Carrier 50TFQ008-012 specifications EconoMi$er IV Controller Potentiometer LED Locations

Page 22

Fig. 32 — EconoMi$er IV Controller Potentiometer

and LED Locations

19

 

18

LED ON

 

 

 

 

D

 

 

 

 

17

 

 

 

 

 

 

 

 

 

16

LED OFF

LED ON

 

 

 

C

 

 

 

15

 

 

 

 

 

 

 

 

mA

14

 

LED OFF

LED ON

 

 

 

B

 

 

13

 

 

 

 

 

 

 

 

 

12

 

 

LED OFF

LED ON

 

 

 

 

A

 

11

 

 

 

Differential Enthalpy Control — For differential enthalpy control, the EconoMi$er IV controller uses two enthalpy sen- sors (HH57AC078 and CRENTDIF004A00), one in the out- side air and one in the return air duct. The EconoMi$er IV controller compares the outdoor air enthalpy to the return air enthalpy to determine EconoMi$er IV use. The controller selects the lower enthalpy air (return or outdoor) for cooling. For example, when the outdoor air has a lower enthalpy than the return air, the EconoMi$er IV opens to bring in outdoor air for free cooling.

Replace the standard outside air dry bulb temperature sen- sor with the accessory enthalpy sensor in the same mounting location. See Fig. 19. Mount the return air enthalpy sensor in the return air duct. See Fig. 34. Wiring is provided in the EconoMi$er IV wiring harness. See Fig. 26. The outdoor en- thalpy changeover set point is set with the outdoor enthalpy set point potentiometer on the EconoMi$er IV controller. When using this mode of changeover control, turn the enthalpy set- point potentiometer fully clockwise to the D setting.

Indoor Air Quality (IAQ) Sensor Input — The IAQ input can be used for demand control ventilation control based on the level of CO2 measured in the space or return air duct.

Mount the accessory IAQ sensor according to manufacturer specifications. The IAQ sensor should be wired to the AQ and AQ1 terminals of the controller. Adjust the DCV potentiome- ters to correspond to the DCV voltage output of the indoor air quality sensor at the user-determined set point. See Fig. 37.

If a separate field-supplied transformer is used to power the IAQ sensor, the sensor must not be grounded or the EconoMi$er IV control board will be damaged.

10

 

 

 

 

 

 

 

 

 

LED OFF

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

 

100

40

45

50

55

60

65

70

75

80

85

90

95

 

 

 

 

DEGREES FAHRENHEIT

 

 

 

 

Fig. 33 — Outside Air Temperature

Changeover Set Points

Differential Dry Bulb Control — For differential dry bulb control the standard outdoor dry bulb sensor is used in conjunc- tion with an additional accessory dry bulb sensor (part number CRTEMPSN002A00). The accessory sensor must be mounted in the return airstream. See Fig. 34. Wiring is provided in the EconoMi$er IV wiring harness. See Fig. 26.

In this mode of operation, the outdoor-air temperature is compared to the return-air temperature and the lower tempera- ture airstream is used for cooling. When using this mode of

ECONOMI$ER IV

ECONOMI$ER IV

CONTROLLER

GROMMET

RETURN AIR

SENSOR

RETURN DUCT (FIELD-PROVIDED)

changeover control, turn the enthalpy set point potentiometer fully clockwise to the D setting. See Fig. 32.

Outdoor Enthalpy Changeover — For enthalpy control, ac- cessory enthalpy sensor (part number HH57AC078) is re- quired. Replace the standard outdoor dry bulb temperature sen- sor with the accessory enthalpy sensor in the same mounting location. See Fig. 19. When the outdoor air enthalpy rises above the outdoor enthalpy changeover set point, the outdoor- air damper moves to its minimum position. The outdoor enthalpy changeover set point is set with the outdoor enthalpy set point potentiometer on the EconoMi$er IV controller. The set points are A, B, C, and D. See Fig. 35. The factory-installed 620-ohm jumper must be in place across terminals SR and SR+ on the EconoMi$er IV controller. See Fig. 19 and 36.

Fig. 34 — Return Air Temperature or Enthalpy

Sensor Mounting Location

22

Image 22
Contents Safety Considerations ContentsInstallation Roof Curb Details Unit Leveling Tolerances Rigging Details Physical Data Unit Size 50TFQBase Unit Dimensions Make Electrical Connections Electric Heating Capacities Electrical Data Units Without Electrical Convenience OutletSIZE† Electrical Data Units With Electrical Convenience Outlet 81/2 TonsOFM IFM Heat SIZE† Unit Size Adjust Factory-Installed Options 208/230 460 575 Heat Anticipator SettingsStage Outdoor-Air Hood Details PremierLink Sensor Usage PremierLink ControllerPremierLink Controller Installed For Differential EconoMi$er IV Component Locations Outdoor-Air Hood Construction EconoMi$er2 with 4 to 20 mA Control Wiring Supply Air Sensor Temperature Resistance Values EconoMi$er IV Sensor UsageEconoMi$er IV Controller Potentiometer LED Locations Enthalpy Changeover Set Points Page CO2 Sensor Standard Settings UrationTypical Belt-Drive Motor Mounting for Size Size 008 Fan Motor PerformanceFan Rpm at Motor Pulley Settings Electric Heater Static Pressure* in. wg 50TFQ008-0122300 519 567 External Static Pressure in. wgRpm Bhp Watts 2250 511 538 2400 534 6302400 534 630 611 798 678 974 Rpm Bhp Watts 2250 511 538 591 697 660 8642300 519 567 597 729 666 900 2500 550 698 624 872Airflow 3900 4000 4100 4200 4250 Rpm Bhp Watts 2550 557 733 631 9103800 Rpm Bhp Watts 25503300 679 1438 741 1663 798 1892 851 2126 3100 646 1217 711 1428 770 1645 825 18693200 662 1324 726 1542 784 1765 838 1994 3400 695 1558 756 1790 812 20253200 583 712 648 865 Rpm Bhp Watts 3000 556 604 623 748 684 8913100 569 656 636 805 3300 597 770 661 9293800 668 1116 726 1299 779 1481 828 1662 3600 639 967 700 1140 754 1312 805 14843700 654 1040 713 1218 767 1395 817 1571 3900 683 1197 739 1385 792 1572 840 17584200 726 1462 780 1665 3500 625 898 687 1066 742 1233 794 14003900 683 1197 739 1385 792 1572 1132 3555 45002400 483 534 570 705 Rpm Bhp Watts 2250 465 459 555 6212300 471 483 560 648 2500 495 588 581 7672400 483 534 570 705 644 880 Rpm Bhp Watts 2250 465 459 555 621 629 7862300 471 483 560 648 634 817 2500 495 588 581 767 653 948Airflow 3800 662 1705 Rpm Bhp Watts 2550 501 617 586 799 658 9833900 675 1828 Airflow 3200 549 637 614 783 676 936 Rpm Bhp Watts 3000 523 541 592 680 657 8253100 536 587 603 730 666 879 3300 562 689 626 839Airflow General Notes for FAN Performance Data Tables PRE-START-UP START-UPOperating Sequence DX Cooling Temperature Control Example Service Cleaning Outdoor CoilLubrication Troubleshooting Cooling Charging Chart, 50TFQ009Page Typical Unit Wiring Schematic 208/203-3-60 Unit Shown Heating and Cooling Troubleshooting Demand Control Enthalpy EconoMi$er IV Input/Output LogicTerminal† Index Mounting Compressor UnitPage Preliminary Information START-UP ChecklistIII. START-UP