Heating — To start the unit, turn on the main power supply.
Set the thermostat at HEAT position at a setting above room temperature, the fan at AUTO position.
The first stage of the thermostat energizes the
If the accessory electric heaters do not energize, reset limit switch (located on
TO SHUT OFF UNIT — Set the system selector switch at OFF position. Resetting the heating selector lever below room temperature temporarily shuts the unit off until the space temperature falls below the thermostat setting.
Safety Relief — A soft solder joint on the suction line at the
Ventilation (Continuous Fan) — Set the fan and system selector switches at ON and OFF positions, respectively. The in- door fan operates continuously to provide constant air circulation.
Operating Sequence
COOLING, UNITS WITHOUT ECONOMIZER — When thermostat calls for cooling, terminals G and Y1 are energized. The
HEATING, UNITS WITHOUT ECONOMIZER — Upon a request for heating from the space thermostat, terminal W1 will be energized with 24 v. The IFC,
If the space temperature continues to fall while W1 is ener- gized, W2 will be energized with 24 v, and the heater contac- tor(s) (HC) will be energized, which will energize the electric heater(s).
When the space thermostat is satisfied, W2 will be deener- gized first, and the electric heater(s) will be deenergized.
Upon a further rise in space temperature, W1 will be deenergized, and the reversing valve solenoids (RVS1 and RVS2) will be energized.
COOLING, UNITS WITH ECONOMI$ER IV — When free cooling is not available, the compressors will be controlled by the zone thermostat. When free cooling is available, the
For EconoMi$er IV operation, there must be a thermostat call for the fan (G). This will move the damper to its minimum position during the occupied mode.
Above 50 F
If optional power exhaust is installed, as the
If
Damper movement from full closed to full open (or vice versa) will take between 11/2 and 21/2 minutes.
If free cooling can be used as determined from the appropri- ate changeover command (switch, dry bulb, enthalpy curve, differential dry bulb, or differential enthalpy), a call for cooling (Y1 closes at the thermostat) will cause the control to modulate the dampers open to maintain the
As the
HEATING, UNITS WITH ECONOMI$ER IV — When the room temperature calls for heat, the heating controls are ener- gized as described in the Heating, Units Without Economizer section. When the thermostat is satisfied, the economizer damper moves to the minimum position.
COOLING, UNITS WITH ECONOMI$ER2, PREMIER- LINK™ CONTROL AND A THERMOSTAT — When free cooling is not available, the compressors will be controlled by the PremierLink control in response to the Y1 and Y2 inputs from the thermostat.
The PremierLink control will use the following information to determine if free cooling is available:
•Indoor fan has been on for at least 30 seconds.
•The SPT, SAT, and OAT inputs must have valid readings.
•OAT must be less than 75 F.
•OAT must be less than SPT.
•Enthalpy must be LOW (may be jumpered if an enthalpy sensor not available).
•Economizer position is NOT forced.
When free cooling is available the PremierLink control will control the compressors and economizer to provide a supply- air temperature determined to meet the Y1 and Y2 calls from the thermostat using the following three routines. The three control routines are based on OAT, where:
SASP = Supply Air Set Point
DXCTLO = Direct Expansion Cooling Lockout Set Point Routine 1 — (OAT < DXCTLO)
•Y1 energized — economizer maintains a SASP = (SATLO1 + 3).
•Y2 energized — economizer maintains a SASP = (SATLO2 + 3).
Routine 2 — (DXCTLO < OAT < 68 F)
•If only Y1 energized, the economizer maintains a SASP = (SATLO1 + 3).
•If SAT > SASP + 5 and economizer position > 80%, economizer will go to minimum position for 3 minutes or until SAT > 68 F.
•First stage of mechanical cooling will be energized.
•Integrator resets.
•Economizer opens again and controls to current SASP after stage one on for 90 seconds.
•With Y1 and Y2 energized Economizer maintains an SASP = SATLO2 + 3.
45