5.Turn the DCV set point potentiometer CW until the DCV LED turns off. The DCV LED should turn off when the potentiometer is approximately 9 v. The actuator should drive fully closed.

6.Turn the DCV and Exhaust potentiometers CCW until the Exhaust LED turns on. The exhaust contacts will close 30 to 120 seconds after the Exhaust LED turns on.

7.Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.

DCV MINIMUM AND MAXIMUM POSITION — To check the DCV minimum and maximum position:

1.Make sure EconoMi$er IV preparation procedure has been performed.

2.Connect a 9-v battery to AQ (positive node) and AQ1 (negative node). The DCV LED should turn on. The actuator should drive to between 90 and 95% open.

3.Turn the DCV Maximum Position potentiometer to mid- point. The actuator should drive to between 20 and 80% open.

4.Turn the DCV Maximum Position potentiometer to fully CCW. The actuator should drive fully closed.

5.Turn the Minimum Position potentiometer to midpoint. The actuator should drive to between 20 and 80% open.

6.Turn the Minimum Position Potentiometer fully CW. The actuator should drive fully open.

7.Remove the jumper from TR and N. The actuator should drive fully closed.

8.Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.

SUPPLY-AIR INPUT — To check supply-air input:

1.Make sure EconoMi$er IV preparation procedure has been performed.

2.Set the Enthalpy potentiometer to A. The Free Cool LED turns on. The actuator should drive to between 20 and 80% open.

3.Remove the 5.6 kilo-ohm resistor and jumper T to T1. The actuator should drive fully open.

4.Remove the jumper across T and T1. The actuator should drive fully closed.

5.Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.

ECONOMI$ER IV TROUBLESHOOTING COMPLE- TION — This procedure is used to return the EconoMi$er IV to operation. No troubleshooting or testing is done by perform- ing the following procedure.

1.Disconnect power at TR and TR1.

2.Set enthalpy potentiometer to previous setting.

3.Set DCV maximum position potentiometer to previous setting.

4.Set minimum position, DCV set point, and exhaust potentiometers to previous settings.

5.Remove 620-ohm resistor from terminals SR and +.

6.Remove 1.2 kilo-ohm checkout resistor from terminals SO and +. If used, reconnect sensor from terminals SO and +.

7.Remove jumper from TR to N.

8.Remove jumper from TR to 1.

9.Remove 5.6 kilo-ohm resistor from T and T1. Reconnect wires at T and T1.

10.Remove jumper from P to P1. Reconnect device at P and P1.

11.Apply power (24 vac) to terminals TR and TR1.

50

Image 50
Contents Installation ContentsSafety Considerations Roof Curb Details Unit Leveling Tolerances Rigging Details Physical Data Unit Size 50TFQBase Unit Dimensions Make Electrical Connections Electric Heating Capacities Electrical Data Units Without Electrical Convenience OutletSIZE† Electrical Data Units With Electrical Convenience Outlet 81/2 TonsOFM IFM Heat SIZE† Unit Size Adjust Factory-Installed Options Stage Heat Anticipator Settings208/230 460 575 Outdoor-Air Hood Details PremierLink Sensor Usage PremierLink ControllerPremierLink Controller Installed For Differential EconoMi$er IV Component Locations Outdoor-Air Hood Construction EconoMi$er2 with 4 to 20 mA Control Wiring Supply Air Sensor Temperature Resistance Values EconoMi$er IV Sensor UsageEconoMi$er IV Controller Potentiometer LED Locations Enthalpy Changeover Set Points Page CO2 Sensor Standard Settings UrationTypical Belt-Drive Motor Mounting for Size Size 008 Fan Motor PerformanceFan Rpm at Motor Pulley Settings Electric Heater Static Pressure* in. wg 50TFQ008-0122300 519 567 External Static Pressure in. wgRpm Bhp Watts 2250 511 538 2400 534 6302400 534 630 611 798 678 974 Rpm Bhp Watts 2250 511 538 591 697 660 8642300 519 567 597 729 666 900 2500 550 698 624 872Airflow 3900 4000 4100 4200 4250 Rpm Bhp Watts 2550 557 733 631 9103800 Rpm Bhp Watts 25503300 679 1438 741 1663 798 1892 851 2126 3100 646 1217 711 1428 770 1645 825 18693200 662 1324 726 1542 784 1765 838 1994 3400 695 1558 756 1790 812 20253200 583 712 648 865 Rpm Bhp Watts 3000 556 604 623 748 684 8913100 569 656 636 805 3300 597 770 661 9293800 668 1116 726 1299 779 1481 828 1662 3600 639 967 700 1140 754 1312 805 14843700 654 1040 713 1218 767 1395 817 1571 3900 683 1197 739 1385 792 1572 840 17584200 726 1462 780 1665 3500 625 898 687 1066 742 1233 794 14003900 683 1197 739 1385 792 1572 1132 3555 45002400 483 534 570 705 Rpm Bhp Watts 2250 465 459 555 6212300 471 483 560 648 2500 495 588 581 7672400 483 534 570 705 644 880 Rpm Bhp Watts 2250 465 459 555 621 629 7862300 471 483 560 648 634 817 2500 495 588 581 767 653 948Airflow 3900 675 1828 Rpm Bhp Watts 2550 501 617 586 799 658 9833800 662 1705 Airflow 3200 549 637 614 783 676 936 Rpm Bhp Watts 3000 523 541 592 680 657 8253100 536 587 603 730 666 879 3300 562 689 626 839Airflow General Notes for FAN Performance Data Tables PRE-START-UP START-UPOperating Sequence DX Cooling Temperature Control Example Service Cleaning Outdoor CoilLubrication Troubleshooting Cooling Charging Chart, 50TFQ009Page Typical Unit Wiring Schematic 208/203-3-60 Unit Shown Heating and Cooling Troubleshooting Terminal† EconoMi$er IV Input/Output LogicDemand Control Enthalpy Index Mounting Compressor UnitPage III. START-UP START-UP ChecklistPreliminary Information