PRE-START-UP

Failure to observe the following warnings could result in serious personal injury:

1.Follow recognized safety practices and wear protec- tive goggles when checking or servicing refrigerant system.

2.Do not operate the compressor or provide any electric power to the unit unless the compressor terminal cover is in place and secured.

3.Do not remove the compressor terminal cover until all electrical sources are disconnected.

4.Relieve all pressure from the system before touching or disturbing anything inside the compressor terminal box if a refrigerant leak is suspected around the com- pressor terminals. Use accepted methods to recover refrigerant.

5.Never attempt to repair a soldered connection while the refrigerant system is under pressure.

6.Do not use a torch to remove any component. The system contains oil and refrigerant under pressure. To remove a component, wear protective goggles and proceed as follows:

a.Shut off electrical power to the unit and tag disconnect.

b.Relieve all pressure from the system using both the high and low-pressure ports. Use accepted methods to recover refrigerant.

c.Cut the component connection tubing with tubing cutter, and remove the component from the unit.

d.Carefully unsweat the remaining tubing stubs when necessary. Oil can ignite when exposed to a torch flame.

Proceed as follows to inspect and prepare the unit for initial start-up:

1.Remove all access panels.

2.Read and follow instructions on all WARNING, CAU- TION, and INFORMATION labels attached to or shipped with unit.

3.Make the following inspections:

a.Inspect for shipping and handling damages such as broken lines, loose parts, or disconnected wires.

b.Inspect for oil at all refrigerant tubing connections and on the unit base. Detecting oil generally indi- cates a refrigerant leak. Leak-test all refrigerant tubing connections using an electronic leak detec- tor, halide torch, or liquid-soap solution.

c.Inspect all field-wiring and factory-wiring con- nections. Be sure that connections are completed and tight. Ensure that electrical wires do not contact refrigerant tubing.

d.Inspect the coil fins. If damaged during shipping and handling, carefully straighten the fins with a fin comb.

4.Verify the following conditions:

a.Make sure that the outdoor-fan blades are correctly positioned in the fan orifice. Refer to Outdoor-Fan Adjustment section on page 48 for more details.

b.Make sure that an air filter(s) is in place.

c.Make sure that the condensate drain trap is filled with water to ensure proper drainage.

d.Make sure that all tools and miscellaneous loose parts have been removed.

START-UP

Unit Preparation — Make sure that the unit has been installed in accordance with installation instructions and applicable codes.

Return-Air Filters — Make sure that the correct filters are installed in the unit (see Table 1). Do not operate the unit without return-air filters.

Outdoor-Air Inlet Screen — The outdoor-air inlet screen must be in place before operating the unit.

Compressor Mounting — Compressors are internally spring mounted. Do not loosen or remove the compressor hold- down bolts.

Internal Wiring — Check all electrical connections in unit control boxes; tighten as required.

Refrigerant Service Ports — Each refrigerant system has 3 Schrader-type service gage ports: One on the suction line, one on the cooling mode liquid line, and one on the compressor discharge line. Be sure that the caps on the ports are tight. The port on the cooling mode liquid line and one port on the discharge line have protective devices installed on them.

HIGH FLOW REFRIGERANT VALVES — Two high flow valves may be located on the hot gas tube coming out of the compressor and the suction tube going into the compressor. Large black plastic caps identify these valves with O-rings inside screwing the cap and onto a brass body. No field access to these valves is available at this time. Ensure the plastic caps remain on the valves and are tight or the possibility of refriger- ant leakage could occur.

Compressor Rotation — It is important to be certain that the scroll compressor (size 012 only) is rotating in the proper direction. To determine whether or not the compressor is rotating in the proper direction:

1.Connect service gages to the suction and discharge pres- sure fittings.

2.Energize the compressor.

3.The suction pressure should drop and the discharge pres- sure should rise, as is normal on any start-up.

If the suction pressure does not drop and the discharge pres- sure does not rise to normal levels:

1.Note that the indoor fan is probably also rotating in the wrong direction.

2.Turn off power to the unit and tag disconnect.

3.Reverse any two of the unit power leads.

4.Turn on power to the unit. Re-energize compressor.

The suction and discharge pressure levels should now move to their normal start-up levels.

NOTE: When the compressor is rotating in the wrong direction, the unit makes more noise and does not provide heating/cooling.

Cooling — To start the unit, turn on main power supply. Set the system selector switch at COOL position and the fan switch at AUTO position. Adjust the thermostat to a setting below room temperature. The compressor starts on closure of the contactor.

Check the unit charge. Refer to Refrigerant Charge section on page 48.

Reset the thermostat at a position above room temperature. The compressor will shut off.

TO SHUT OFF UNIT — Set the system selector switch at OFF position. Resetting the thermostat at a position above room temperature shuts the unit off temporarily until the space temperature exceeds the thermostat setting.

The compressor restart is accomplished by manual reset at the thermostat by turning the selector switch to OFF position and then ON position.

44

Image 44
Contents Installation ContentsSafety Considerations Roof Curb Details Unit Leveling Tolerances Rigging Details Physical Data Unit Size 50TFQBase Unit Dimensions Make Electrical Connections Electric Heating Capacities Electrical Data Units Without Electrical Convenience OutletSIZE† Electrical Data Units With Electrical Convenience Outlet 81/2 TonsOFM IFM Heat SIZE† Unit Size Adjust Factory-Installed Options Stage Heat Anticipator Settings208/230 460 575 Outdoor-Air Hood Details PremierLink Sensor Usage PremierLink ControllerPremierLink Controller Installed For Differential EconoMi$er IV Component Locations Outdoor-Air Hood Construction EconoMi$er2 with 4 to 20 mA Control Wiring Supply Air Sensor Temperature Resistance Values EconoMi$er IV Sensor UsageEconoMi$er IV Controller Potentiometer LED Locations Enthalpy Changeover Set Points Page CO2 Sensor Standard Settings UrationTypical Belt-Drive Motor Mounting for Size Size 008 Fan Motor PerformanceFan Rpm at Motor Pulley Settings Electric Heater Static Pressure* in. wg 50TFQ008-012External Static Pressure in. wg Rpm Bhp Watts 2250 511 5382300 519 567 2400 534 630Rpm Bhp Watts 2250 511 538 591 697 660 864 2300 519 567 597 729 666 9002400 534 630 611 798 678 974 2500 550 698 624 872Airflow Rpm Bhp Watts 2550 557 733 631 910 38003900 4000 4100 4200 4250 Rpm Bhp Watts 25503100 646 1217 711 1428 770 1645 825 1869 3200 662 1324 726 1542 784 1765 838 19943300 679 1438 741 1663 798 1892 851 2126 3400 695 1558 756 1790 812 2025Rpm Bhp Watts 3000 556 604 623 748 684 891 3100 569 656 636 8053200 583 712 648 865 3300 597 770 661 9293600 639 967 700 1140 754 1312 805 1484 3700 654 1040 713 1218 767 1395 817 15713800 668 1116 726 1299 779 1481 828 1662 3900 683 1197 739 1385 792 1572 840 17583500 625 898 687 1066 742 1233 794 1400 3900 683 1197 739 1385 792 15724200 726 1462 780 1665 1132 3555 4500Rpm Bhp Watts 2250 465 459 555 621 2300 471 483 560 6482400 483 534 570 705 2500 495 588 581 767Rpm Bhp Watts 2250 465 459 555 621 629 786 2300 471 483 560 648 634 8172400 483 534 570 705 644 880 2500 495 588 581 767 653 948Airflow 3900 675 1828 Rpm Bhp Watts 2550 501 617 586 799 658 9833800 662 1705 Airflow Rpm Bhp Watts 3000 523 541 592 680 657 825 3100 536 587 603 730 666 8793200 549 637 614 783 676 936 3300 562 689 626 839Airflow General Notes for FAN Performance Data Tables PRE-START-UP START-UPOperating Sequence DX Cooling Temperature Control Example Service Cleaning Outdoor CoilLubrication Troubleshooting Cooling Charging Chart, 50TFQ009Page Typical Unit Wiring Schematic 208/203-3-60 Unit Shown Heating and Cooling Troubleshooting Terminal† EconoMi$er IV Input/Output LogicDemand Control Enthalpy Index Mounting Compressor UnitPage III. START-UP START-UP ChecklistPreliminary Information