Carrier 50TFQ008-012 specifications Service, Cleaning Outdoor Coil

Page 47

HEATING, UNIT WITH ECONOMI$ER2, PREMIERLINK™ CONTROL AND A ROOM SENSOR — Every 40 seconds the controller will calculate the required heat stages (maximum of 3) to maintain supply air temperature (SAT) if the following qualifying conditions are met:

Indoor fan has been on for at least 30 seconds.

COOL mode is not active.

OCCUPIED, TEMP.COMPENSATED START or HEAT mode is active.

SAT reading is available.

Fire shutdown mode is not active.

If all of the above conditions are met, the number of heat stages is calculated; otherwise the required number of heat stages will be set to 0.

If the PremierLink controller determines that heat stages are required, the economizer damper will be moved to minimum position if occupied and closed if unoccupied.

SERVICE

When servicing the unit, shut off all electrical power to the unit to avoid shock hazard or injury from rotating parts.

Cleaning — Inspect the unit interior at the beginning of each heating and cooling season or as operating conditions require.

INDOOR COIL

1.Turn off the unit power and tag disconnect. Remove the filter access panel and indoor coil access panel.

2.If an economizer or accessory two-position damper is installed, remove the economizer or two-position damper by disconnecting the economizer plug and removing the mounting screws.

3.Slide the filters out of the unit.

4.Clean the coil using a commercial coil cleaner or dish- washer detergent in a pressurized spray canister. Wash both sides of the coil and flush with clean water. For best results, backflush toward the return-air section to remove foreign material.

5.Flush the condensate pan after completion.

6.Reinstall the economizer/two-position damper and filters.

7.Reconnect the wiring.

8.Replace the access panels.

OUTDOOR COILS — Inspect the coils monthly. Clean condenser coils annually, and as required by location and outdoor-air conditions.

Clean 2-row coils as follows:

1.Turn off the unit power and tag disconnect.

2.Remove the top panel screws on the outdoor end of the unit.

3.Remove the outdoor coil corner post. See Fig. 43. To hold the top panel open, place the coil corner post between the top panel and the center post. See Fig. 44.

4.Remove the device holding the coil sections together at the return end of the outdoor coil. Carefully separate the outer coil section 3 to 4 in. from the inner coil section. See Fig. 45.

5.Use a water hose or other suitable equipment to flush down between the 2 coil sections to remove dirt and debris. Clean the outer surfaces with a stiff brush in the normal manner.

6.Secure the sections together. Reposition the coil sections, and remove the coil corner post from between the top panel and center post. Install the coil corner post and coil center post, and replace all screws.

CONDENSATE DRAIN — Check and clean each year at the start of cooling season. In winter, keep the drain dry or protect it against freeze-up.

Fig. 43 — Cleaning Outdoor Coil

Fig. 44 — Propping Up Top Panel

Fig. 45 — Separating Coil Sections

47

Image 47
Contents Installation ContentsSafety Considerations Roof Curb Details Unit Leveling Tolerances Rigging Details Unit Size 50TFQ Physical DataBase Unit Dimensions Make Electrical Connections Electrical Data Units Without Electrical Convenience Outlet Electric Heating CapacitiesSIZE† 81/2 Tons Electrical Data Units With Electrical Convenience OutletOFM IFM Heat SIZE† Unit Size Adjust Factory-Installed Options Stage Heat Anticipator Settings208/230 460 575 Outdoor-Air Hood Details PremierLink Controller PremierLink Sensor UsagePremierLink Controller Installed For Differential EconoMi$er IV Component Locations Outdoor-Air Hood Construction EconoMi$er2 with 4 to 20 mA Control Wiring EconoMi$er IV Sensor Usage Supply Air Sensor Temperature Resistance ValuesEconoMi$er IV Controller Potentiometer LED Locations Enthalpy Changeover Set Points Page Uration CO2 Sensor Standard SettingsSize 008 Fan Motor Performance Typical Belt-Drive Motor Mounting for SizeElectric Heater Static Pressure* in. wg 50TFQ008-012 Fan Rpm at Motor Pulley Settings2400 534 630 External Static Pressure in. wgRpm Bhp Watts 2250 511 538 2300 519 5672500 550 698 624 872 Rpm Bhp Watts 2250 511 538 591 697 660 8642300 519 567 597 729 666 900 2400 534 630 611 798 678 974Airflow Rpm Bhp Watts 2550 Rpm Bhp Watts 2550 557 733 631 9103800 3900 4000 4100 4200 42503400 695 1558 756 1790 812 2025 3100 646 1217 711 1428 770 1645 825 18693200 662 1324 726 1542 784 1765 838 1994 3300 679 1438 741 1663 798 1892 851 21263300 597 770 661 929 Rpm Bhp Watts 3000 556 604 623 748 684 8913100 569 656 636 805 3200 583 712 648 8653900 683 1197 739 1385 792 1572 840 1758 3600 639 967 700 1140 754 1312 805 14843700 654 1040 713 1218 767 1395 817 1571 3800 668 1116 726 1299 779 1481 828 16621132 3555 4500 3500 625 898 687 1066 742 1233 794 14003900 683 1197 739 1385 792 1572 4200 726 1462 780 16652500 495 588 581 767 Rpm Bhp Watts 2250 465 459 555 6212300 471 483 560 648 2400 483 534 570 7052500 495 588 581 767 653 948 Rpm Bhp Watts 2250 465 459 555 621 629 7862300 471 483 560 648 634 817 2400 483 534 570 705 644 880Airflow 3900 675 1828 Rpm Bhp Watts 2550 501 617 586 799 658 9833800 662 1705 Airflow 3300 562 689 626 839 Rpm Bhp Watts 3000 523 541 592 680 657 8253100 536 587 603 730 666 879 3200 549 637 614 783 676 936Airflow General Notes for FAN Performance Data Tables START-UP PRE-START-UPOperating Sequence DX Cooling Temperature Control Example Cleaning Outdoor Coil ServiceLubrication Cooling Charging Chart, 50TFQ009 TroubleshootingPage Typical Unit Wiring Schematic 208/203-3-60 Unit Shown Heating and Cooling Troubleshooting Terminal† EconoMi$er IV Input/Output LogicDemand Control Enthalpy Mounting Compressor Unit IndexPage III. START-UP START-UP ChecklistPreliminary Information