Carrier 50TFQ008-012 specifications DX Cooling Temperature Control Example

Page 46

If SAT > SASP + 5 and economizer position >80%, economizer will go to minimum position for 3 minutes or until SAT > 68 F.

If compressor no. 1 is on then second stage of mechani- cal cooling will be energized. Otherwise the first stage will be energized.

Integrator resets.

Economizer opens again and controls to SASP after stage one on for 90 seconds.

Routine 3 — (OAT > 68)

Economizer is opened 100%.

Compressors 1 and 2 are cycled based on Y1 and Y2 using minimum on and off times and watching the sup- ply air temperature as compared to SATLO1 and SATLO2 set points.

If optional power exhaust is installed, as the outdoor-air damper opens and closes, the power exhaust fans will be ener- gized and deenergized.

If field-installed accessory CO2 sensors are connected to the PremierLink™ control, a PID-controlled demand ventilation strategy will begin to operate. As the CO2 level in the zone increases above the CO2 set point, the minimum position of the damper will be increased proportionally. As the CO2 level decreases because of the increase in fresh air, the outdoor-air damper will be proportionally closed.

HEATING, UNITS WITH ECONOMI$ER2, PREMIER- LINK CONTROL AND A THERMOSTAT — When the thermostat calls for heating, terminal W1 is energized. The PremierLink control will move the economizer damper to the minimum position if there is a call for G and closed if there is a call for W1 without G. In order to prevent thermostat from short cycling, the unit is locked into the heating mode for at least 10 minutes when W1 is energized.

COOLING, UNITS WITH ECONOMI$ER2, PREMIER- LINK CONTROL AND A ROOM SENSOR — When free cooling is not available, the compressors will be controlled by the PremierLink controller using a PID (proportional integral) Error reduction calculation as indicated by Fig. 41.

The PremierLink controller will use the following informa- tion to determine if free cooling is available:

Indoor fan has been on for at least 30 seconds.

The SPT, SAT, and OAT inputs must have valid readings.

OAT must be less than 75 F.

OAT must be less than SPT.

Enthalpy must be LOW (may be jumpered if and enthalpy sensor is not available).

Economizer position is NOT forced.

When free cooling is available, the outdoor-air damper is positioned through the use of a Proportional Integral (PID) control process to provide a calculated supply-air temperature into the zone. The supply air will maintain the space tempera- ture between the heating and cooling set points as indicated in Fig. 42.

The PremierLink control will integrate the compressor stages with the economizer based on similar logic as the three routines listed in the previous section. The SASP will float up and down based on the error reduction calculations that com- pare space temperature and space set point.

When outside-air temperature conditions require the econo- mizer to close for a compressor stage-up sequence, the econo- mizer control integrator is reset to zero after the stage-up se- quence is completed. This prevents the supply-air temperature from dropping too quickly and creating a freeze condition that would make the compressor turn off prematurely.

The high space set point is used for DX (direct expansion) cooling control, while the economizer space set point is a calculated value between the heating and cooling set points.

The economizer set point will always be at least one degree below the cooling set point, allowing for a smooth transition from mechanical cooling with economizer assist, back to economizer cooling as the cooling set point is achieved. The compressors may be used for initial cooling then the PremierLink controller will modulate the economizer using an error reduction calculation to hold the space temperature between the heating and cooling set points. See Fig. 42.

The controller uses the following conditions to determine economizer cooling:

Enthalpy is Low

SAT reading is available

OAT reading is available

SPT reading is available

OAT SPT

Economizer Position is NOT forced

If any of the above conditions are not met, the economizer submaster reference (ECSR) is set to maximum limit and the damper moves to minimum position. The operating sequence is complete. The ECSR is recalculated every 30 seconds.

If an optional power exhaust is installed, as the outdoor-air damper opens and closes, the power exhaust fans will be energized and deenergized.

If field-installed accessory CO2 sensors are connected to the PremierLink control, a PID-controlled demand ventilation strategy will begin to operate. As the CO2 level in the zone increases above the CO2 set point, the minimum position of the damper will be increased proportionally. As the CO2 level decreases because of the increase in fresh air, the outdoor-air damper will be proportionally closed.

 

 

TEMPERATURE CONTROL

TEMPERATURE

75

 

74

 

73

 

72

SET POINT

71

TEMPERATURE

70

 

SPACE

 

69

 

68

 

 

 

 

 

TIME

NOTE: PremierLink control performs smart staging of 2 stages of DX cooling and up to 3 stages of heat.

Fig. 41 — DX Cooling Temperature

Control Example

 

 

TEMPERATURE CONTROL

TEMPERATURE

75

 

74

 

73

 

72

COOL SETPOINT

71

TEMPERATURE

70

HEAT SETPOINT

SPACE

69

 

68

 

 

 

 

 

TIME

Fig. 42 — Economizer Temperature

Control Example

46

Image 46
Contents Safety Considerations ContentsInstallation Roof Curb Details Unit Leveling Tolerances Rigging Details Physical Data Unit Size 50TFQBase Unit Dimensions Make Electrical Connections Electric Heating Capacities Electrical Data Units Without Electrical Convenience OutletSIZE† Electrical Data Units With Electrical Convenience Outlet 81/2 TonsOFM IFM Heat SIZE† Unit Size Adjust Factory-Installed Options 208/230 460 575 Heat Anticipator SettingsStage Outdoor-Air Hood Details PremierLink Sensor Usage PremierLink ControllerPremierLink Controller Installed For Differential EconoMi$er IV Component Locations Outdoor-Air Hood Construction EconoMi$er2 with 4 to 20 mA Control Wiring Supply Air Sensor Temperature Resistance Values EconoMi$er IV Sensor UsageEconoMi$er IV Controller Potentiometer LED Locations Enthalpy Changeover Set Points Page CO2 Sensor Standard Settings UrationTypical Belt-Drive Motor Mounting for Size Size 008 Fan Motor PerformanceFan Rpm at Motor Pulley Settings Electric Heater Static Pressure* in. wg 50TFQ008-0122300 519 567 External Static Pressure in. wgRpm Bhp Watts 2250 511 538 2400 534 6302400 534 630 611 798 678 974 Rpm Bhp Watts 2250 511 538 591 697 660 8642300 519 567 597 729 666 900 2500 550 698 624 872Airflow 3900 4000 4100 4200 4250 Rpm Bhp Watts 2550 557 733 631 9103800 Rpm Bhp Watts 25503300 679 1438 741 1663 798 1892 851 2126 3100 646 1217 711 1428 770 1645 825 18693200 662 1324 726 1542 784 1765 838 1994 3400 695 1558 756 1790 812 20253200 583 712 648 865 Rpm Bhp Watts 3000 556 604 623 748 684 8913100 569 656 636 805 3300 597 770 661 9293800 668 1116 726 1299 779 1481 828 1662 3600 639 967 700 1140 754 1312 805 14843700 654 1040 713 1218 767 1395 817 1571 3900 683 1197 739 1385 792 1572 840 17584200 726 1462 780 1665 3500 625 898 687 1066 742 1233 794 14003900 683 1197 739 1385 792 1572 1132 3555 45002400 483 534 570 705 Rpm Bhp Watts 2250 465 459 555 6212300 471 483 560 648 2500 495 588 581 7672400 483 534 570 705 644 880 Rpm Bhp Watts 2250 465 459 555 621 629 7862300 471 483 560 648 634 817 2500 495 588 581 767 653 948Airflow 3800 662 1705 Rpm Bhp Watts 2550 501 617 586 799 658 9833900 675 1828 Airflow 3200 549 637 614 783 676 936 Rpm Bhp Watts 3000 523 541 592 680 657 8253100 536 587 603 730 666 879 3300 562 689 626 839Airflow General Notes for FAN Performance Data Tables PRE-START-UP START-UPOperating Sequence DX Cooling Temperature Control Example Service Cleaning Outdoor CoilLubrication Troubleshooting Cooling Charging Chart, 50TFQ009Page Typical Unit Wiring Schematic 208/203-3-60 Unit Shown Heating and Cooling Troubleshooting Demand Control Enthalpy EconoMi$er IV Input/Output LogicTerminal† Index Mounting Compressor UnitPage Preliminary Information START-UP ChecklistIII. START-UP