel (hood top). Use the screws provided to attach the hood sides to the hood top. Use screws pro- vided to attach the hood sides to the unit. See Fig. 24.
5.Remove the shipping tape holding the economizer baro- metric relief damper in place.
FILTER ACCESS PANEL
INDOOR COIL ACCESS PANEL
Fig. 21 — Typical Access Panel Locations
|
|
| x |
|
|
| o |
| |
o | B |
| HOOD BOX | |
H | od |
|
| |
|
|
| BRACKET | |
|
|
|
|
Fig. 22 — Hood Box Removal
SIDE
PANEL
| TOP |
| SIDE |
| PANEL |
| CAULK |
| HERE |
INDOOR | INDOOR |
COIL | COIL |
ACCESS | ACCESS |
PANEL | PANEL |
Fig. 23 — Indoor Coil Access Panel Relocation
18