Carrier 50TFQ008-012 specifications Troubleshooting, Cooling Charging Chart, 50TFQ009

Page 49

Fig. 48 — Cooling Charging Chart, 50TFQ009

TROUBLESHOOTING

Unit Troubleshooting — For unit troubleshooting, re- fer to Fig. 50 and Table 28.

EconoMi$er IV Troubleshooting — See Table 29 for EconoMi$er IV logic.

A functional view of the EconoMi$er IV is shown in Fig. 51. Typical settings, sensor ranges, and jumper positions are also shown. An EconoMi$er IV simulator program is avail- able from Carrier to help with EconoMi$er IV training and troubleshooting.

ECONOMI$ER IV PREPARATION — This procedure is used to prepare the EconoMi$er IV for troubleshooting. No troubleshooting or testing is done by performing the following procedure.

NOTE: This procedure requires a 9-v battery, 1.2 kilo-ohm resistor, and a 5.6 kilo-ohm resistor which are not supplied with the EconoMi$er IV.

IMPORTANT: Be sure to record the positions of all poten- tiometers before starting troubleshooting.

1.Disconnect power at TR and TR1. All LEDs should be off. Exhaust fan contacts should be open.

2.Disconnect device at P and P1.

3.Jumper P to P1.

4.Disconnect wires at T and T1. Place 5.6 kilo-ohm resistor across T and T1.

5.Jumper TR to 1.

6.Jumper TR to N.

7.If connected, remove sensor from terminals SO and +. Connect 1.2 kilo-ohm 4074EJM checkout resistor across terminals SO and +.

8.Put 620-ohm resistor across terminals SR and +.

9.Set minimum position, DCV set point, and exhaust potentiometers fully CCW (counterclockwise).

10.Set DCV maximum position potentiometer fully CW (clockwise).

Fig. 49 — Cooling Charging Chart, 50TFQ012

11.Set enthalpy potentiometer to D.

12.Apply power (24 vac) to terminals TR and TR1.

DIFFERENTIAL ENTHALPY — To check differential enthalpy:

1.Make sure EconoMi$er IV preparation procedure has been performed.

2.Place 620-ohm resistor across SO and +.

3.Place 1.2 kilo-ohm resistor across SR and +. The Free Cool LED should be lit.

4.Remove 620-ohm resistor across SO and +. The Free Cool LED should turn off.

5.Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.

SINGLE ENTHALPY — To check single enthalpy:

1.Make sure EconoMi$er IV preparation procedure has been performed.

2.Set the enthalpy potentiometer to A (fully CCW). The Free Cool LED should be lit.

3.Set the enthalpy potentiometer to D (fully CW). The Free Cool LED should turn off.

4.Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.

DCV (DEMAND CONTROLLED VENTILATION) AND POWER EXHAUST — To check DCV and Power Exhaust:

1.Make sure EconoMi$er IV preparation procedure has been performed.

2.Ensure terminals AQ and AQ1 are open. The LED for both DCV and Exhaust should be off. The actuator should be fully closed.

3.Connect a 9-v battery to AQ (positive node) and AQ1 (negative node). The LED for both DCV and Exhaust should turn on. The actuator should drive to between 90 and 95% open.

4.Turn the Exhaust potentiometer CW until the Exhaust LED turns off. The LED should turn off when the potentiometer is approximately 90%. The actuator should remain in position.

49

Image 49
Contents Safety Considerations ContentsInstallation Roof Curb Details Unit Leveling Tolerances Rigging Details Unit Size 50TFQ Physical DataBase Unit Dimensions Make Electrical Connections Electrical Data Units Without Electrical Convenience Outlet Electric Heating CapacitiesSIZE† 81/2 Tons Electrical Data Units With Electrical Convenience OutletOFM IFM Heat SIZE† Unit Size Adjust Factory-Installed Options 208/230 460 575 Heat Anticipator SettingsStage Outdoor-Air Hood Details PremierLink Controller PremierLink Sensor UsagePremierLink Controller Installed For Differential EconoMi$er IV Component Locations Outdoor-Air Hood Construction EconoMi$er2 with 4 to 20 mA Control Wiring EconoMi$er IV Sensor Usage Supply Air Sensor Temperature Resistance ValuesEconoMi$er IV Controller Potentiometer LED Locations Enthalpy Changeover Set Points Page Uration CO2 Sensor Standard SettingsSize 008 Fan Motor Performance Typical Belt-Drive Motor Mounting for SizeElectric Heater Static Pressure* in. wg 50TFQ008-012 Fan Rpm at Motor Pulley SettingsRpm Bhp Watts 2250 511 538 External Static Pressure in. wg2300 519 567 2400 534 6302300 519 567 597 729 666 900 Rpm Bhp Watts 2250 511 538 591 697 660 8642400 534 630 611 798 678 974 2500 550 698 624 872Airflow 3800 Rpm Bhp Watts 2550 557 733 631 9103900 4000 4100 4200 4250 Rpm Bhp Watts 25503200 662 1324 726 1542 784 1765 838 1994 3100 646 1217 711 1428 770 1645 825 18693300 679 1438 741 1663 798 1892 851 2126 3400 695 1558 756 1790 812 20253100 569 656 636 805 Rpm Bhp Watts 3000 556 604 623 748 684 8913200 583 712 648 865 3300 597 770 661 9293700 654 1040 713 1218 767 1395 817 1571 3600 639 967 700 1140 754 1312 805 14843800 668 1116 726 1299 779 1481 828 1662 3900 683 1197 739 1385 792 1572 840 17583900 683 1197 739 1385 792 1572 3500 625 898 687 1066 742 1233 794 14004200 726 1462 780 1665 1132 3555 45002300 471 483 560 648 Rpm Bhp Watts 2250 465 459 555 6212400 483 534 570 705 2500 495 588 581 7672300 471 483 560 648 634 817 Rpm Bhp Watts 2250 465 459 555 621 629 7862400 483 534 570 705 644 880 2500 495 588 581 767 653 948Airflow 3800 662 1705 Rpm Bhp Watts 2550 501 617 586 799 658 9833900 675 1828 Airflow 3100 536 587 603 730 666 879 Rpm Bhp Watts 3000 523 541 592 680 657 8253200 549 637 614 783 676 936 3300 562 689 626 839Airflow General Notes for FAN Performance Data Tables START-UP PRE-START-UPOperating Sequence DX Cooling Temperature Control Example Cleaning Outdoor Coil ServiceLubrication Cooling Charging Chart, 50TFQ009 TroubleshootingPage Typical Unit Wiring Schematic 208/203-3-60 Unit Shown Heating and Cooling Troubleshooting Demand Control Enthalpy EconoMi$er IV Input/Output LogicTerminal† Mounting Compressor Unit IndexPage Preliminary Information START-UP ChecklistIII. START-UP