Carrier 50TFQ008-012 specifications Unit Leveling Tolerances

Page 3

MAXIMUM ALLOWABLE

DIFFERENCE (in.)

A-B

B-C

A-C

0.5

1.0

1.0

Fig. 2 — Unit Leveling Tolerances

SLAB MOUNT (Horizontal Units Only) — Provide a level concrete slab that extends a minimum of 6 in. beyond the unit cabinet on all sides. Install a gravel apron in front of the outdoor coil air inlet to prevent grass and foliage from obstruct- ing airflow.

NOTE: Horizontal units may be installed on a roof curb if required.

ALTERNATE UNIT SUPPORT — When the curb or adapter cannot be used, support unit with sleeper rails using unit curb or adapter support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side.

Step 2 — Field Fabricate Ductwork — On verti- cal discharge units, secure all ducts to the roof curb and building structure. Do not connect ductwork to the unit. For horizontal applications, field-supplied flanges should be attached to horizontal discharge openings and all ductwork attached to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accor- dance with applicable codes.

Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.

If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applica- ble fire codes.

A minimum clearance is not required around ductwork. Cabinet return-air static pressure (a negative condition) should not exceed 0.35 in. wg with economizer, or 0.45 in. wg without economizer.

Step 3 — Install Condensate Drain Line and External Trap — Condensate drain connections are locat- ed at the bottom and end of the unit. Unit discharge connec- tions do not determine the use of drain connections; either drain connection can be used in vertical or horizontal applications.

When using the standard end drain connection, make sure the plug in the alternate bottom connection is tight before in- stalling the unit.

To use the bottom drain connection for a roof curb installa- tion, relocate the factory-installed plug from the bottom connec- tion to the end connection. The center drain plug looks like a star connection, but can be removed with a 1/2-in. socket drive exten- sion. See Fig. 3. The piping for the condensate drain and external trap can be completed after the unit is in place.

All units must have an external trap for condensate drain- age. Install a trap at least 4-in. deep and protect against freeze- up. If drain line is installed downstream from the external trap,

pitch the line away from the unit at 1/4-in. per ft of run. Do not use a pipe size smaller than the unit connection. See Fig. 4.

Step 4 — Rig and Place Unit — Inspect the unit for transportation damage. File any claim with the transportation agency. Keep the unit upright and do not drop it. Spreader bars are not required if top crating is left on the unit. Rollers may be used to move the unit across a roof. Level by using the unit frame as a reference. See Table 1 and Fig. 5 for additional information. Operating weight is shown in Table 1 and Fig. 5.

Lifting holes are provided in the base rails as shown in Fig. 5 and 6. Refer to rigging instructions on the unit.

POSITIONING — Maintain clearance around and above the unit to provide proper airflow and service access. See Fig. 6.

Position the unit on the roof curb so that the following clear- ances are maintained: 1/4-in. clearance between the roof curb and base rails on each side and in front of the unit; 35/16-in. clearance between the roof curb and the outdoor fan end of the unit (see Fig. 1, section C-C).

Do not install the unit indoors. Do not locate the unit air inlet near exhaust vents or other sources of contaminated air.

Although the unit is weatherproof, guard against water from higher level runoff and overhangs.

After the unit is in position, remove the polyethylene ship- ping wrapper and rigging skid.

HORIZONTAL

DRAIN PLUG

DRAIN OUTLET

 

NOTE: Drain plug is shown in factory-installed position.

Fig. 3 — Condensate Drain Pan (Side View)

NOTE: Trap should be deep enough to offset maximum unit static difference. A 4-in. trap is recommended.

Fig. 4 — Condensate Drain Piping Details

3

Image 3
Contents Contents Safety ConsiderationsInstallation Roof Curb Details Unit Leveling Tolerances Rigging Details Unit Size 50TFQ Physical DataBase Unit Dimensions Make Electrical Connections Electrical Data Units Without Electrical Convenience Outlet Electric Heating CapacitiesSIZE† 81/2 Tons Electrical Data Units With Electrical Convenience OutletOFM IFM Heat SIZE† Unit Size Adjust Factory-Installed Options Heat Anticipator Settings 208/230 460 575Stage Outdoor-Air Hood Details PremierLink Controller PremierLink Sensor UsagePremierLink Controller Installed For Differential EconoMi$er IV Component Locations Outdoor-Air Hood Construction EconoMi$er2 with 4 to 20 mA Control Wiring EconoMi$er IV Sensor Usage Supply Air Sensor Temperature Resistance ValuesEconoMi$er IV Controller Potentiometer LED Locations Enthalpy Changeover Set Points Page Uration CO2 Sensor Standard SettingsSize 008 Fan Motor Performance Typical Belt-Drive Motor Mounting for SizeElectric Heater Static Pressure* in. wg 50TFQ008-012 Fan Rpm at Motor Pulley Settings2400 534 630 External Static Pressure in. wgRpm Bhp Watts 2250 511 538 2300 519 5672500 550 698 624 872 Rpm Bhp Watts 2250 511 538 591 697 660 8642300 519 567 597 729 666 900 2400 534 630 611 798 678 974Airflow Rpm Bhp Watts 2550 Rpm Bhp Watts 2550 557 733 631 9103800 3900 4000 4100 4200 42503400 695 1558 756 1790 812 2025 3100 646 1217 711 1428 770 1645 825 18693200 662 1324 726 1542 784 1765 838 1994 3300 679 1438 741 1663 798 1892 851 21263300 597 770 661 929 Rpm Bhp Watts 3000 556 604 623 748 684 8913100 569 656 636 805 3200 583 712 648 8653900 683 1197 739 1385 792 1572 840 1758 3600 639 967 700 1140 754 1312 805 14843700 654 1040 713 1218 767 1395 817 1571 3800 668 1116 726 1299 779 1481 828 16621132 3555 4500 3500 625 898 687 1066 742 1233 794 14003900 683 1197 739 1385 792 1572 4200 726 1462 780 16652500 495 588 581 767 Rpm Bhp Watts 2250 465 459 555 6212300 471 483 560 648 2400 483 534 570 7052500 495 588 581 767 653 948 Rpm Bhp Watts 2250 465 459 555 621 629 7862300 471 483 560 648 634 817 2400 483 534 570 705 644 880Airflow Rpm Bhp Watts 2550 501 617 586 799 658 983 3800 662 17053900 675 1828 Airflow 3300 562 689 626 839 Rpm Bhp Watts 3000 523 541 592 680 657 8253100 536 587 603 730 666 879 3200 549 637 614 783 676 936Airflow General Notes for FAN Performance Data Tables START-UP PRE-START-UPOperating Sequence DX Cooling Temperature Control Example Cleaning Outdoor Coil ServiceLubrication Cooling Charging Chart, 50TFQ009 TroubleshootingPage Typical Unit Wiring Schematic 208/203-3-60 Unit Shown Heating and Cooling Troubleshooting EconoMi$er IV Input/Output Logic Demand Control EnthalpyTerminal† Mounting Compressor Unit IndexPage START-UP Checklist Preliminary InformationIII. START-UP