Carrier 50TFQ008-012 EconoMi$er IV Input/Output Logic, Demand Control Enthalpy, Terminal†

Page 53

Table 29 — EconoMi$er IV Input/Output Logic

 

INPUTS

 

 

 

 

 

OUTPUTS

 

Demand Control

Enthalpy*

 

 

 

Compressor

N Terminal†

 

 

Y1

Y2

Stage

Stage

Occupied

Unoccupied

Ventilation (DCV)

Outdoor

Return

 

 

1

2

Damper

 

 

 

 

 

Below set

High

Low

On

On

On

On

Minimum position

Closed

(DCV LED Off)

(Free Cooling LED Off)

 

On

Off

On

Off

 

 

 

 

 

 

 

 

 

 

Off

Off

Off

Off

 

 

 

Low

High

On

On

On

Off

Modulating** (between min.

Modulating** (between

 

(Free Cooling LED On)

 

On

Off

Off

Off

position and full-open)

closed and full-open)

 

 

 

 

 

 

 

 

Off

Off

Off

Off

Minimum position

Closed

Above set

High

Low

On

On

On

On

Modulating†† (between min.

Modulating†† (between

(DCV LED On)

(Free Cooling LED Off)

 

On

Off

On

Off

position and DCV maximum)

closed and DCV

 

 

 

 

maximum)

 

 

 

Off

Off

Off

Off

 

 

 

 

 

 

 

Low

High

On

On

On

Off

Modulating***

Modulating†††

 

(Free Cooling LED On)

 

On

Off

Off

Off

 

 

 

 

 

 

 

 

 

 

Off

Off

Off

Off

 

 

*For single enthalpy control, the module compares outdoor enthalpy to the ABCD set point.

†Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied).

**Modulation is based on the supply-air sensor signal. ††Modulation is based on the DCV signal.

***Modulation is based on the greater of DCV and supply-air sen- sor signals, between minimum position and either maximum position (DCV) or fully open (supply-air signal).

†††Modulation is based on the greater of DCV and supply-air sen- sor signals, between closed and either maximum position (DCV) or fully open (supply-air signal).

Fig. 51 — EconoMi$er IV Functional View

53

Image 53
Contents Installation ContentsSafety Considerations Roof Curb Details Unit Leveling Tolerances Rigging Details Unit Size 50TFQ Physical DataBase Unit Dimensions Make Electrical Connections Electrical Data Units Without Electrical Convenience Outlet Electric Heating CapacitiesSIZE† 81/2 Tons Electrical Data Units With Electrical Convenience OutletOFM IFM Heat SIZE† Unit Size Adjust Factory-Installed Options Stage Heat Anticipator Settings208/230 460 575 Outdoor-Air Hood Details PremierLink Controller PremierLink Sensor UsagePremierLink Controller Installed For Differential EconoMi$er IV Component Locations Outdoor-Air Hood Construction EconoMi$er2 with 4 to 20 mA Control Wiring EconoMi$er IV Sensor Usage Supply Air Sensor Temperature Resistance ValuesEconoMi$er IV Controller Potentiometer LED Locations Enthalpy Changeover Set Points Page Uration CO2 Sensor Standard SettingsSize 008 Fan Motor Performance Typical Belt-Drive Motor Mounting for SizeElectric Heater Static Pressure* in. wg 50TFQ008-012 Fan Rpm at Motor Pulley SettingsRpm Bhp Watts 2250 511 538 External Static Pressure in. wg2300 519 567 2400 534 6302300 519 567 597 729 666 900 Rpm Bhp Watts 2250 511 538 591 697 660 8642400 534 630 611 798 678 974 2500 550 698 624 872Airflow 3800 Rpm Bhp Watts 2550 557 733 631 9103900 4000 4100 4200 4250 Rpm Bhp Watts 25503200 662 1324 726 1542 784 1765 838 1994 3100 646 1217 711 1428 770 1645 825 18693300 679 1438 741 1663 798 1892 851 2126 3400 695 1558 756 1790 812 20253100 569 656 636 805 Rpm Bhp Watts 3000 556 604 623 748 684 8913200 583 712 648 865 3300 597 770 661 9293700 654 1040 713 1218 767 1395 817 1571 3600 639 967 700 1140 754 1312 805 14843800 668 1116 726 1299 779 1481 828 1662 3900 683 1197 739 1385 792 1572 840 17583900 683 1197 739 1385 792 1572 3500 625 898 687 1066 742 1233 794 14004200 726 1462 780 1665 1132 3555 45002300 471 483 560 648 Rpm Bhp Watts 2250 465 459 555 6212400 483 534 570 705 2500 495 588 581 7672300 471 483 560 648 634 817 Rpm Bhp Watts 2250 465 459 555 621 629 7862400 483 534 570 705 644 880 2500 495 588 581 767 653 948Airflow 3900 675 1828 Rpm Bhp Watts 2550 501 617 586 799 658 9833800 662 1705 Airflow 3100 536 587 603 730 666 879 Rpm Bhp Watts 3000 523 541 592 680 657 8253200 549 637 614 783 676 936 3300 562 689 626 839Airflow General Notes for FAN Performance Data Tables START-UP PRE-START-UPOperating Sequence DX Cooling Temperature Control Example Cleaning Outdoor Coil ServiceLubrication Cooling Charging Chart, 50TFQ009 TroubleshootingPage Typical Unit Wiring Schematic 208/203-3-60 Unit Shown Heating and Cooling Troubleshooting Terminal† EconoMi$er IV Input/Output LogicDemand Control Enthalpy Mounting Compressor Unit IndexPage III. START-UP START-UP ChecklistPreliminary Information