OPTIONAL ECONOMI$ER IV AND ECONOMI$ER2 — See Fig. 19 for EconoMi$er IV component locations. See Fig. 20 for EconoMi$er2 component locations.

NOTE: These instructions are for installing the optional EconoMi$er IV and EconoMi$er2 only. Refer to the accessory EconoMi$er IV or EconoMi$er2 installation instructions when field installing an EconoMi$er IV or EconoMi$er2 accessory.

1.To remove the existing unit filter access panel, raise the panel and swing the bottom outward. The panel is now disengaged from the track and can be removed. See Fig. 21.

2.The box with the economizer hood components is shipped in the compartment behind the economizer. The EconoMi$er IV controller is mounted on top of the EconoMi$er IV in the position shown in Fig. 19. The optional EconoMi$er2 with 4 to 20 mA actuator signal control does not include the EconoMi$er IV controller. To remove the component box from its shipping position, remove the screw holding the hood box bracket to the top of the economizer. Slide the hood box out of the unit. See Fig. 22.

IMPORTANT: If the power exhaust accessory is to be installed on the unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter for use in the power exhaust hood assembly.

3.The indoor coil access panel will be used as the top of the hood. Remove the screws along the sides and bottom of the indoor coil access panel. See Fig. 23.

ECONOMI$ER IV

CONTROLLER

WIRING

OUTSIDE AIR

TEMPERATURE SENSOR

HARNESS

 

LOW AMBIENT

SENSOR

ACTUATOR

Fig. 19 — EconoMi$er IV Component Locations

 

OUTDOOR

 

AIR HOOD

ECONOMI$ER2

HOOD

PLUG

SHIPPING

 

BRACKET

GEAR DRIVEN

BAROMETRICDAMPER RELIEF

DAMPER

Fig. 20 — EconoMi$er2 Component Locations

4.Swing out indoor coil access panel and insert the hood sides under the panel (hood top). Use the screws provided to attach the hood sides to the hood top. Use screws pro- vided to attach the hood sides to the unit. See Fig. 24.

5.Remove the shipping tape holding the economizer baro- metric relief damper in place.

FILTER ACCESS PANEL

INDOOR COIL ACCESS PANEL

Fig. 21 — Typical Access Panel Locations

 

 

 

x

 

 

 

o

 

o

B

 

HOOD BOX

H

od

 

 

 

 

 

BRACKET

 

 

 

 

Fig. 22 — Hood Box Removal

SIDE

PANEL

 

TOP

 

SIDE

 

PANEL

 

CAULK

 

HERE

INDOOR

INDOOR

COIL

COIL

ACCESS

ACCESS

PANEL

PANEL

Fig. 23 — Indoor Coil Access Panel Relocation

18

Image 18
Contents Contents Safety ConsiderationsInstallation Roof Curb Details Unit Leveling Tolerances Rigging Details Physical Data Unit Size 50TFQBase Unit Dimensions Make Electrical Connections Electric Heating Capacities Electrical Data Units Without Electrical Convenience OutletSIZE† Electrical Data Units With Electrical Convenience Outlet 81/2 TonsOFM IFM Heat SIZE† Unit Size Adjust Factory-Installed Options Heat Anticipator Settings 208/230 460 575Stage Outdoor-Air Hood Details PremierLink Sensor Usage PremierLink ControllerPremierLink Controller Installed For Differential EconoMi$er IV Component Locations Outdoor-Air Hood Construction EconoMi$er2 with 4 to 20 mA Control Wiring Supply Air Sensor Temperature Resistance Values EconoMi$er IV Sensor UsageEconoMi$er IV Controller Potentiometer LED Locations Enthalpy Changeover Set Points Page CO2 Sensor Standard Settings UrationTypical Belt-Drive Motor Mounting for Size Size 008 Fan Motor PerformanceFan Rpm at Motor Pulley Settings Electric Heater Static Pressure* in. wg 50TFQ008-0122300 519 567 External Static Pressure in. wgRpm Bhp Watts 2250 511 538 2400 534 6302400 534 630 611 798 678 974 Rpm Bhp Watts 2250 511 538 591 697 660 8642300 519 567 597 729 666 900 2500 550 698 624 872Airflow 3900 4000 4100 4200 4250 Rpm Bhp Watts 2550 557 733 631 9103800 Rpm Bhp Watts 25503300 679 1438 741 1663 798 1892 851 2126 3100 646 1217 711 1428 770 1645 825 18693200 662 1324 726 1542 784 1765 838 1994 3400 695 1558 756 1790 812 20253200 583 712 648 865 Rpm Bhp Watts 3000 556 604 623 748 684 8913100 569 656 636 805 3300 597 770 661 9293800 668 1116 726 1299 779 1481 828 1662 3600 639 967 700 1140 754 1312 805 14843700 654 1040 713 1218 767 1395 817 1571 3900 683 1197 739 1385 792 1572 840 17584200 726 1462 780 1665 3500 625 898 687 1066 742 1233 794 14003900 683 1197 739 1385 792 1572 1132 3555 45002400 483 534 570 705 Rpm Bhp Watts 2250 465 459 555 6212300 471 483 560 648 2500 495 588 581 7672400 483 534 570 705 644 880 Rpm Bhp Watts 2250 465 459 555 621 629 7862300 471 483 560 648 634 817 2500 495 588 581 767 653 948Airflow Rpm Bhp Watts 2550 501 617 586 799 658 983 3800 662 17053900 675 1828 Airflow 3200 549 637 614 783 676 936 Rpm Bhp Watts 3000 523 541 592 680 657 8253100 536 587 603 730 666 879 3300 562 689 626 839Airflow General Notes for FAN Performance Data Tables PRE-START-UP START-UPOperating Sequence DX Cooling Temperature Control Example Service Cleaning Outdoor CoilLubrication Troubleshooting Cooling Charging Chart, 50TFQ009Page Typical Unit Wiring Schematic 208/203-3-60 Unit Shown Heating and Cooling Troubleshooting EconoMi$er IV Input/Output Logic Demand Control EnthalpyTerminal† Index Mounting Compressor UnitPage START-UP Checklist Preliminary InformationIII. START-UP