Carrier 50TFQ008-012 specifications Operating Sequence

Page 45

Heating — To start the unit, turn on the main power supply.

Set the thermostat at HEAT position at a setting above room temperature, the fan at AUTO position.

The first stage of the thermostat energizes the indoor-fan motor, compressor, and outdoor fan; the second stage energizes electric heater elements, if installed. Check the heating effects at the air supply grille(s).

If the accessory electric heaters do not energize, reset limit switch (located on indoor-fan scroll) by pressing the button located between terminals on the switch.

TO SHUT OFF UNIT — Set the system selector switch at OFF position. Resetting the heating selector lever below room temperature temporarily shuts the unit off until the space temperature falls below the thermostat setting.

Safety Relief — A soft solder joint on the suction line at the loss-of-charge/low-pressure fitting provides pressure relief under abnormal temperature and pressure conditions.

Ventilation (Continuous Fan) — Set the fan and system selector switches at ON and OFF positions, respectively. The in- door fan operates continuously to provide constant air circulation.

Operating Sequence

COOLING, UNITS WITHOUT ECONOMIZER — When thermostat calls for cooling, terminals G and Y1 are energized. The indoor-fan contactor (IFC), reversing valve solenoid (RVS1) and compressor contactor no. 1 (C1) are energized and indoor-fan motor, compressor no. 1, and outdoor fan starts. The outdoor-fan motor(s) run continuously while unit is cooling. If the thermostat calls for a second stage of cooling by energizing Y2, compressor contactor no. 2 (C2) and reversing valve sole- noid (RVS2) are energized and compressor no. 2 starts.

HEATING, UNITS WITHOUT ECONOMIZER — Upon a request for heating from the space thermostat, terminal W1 will be energized with 24 v. The IFC, outdoor-fan contactor (OFC), C1, and C2 will be energized. The reversing valves switch po- sition and the indoor fan, outdoor fan, compressor no. 1, and compressor no. 2 are energized.

If the space temperature continues to fall while W1 is ener- gized, W2 will be energized with 24 v, and the heater contac- tor(s) (HC) will be energized, which will energize the electric heater(s).

When the space thermostat is satisfied, W2 will be deener- gized first, and the electric heater(s) will be deenergized.

Upon a further rise in space temperature, W1 will be deenergized, and the reversing valve solenoids (RVS1 and RVS2) will be energized.

COOLING, UNITS WITH ECONOMI$ER IV — When free cooling is not available, the compressors will be controlled by the zone thermostat. When free cooling is available, the outdoor-air damper is modulated by the EconoMi$er IV con- trol to provide a 50 to 55 F supply-air temperature into the zone. As the supply-air temperature fluctuates above 55 or below 50 F, the dampers will be modulated (open or close) to bring the supply-air temperature back within set point limits.

For EconoMi$er IV operation, there must be a thermostat call for the fan (G). This will move the damper to its minimum position during the occupied mode.

Above 50 F supply-air temperature, the dampers will modu- late from 100% open to the minimum open position. From 50 F to 45 F supply-air temperature, the dampers will maintain at the minimum open position. Below 45 F the dampers will be completely shut. As the supply-air temperature rises, the damp- ers will come back open to the minimum open position once the supply-air temperature rises to 48 F.

If optional power exhaust is installed, as the outdoor-air damper opens and closes, the power exhaust fans will be ener- gized and deenergized.

If field-installed accessory CO2 sensors are connected to the EconoMi$er IV control, a demand controlled ventilation strate- gy will begin to operate. As the CO2 level in the zone increases above the CO2 set point, the minimum position of the damper will be increased proportionally. As the CO2 level decreases because of the increase in fresh air, the outdoor-air damper will be proportionally closed. Damper position will follow the high- er demand condition from DCV mode or free cooling mode.

Damper movement from full closed to full open (or vice versa) will take between 11/2 and 21/2 minutes.

If free cooling can be used as determined from the appropri- ate changeover command (switch, dry bulb, enthalpy curve, differential dry bulb, or differential enthalpy), a call for cooling (Y1 closes at the thermostat) will cause the control to modulate the dampers open to maintain the supply-air temperature set point at 50 to 55 F.

As the supply-air temperature drops below the set point range of 50 to 55 F, the control will modulate the outdoor-air dampers closed to maintain the proper supply-air temperature.

HEATING, UNITS WITH ECONOMI$ER IV — When the room temperature calls for heat, the heating controls are ener- gized as described in the Heating, Units Without Economizer section. When the thermostat is satisfied, the economizer damper moves to the minimum position.

COOLING, UNITS WITH ECONOMI$ER2, PREMIER- LINK™ CONTROL AND A THERMOSTAT — When free cooling is not available, the compressors will be controlled by the PremierLink control in response to the Y1 and Y2 inputs from the thermostat.

The PremierLink control will use the following information to determine if free cooling is available:

Indoor fan has been on for at least 30 seconds.

The SPT, SAT, and OAT inputs must have valid readings.

OAT must be less than 75 F.

OAT must be less than SPT.

Enthalpy must be LOW (may be jumpered if an enthalpy sensor not available).

Economizer position is NOT forced.

Pre-cooling occurs when the is no call from the thermostat except G. Pre-cooling is defined as the economizer modulates to provide 70 F supply air.

When free cooling is available the PremierLink control will control the compressors and economizer to provide a supply- air temperature determined to meet the Y1 and Y2 calls from the thermostat using the following three routines. The three control routines are based on OAT, where:

SASP = Supply Air Set Point

DXCTLO = Direct Expansion Cooling Lockout Set Point Routine 1 — (OAT < DXCTLO)

Y1 energized — economizer maintains a SASP = (SATLO1 + 3).

Y2 energized — economizer maintains a SASP = (SATLO2 + 3).

Routine 2 — (DXCTLO < OAT < 68 F)

If only Y1 energized, the economizer maintains a SASP = (SATLO1 + 3).

If SAT > SASP + 5 and economizer position > 80%, economizer will go to minimum position for 3 minutes or until SAT > 68 F.

First stage of mechanical cooling will be energized.

Integrator resets.

Economizer opens again and controls to current SASP after stage one on for 90 seconds.

With Y1 and Y2 energized Economizer maintains an SASP = SATLO2 + 3.

45

Image 45
Contents Contents Safety ConsiderationsInstallation Roof Curb Details Unit Leveling Tolerances Rigging Details Unit Size 50TFQ Physical DataBase Unit Dimensions Make Electrical Connections Electrical Data Units Without Electrical Convenience Outlet Electric Heating CapacitiesSIZE† 81/2 Tons Electrical Data Units With Electrical Convenience OutletOFM IFM Heat SIZE† Unit Size Adjust Factory-Installed Options Heat Anticipator Settings 208/230 460 575Stage Outdoor-Air Hood Details PremierLink Controller PremierLink Sensor UsagePremierLink Controller Installed For Differential EconoMi$er IV Component Locations Outdoor-Air Hood Construction EconoMi$er2 with 4 to 20 mA Control Wiring EconoMi$er IV Sensor Usage Supply Air Sensor Temperature Resistance ValuesEconoMi$er IV Controller Potentiometer LED Locations Enthalpy Changeover Set Points Page Uration CO2 Sensor Standard SettingsSize 008 Fan Motor Performance Typical Belt-Drive Motor Mounting for SizeElectric Heater Static Pressure* in. wg 50TFQ008-012 Fan Rpm at Motor Pulley SettingsRpm Bhp Watts 2250 511 538 External Static Pressure in. wg2300 519 567 2400 534 6302300 519 567 597 729 666 900 Rpm Bhp Watts 2250 511 538 591 697 660 8642400 534 630 611 798 678 974 2500 550 698 624 872Airflow 3800 Rpm Bhp Watts 2550 557 733 631 9103900 4000 4100 4200 4250 Rpm Bhp Watts 25503200 662 1324 726 1542 784 1765 838 1994 3100 646 1217 711 1428 770 1645 825 18693300 679 1438 741 1663 798 1892 851 2126 3400 695 1558 756 1790 812 20253100 569 656 636 805 Rpm Bhp Watts 3000 556 604 623 748 684 8913200 583 712 648 865 3300 597 770 661 9293700 654 1040 713 1218 767 1395 817 1571 3600 639 967 700 1140 754 1312 805 14843800 668 1116 726 1299 779 1481 828 1662 3900 683 1197 739 1385 792 1572 840 17583900 683 1197 739 1385 792 1572 3500 625 898 687 1066 742 1233 794 14004200 726 1462 780 1665 1132 3555 45002300 471 483 560 648 Rpm Bhp Watts 2250 465 459 555 6212400 483 534 570 705 2500 495 588 581 7672300 471 483 560 648 634 817 Rpm Bhp Watts 2250 465 459 555 621 629 7862400 483 534 570 705 644 880 2500 495 588 581 767 653 948Airflow Rpm Bhp Watts 2550 501 617 586 799 658 983 3800 662 17053900 675 1828 Airflow 3100 536 587 603 730 666 879 Rpm Bhp Watts 3000 523 541 592 680 657 8253200 549 637 614 783 676 936 3300 562 689 626 839Airflow General Notes for FAN Performance Data Tables START-UP PRE-START-UPOperating Sequence DX Cooling Temperature Control Example Cleaning Outdoor Coil ServiceLubrication Cooling Charging Chart, 50TFQ009 TroubleshootingPage Typical Unit Wiring Schematic 208/203-3-60 Unit Shown Heating and Cooling Troubleshooting EconoMi$er IV Input/Output Logic Demand Control EnthalpyTerminal† Mounting Compressor Unit IndexPage START-UP Checklist Preliminary InformationIII. START-UP