Carrier 50TFQ008-012 specifications Outdoor-Air Hood Details

Page 14

Fig. 12 — Outdoor-Air Hood Details

SCREW HOLES (TOP)

HOOD

HOOD SCREEN LOCATION (SCREEN NOT SHOWN)

Fig. 13 — Optional Manual Outdoor-Air

Damper with Hood Attached

Fig. 14 — Outdoor Air Damper Position Setting

PREMIERLINK™ CONTROL — The PremierLink control- ler is compatible with Carrier Comfort Network® (CCN) devices. This control is designed to allow users the access and ability to change factory-defined settings, thus expanding the function of the standard unit control board. Carrier’s diag- nostic standard tier display tools such as Navigator™ module or Scrolling Marquee can be used with the PremierLink controller.

The PremierLink controller (see Fig. 15A and 15B) requires a Carrier electronic thermostat or a CCN connection for time broadcast to initiate its internal timeclock. This is necessary for broadcast of time of day functions (occupied/unoccupied). Re- fer to Fig. 16. The PremierLink control may be mounted in the control panel or an area below the control panel.

NOTE: PremierLink versions 1.3 and later are shipped in Sen- sor mode. If used with a thermostat, the PremierLink control must be configured to Thermostat mode.

The PremierLink control includes a supply-air temperature sensor (SAT) and an outdoor-air temperature sensor (OAT) as standard. An indoor-air quality (CO2) sensor can be added as an option. Refer to Table 5 for sensor usage.

Install the Supply Air Temperature (SAT) Sensor — When the unit is supplied with a factory-mounted PremierLink con- trol, the supply-air temperature (SAT) sensor (33ZCSENSAT) is factory-supplied and wired. The wiring is routed from the PremierLink control over the control box, through a grommet, into the fan section, down along the back side of the fan, and along the fan deck over to the supply-air opening.

The SAT probe is wire-tied to the supply-air opening (on the horizontal opening end) in its shipping position. Remove the sensor for installation. Re-position the sensor for installation. Re-position the sensor in the flange of the supply-air opening or in the supply air duct (as required by local codes). Drill or punch a 1/2-in. hole in the flange or duct. Use two field- supplied, self-drilling screws to secure the sensor probe in a horizontal orientation.

NOTE: The sensor must be mounted in the discharge airstream downstream of the cooling coil and any heating devices. Be sure that the probe tip does not come in contact with any of the unit or heat surfaces.

Outdoor Air Temperature (OAT) Sensor — When the unit is supplied with a factory-mounted PremierLink control, the outdoor-air temperature (OAT) sensor is factory-supplied and wired.

Install the Indoor Air Quality (CO2) Sensor — Mount the optional indoor air quality (CO2) sensor according to manufac- turer specifications.

A separate field-supplied transformer must be used to pow- er the CO2 sensor.

Wire the CO2 sensor to the COM and IAQI terminals of J5 on the PremierLink controller. Refer to the PremierLink Instal- lation, Start-up, and Configuration Instructions for detailed wiring and configuration information.

14

Image 14
Contents Installation ContentsSafety Considerations Roof Curb Details Unit Leveling Tolerances Rigging Details Physical Data Unit Size 50TFQBase Unit Dimensions Make Electrical Connections Electric Heating Capacities Electrical Data Units Without Electrical Convenience OutletSIZE† Electrical Data Units With Electrical Convenience Outlet 81/2 TonsOFM IFM Heat SIZE† Unit Size Adjust Factory-Installed Options Stage Heat Anticipator Settings208/230 460 575 Outdoor-Air Hood Details PremierLink Sensor Usage PremierLink ControllerPremierLink Controller Installed For Differential EconoMi$er IV Component Locations Outdoor-Air Hood Construction EconoMi$er2 with 4 to 20 mA Control Wiring Supply Air Sensor Temperature Resistance Values EconoMi$er IV Sensor UsageEconoMi$er IV Controller Potentiometer LED Locations Enthalpy Changeover Set Points Page CO2 Sensor Standard Settings UrationTypical Belt-Drive Motor Mounting for Size Size 008 Fan Motor PerformanceFan Rpm at Motor Pulley Settings Electric Heater Static Pressure* in. wg 50TFQ008-0122300 519 567 External Static Pressure in. wgRpm Bhp Watts 2250 511 538 2400 534 6302400 534 630 611 798 678 974 Rpm Bhp Watts 2250 511 538 591 697 660 8642300 519 567 597 729 666 900 2500 550 698 624 872Airflow 3900 4000 4100 4200 4250 Rpm Bhp Watts 2550 557 733 631 9103800 Rpm Bhp Watts 25503300 679 1438 741 1663 798 1892 851 2126 3100 646 1217 711 1428 770 1645 825 18693200 662 1324 726 1542 784 1765 838 1994 3400 695 1558 756 1790 812 20253200 583 712 648 865 Rpm Bhp Watts 3000 556 604 623 748 684 8913100 569 656 636 805 3300 597 770 661 9293800 668 1116 726 1299 779 1481 828 1662 3600 639 967 700 1140 754 1312 805 14843700 654 1040 713 1218 767 1395 817 1571 3900 683 1197 739 1385 792 1572 840 17584200 726 1462 780 1665 3500 625 898 687 1066 742 1233 794 14003900 683 1197 739 1385 792 1572 1132 3555 45002400 483 534 570 705 Rpm Bhp Watts 2250 465 459 555 6212300 471 483 560 648 2500 495 588 581 7672400 483 534 570 705 644 880 Rpm Bhp Watts 2250 465 459 555 621 629 7862300 471 483 560 648 634 817 2500 495 588 581 767 653 948Airflow 3900 675 1828 Rpm Bhp Watts 2550 501 617 586 799 658 9833800 662 1705 Airflow 3200 549 637 614 783 676 936 Rpm Bhp Watts 3000 523 541 592 680 657 8253100 536 587 603 730 666 879 3300 562 689 626 839Airflow General Notes for FAN Performance Data Tables PRE-START-UP START-UPOperating Sequence DX Cooling Temperature Control Example Service Cleaning Outdoor CoilLubrication Troubleshooting Cooling Charging Chart, 50TFQ009Page Typical Unit Wiring Schematic 208/203-3-60 Unit Shown Heating and Cooling Troubleshooting Terminal† EconoMi$er IV Input/Output LogicDemand Control Enthalpy Index Mounting Compressor UnitPage III. START-UP START-UP ChecklistPreliminary Information