FILTERS — Clean or replace at the start of each heating and cooling season, or more often if operating conditions require it. Replacement filters must be the same dimensions as original filters.
Lubrication
COMPRESSORS — Each compressor is charged with correct amount of oil at the factory.
FAN MOTOR BEARINGS — Fan motor bearings are per- manently lubricated. No further lubrication of outdoor or
Outdoor Fan Adjustment (Fig. 46)
1.Shut off the unit power supply and tag disconnect.
2.Remove the
3.Adjust the fan height as shown in Fig. 46.
4.Tighten the setscrews and replace the
UNIT | “A” |
VOLTAGE | in. |
208/230 V | 2.75 |
460 V and 575 V | 3.50 |
Fig. 46 — Outdoor Fan Adjustment
Blower Belt Adjustment — Inspect the blower belt for wear, proper belt tension, and pulley alignment as condi- tions require or at the beginning of each heating and air condi- tioning season.
Refer to Step 7 — Adjust
Freezestat — Located on the “hair pin” end of the indoor coil is a bimetal temperature sensing switch. This switch pro- tects the evaporator coil from
Refrigerant Charge — The amount of refrigerant charge is listed on the unit nameplate (also refer to Table 1). Refer to Carrier Refrigerant Service Techniques Manual, Refrigerants section.
Unit panels must be in place when the unit is operating during charging procedure.
NO CHARGE — Use standard evacuating techniques. After evacuating the system, weigh in the specified amount of refrig- erant (refer to Table 1).
LOW CHARGE COOLING — Use the Cooling Charging Charts, Fig.
TO USE COOLING CHARGING CHARTS — Take the out- door ambient temperature and read the suction pressure gage. Refer to the appropriate chart to determine what the suction temperature should be. If the suction temperature is high, add refrigerant. If the suction temperature is low, carefully recover some of the charge. Recheck the suction pressure as charge is adjusted.
EXAMPLE: (Fig. 47)
Outdoor Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 F Suction Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 psig Suction Temperature should be . . . . . . . . . . . . . . . . . . . . . 49 F (Suction Temperature may vary ±5° F.)
HEATING CHARGE — Do not attempt to adjust refrigerant charge while the unit is operating in the heating mode. If the charge amount is believed to be incorrect, recover refrigerant and weigh in the amount listed on the unit rating plate.
Replacement Parts — A complete list of replacement parts can be obtained from any Carrier distributor.
Fig. 47 — Cooling Charging Chart, 50TFQ008
48