Carrier 50TFQ008-012 specifications For Differential

Page 17

Enthalpy Sensors and Control — The enthalpy control (HH57AC077) is supplied as a field-installed accessory to be used with the economizer damper control option. The outdoor air enthalpy sensor is part of the enthalpy control. The separate field-installed accessory return air enthalpy sensor (HH57AC078) is required for differential enthalpy control.

NOTE: The enthalpy control must be set to the “D” setting for differential enthalpy control to work properly.

The enthalpy control receives the indoor and return enthalpy from the outdoor and return air enthalpy sensors and provides a dry contact switch input to the PremierLink™ controller. Locate the controller in place of an existing econo- mizer controller or near the actuator. The mounting plate may not be needed if existing bracket is used.

A closed contact indicates that outside air is preferred to the return air. An open contact indicates that the economizer should remain at minimum position.

Outdoor Air Enthalpy Sensor/Enthalpy Controller (HH57AC077) — To wire the outdoor air enthalpy sensor, perform the following (see Fig. 17 and 18):

NOTE: The outdoor air sensor can be removed from the back of the enthalpy controller and mounted remotely.

1.Use a 4-conductor, 18 or 20 AWG cable to connect the enthalpy control to the PremierLink controller and power transformer.

2.Connect the following 4 wires from the wire harness located in rooftop unit to the enthalpy controller:

a.Connect the BRN wire to the 24 vac terminal (TR1) on enthalpy control and to pin 1 on 12-pin harness.

b.Connect the RED wire to the 24 vac GND terminal (TR) on enthalpy sensor and to pin 4 on 12-pin harness.

c.Connect the GRAY/ORN wire to J4-2 on Premier- Link controller and to terminal (3) on enthalpy sensor.

d.Connect the GRAY/RED wire to J4-1 on Premier- Link controller and to terminal (2) on enthalpy sensor.

NOTE: If installing in a Carrier rooftop, use the two gray wires provided from the control section to the economizer to connect PremierLink controller to terminals 2 and 3 on enthalpy sensor.

If NOT using Carrier equipment, wires may need to be field supplied and installed.

Return Air Enthalpy Sensor — Mount the return-air enthalpy sensor (HH57AC078) in the return-air duct. The return air sensor is wired to the enthalpy controller (HH57AC077). The outdoor enthalpy changeover set point is set at the controller.

To wire the return air enthalpy sensor, perform the follow- ing (see Fig. 17):

1.Use a 2-conductor, 18 or 20 AWG, twisted pair cable to connect the return air enthalpy sensor to the enthalpy controller.

2.At the enthalpy control remove the factory-installed resistor from the (SR) and (+) terminals.

3.Connect the field-supplied RED wire to (+) spade connector on the return air enthalpy sensor and the (SR+) terminal on the enthalpy controller. Connect the BLK wire to (S) spade connector on the return air enthalpy sensor and the (SR) terminal on the enthalpy controller.

ENTHALPY CONTROLLER

RED

 

 

 

 

 

S (OUTDOOR

 

 

 

 

 

 

 

 

 

+

AIR

 

 

 

 

BRN

 

 

 

 

 

A B C

TR

TR1

 

 

BLK

 

 

ENTHALPY

 

 

 

 

 

 

SENSOR)

 

 

 

 

 

 

 

 

 

 

D

SO

+

 

 

 

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

SR

+

 

 

 

 

 

 

 

S (RETURN AIR

 

 

 

 

 

 

 

 

 

 

+

ENTHALPY

 

2

3

 

 

 

 

 

 

 

 

SENSOR)

 

1

 

 

GRAY/ORN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LED

 

 

 

 

 

 

 

 

WIRE HARNESS

 

 

 

 

GRAY/RED

IN UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

1.Remove factory-installed jumper across SR and + before con- necting wires from return air sensor.

2.Switches shown in high outdoor air enthalpy state. Terminals 2 and 3 close on low outdoor air enthalpy relative to indoor air enthalpy.

3.Remove sensor mounted on back of control and locate in out- door airstream.

Fig. 17 — Outdoor and Return Air Sensor Wiring Connections for Differential Enthalpy Control

HH57AC077

ENTHALPY

CONTROL AND

BRACKET OUTDOOR AIR

ENTHALPY

SENSOR

HH57AC078 ENTHALPY

 

SENSOR (USED WITH

 

ENTHALPY CONTROL

C7400A1004

FOR DIFFERENTIAL

ENTHALPY OPERATION)

+

MOUNTING PLATE

Fig. 18 — Differential Enthalpy Control,

Sensor and Mounting Plate (33AMKITENT006)

17

Image 17
Contents Installation ContentsSafety Considerations Roof Curb Details Unit Leveling Tolerances Rigging Details Unit Size 50TFQ Physical DataBase Unit Dimensions Make Electrical Connections Electrical Data Units Without Electrical Convenience Outlet Electric Heating CapacitiesSIZE† 81/2 Tons Electrical Data Units With Electrical Convenience OutletOFM IFM Heat SIZE† Unit Size Adjust Factory-Installed Options Stage Heat Anticipator Settings208/230 460 575 Outdoor-Air Hood Details PremierLink Controller PremierLink Sensor UsagePremierLink Controller Installed For Differential EconoMi$er IV Component Locations Outdoor-Air Hood Construction EconoMi$er2 with 4 to 20 mA Control Wiring EconoMi$er IV Sensor Usage Supply Air Sensor Temperature Resistance ValuesEconoMi$er IV Controller Potentiometer LED Locations Enthalpy Changeover Set Points Page Uration CO2 Sensor Standard SettingsSize 008 Fan Motor Performance Typical Belt-Drive Motor Mounting for SizeElectric Heater Static Pressure* in. wg 50TFQ008-012 Fan Rpm at Motor Pulley SettingsRpm Bhp Watts 2250 511 538 External Static Pressure in. wg2300 519 567 2400 534 6302300 519 567 597 729 666 900 Rpm Bhp Watts 2250 511 538 591 697 660 8642400 534 630 611 798 678 974 2500 550 698 624 872Airflow 3800 Rpm Bhp Watts 2550 557 733 631 9103900 4000 4100 4200 4250 Rpm Bhp Watts 25503200 662 1324 726 1542 784 1765 838 1994 3100 646 1217 711 1428 770 1645 825 18693300 679 1438 741 1663 798 1892 851 2126 3400 695 1558 756 1790 812 20253100 569 656 636 805 Rpm Bhp Watts 3000 556 604 623 748 684 8913200 583 712 648 865 3300 597 770 661 9293700 654 1040 713 1218 767 1395 817 1571 3600 639 967 700 1140 754 1312 805 14843800 668 1116 726 1299 779 1481 828 1662 3900 683 1197 739 1385 792 1572 840 17583900 683 1197 739 1385 792 1572 3500 625 898 687 1066 742 1233 794 14004200 726 1462 780 1665 1132 3555 45002300 471 483 560 648 Rpm Bhp Watts 2250 465 459 555 6212400 483 534 570 705 2500 495 588 581 7672300 471 483 560 648 634 817 Rpm Bhp Watts 2250 465 459 555 621 629 7862400 483 534 570 705 644 880 2500 495 588 581 767 653 948Airflow 3900 675 1828 Rpm Bhp Watts 2550 501 617 586 799 658 9833800 662 1705 Airflow 3100 536 587 603 730 666 879 Rpm Bhp Watts 3000 523 541 592 680 657 8253200 549 637 614 783 676 936 3300 562 689 626 839Airflow General Notes for FAN Performance Data Tables START-UP PRE-START-UPOperating Sequence DX Cooling Temperature Control Example Cleaning Outdoor Coil ServiceLubrication Cooling Charging Chart, 50TFQ009 TroubleshootingPage Typical Unit Wiring Schematic 208/203-3-60 Unit Shown Heating and Cooling Troubleshooting Terminal† EconoMi$er IV Input/Output LogicDemand Control Enthalpy Mounting Compressor Unit IndexPage III. START-UP START-UP ChecklistPreliminary Information