Carrier 50TFQ008-012 specifications Outdoor-Air Hood Construction

Page 19

6.Insert the hood divider between the hood sides. See Fig. 24 and 25. Secure hood divider with 2 screws on each hood side. The hood divider is also used as the bot- tom filter rack for the aluminum filter.

7.Open the filter clips which are located underneath the hood top. Insert the aluminum filter into the bottom filter rack (hood divider). Push the filter into position past the open filter clips. Close the filter clips to lock the filter into place. See Fig. 25.

8.Caulk the ends of the joint between the unit top panel and the hood top. See Fig. 23.

9.Replace the filter access panel.

10.Install all EconoMi$er IV accessories. EconoMi$er IV wiring is shown in Fig. 26. EconoMi$er2 wiring is shown in Fig. 27.

Barometric flow capacity is shown in Fig. 28. Outdoor air leakage is shown in Fig. 29. Return air pressure drop is shown in Fig. 30.

22 1/4”

LEFT

HOOD

SIDE

24 9/16”

B

TOP

PANEL

INDOOR COIL

ACCESS PANEL

SCREW

40 3/8”

HOOD DIVIDER

DIVIDER

OUTSIDE

AIR

HOOD

CLEANABLE

ALUMINUM FILTER FILTER

Fig. 24 — Outdoor-Air Hood Construction

BAROMETRIC RELIEF

FILTER CLIP

Fig. 25 — Filter Installation

FOR OCCUPANCY CONTROL

REPLACE JUMPER WITH

FIELD-SUPPLIED TIME CLOCK

LEGEND

Potentiometer Defaults Settings:

DCV— Demand Controlled Ventilation

Power Exhaust

Middle

Minimum Pos.

Fully Closed

IAQ — Indoor Air Quality

DCV Max.

Middle

LA — Low Ambient Lockout Device

DCV Set

Middle

OAT — Outdoor-Air Temperature

Enthalpy

C Setting

POT — Potentiometer

 

 

RAT — Return-Air Temperature

NOTES:

1.620 ohm, 1 watt 5% resistor should be removed only when using differential enthalpy or dry bulb.

2.If a separate field-supplied 24 v transformer is used for the IAQ sensor power supply, it cannot have the secondary of the transformer grounded.

3.For field-installed remote minimum position POT, remove black wire jumper between P and P1 and set control minimum position POT. to the minimum position.

Fig. 26 — EconoMi$er IV Wiring

19

Image 19
Contents Safety Considerations ContentsInstallation Roof Curb Details Unit Leveling Tolerances Rigging Details Unit Size 50TFQ Physical DataBase Unit Dimensions Make Electrical Connections Electrical Data Units Without Electrical Convenience Outlet Electric Heating CapacitiesSIZE† 81/2 Tons Electrical Data Units With Electrical Convenience OutletOFM IFM Heat SIZE† Unit Size Adjust Factory-Installed Options 208/230 460 575 Heat Anticipator SettingsStage Outdoor-Air Hood Details PremierLink Controller PremierLink Sensor UsagePremierLink Controller Installed For Differential EconoMi$er IV Component Locations Outdoor-Air Hood Construction EconoMi$er2 with 4 to 20 mA Control Wiring EconoMi$er IV Sensor Usage Supply Air Sensor Temperature Resistance ValuesEconoMi$er IV Controller Potentiometer LED Locations Enthalpy Changeover Set Points Page Uration CO2 Sensor Standard SettingsSize 008 Fan Motor Performance Typical Belt-Drive Motor Mounting for SizeElectric Heater Static Pressure* in. wg 50TFQ008-012 Fan Rpm at Motor Pulley Settings2400 534 630 External Static Pressure in. wgRpm Bhp Watts 2250 511 538 2300 519 5672500 550 698 624 872 Rpm Bhp Watts 2250 511 538 591 697 660 8642300 519 567 597 729 666 900 2400 534 630 611 798 678 974Airflow Rpm Bhp Watts 2550 Rpm Bhp Watts 2550 557 733 631 9103800 3900 4000 4100 4200 42503400 695 1558 756 1790 812 2025 3100 646 1217 711 1428 770 1645 825 18693200 662 1324 726 1542 784 1765 838 1994 3300 679 1438 741 1663 798 1892 851 21263300 597 770 661 929 Rpm Bhp Watts 3000 556 604 623 748 684 8913100 569 656 636 805 3200 583 712 648 8653900 683 1197 739 1385 792 1572 840 1758 3600 639 967 700 1140 754 1312 805 14843700 654 1040 713 1218 767 1395 817 1571 3800 668 1116 726 1299 779 1481 828 16621132 3555 4500 3500 625 898 687 1066 742 1233 794 14003900 683 1197 739 1385 792 1572 4200 726 1462 780 16652500 495 588 581 767 Rpm Bhp Watts 2250 465 459 555 6212300 471 483 560 648 2400 483 534 570 7052500 495 588 581 767 653 948 Rpm Bhp Watts 2250 465 459 555 621 629 7862300 471 483 560 648 634 817 2400 483 534 570 705 644 880Airflow 3800 662 1705 Rpm Bhp Watts 2550 501 617 586 799 658 9833900 675 1828 Airflow 3300 562 689 626 839 Rpm Bhp Watts 3000 523 541 592 680 657 8253100 536 587 603 730 666 879 3200 549 637 614 783 676 936Airflow General Notes for FAN Performance Data Tables START-UP PRE-START-UPOperating Sequence DX Cooling Temperature Control Example Cleaning Outdoor Coil ServiceLubrication Cooling Charging Chart, 50TFQ009 TroubleshootingPage Typical Unit Wiring Schematic 208/203-3-60 Unit Shown Heating and Cooling Troubleshooting Demand Control Enthalpy EconoMi$er IV Input/Output LogicTerminal† Mounting Compressor Unit IndexPage Preliminary Information START-UP ChecklistIII. START-UP