Carrier 50TFQ008-012 specifications Physical Data, Unit Size 50TFQ

Page 5

Table 1 — Physical Data

UNIT SIZE 50TFQ

 

008

 

 

009

 

 

012

NOMINAL CAPACITY (tons)

 

71/2

 

 

81/2

 

 

10

OPERATING WEIGHT (lb)

 

 

 

 

 

 

 

 

 

Unit

 

940

 

 

965

 

 

1015

Economizer

 

 

 

 

 

 

 

 

 

EconoMi$er IV

 

75

 

 

75

 

 

75

Roof Curb*

 

143

 

 

143

 

 

143

COMPRESSOR (Hermetic)

 

 

Reciprocating

 

 

Scroll

Quantity

 

2

 

 

2

 

 

2

 

 

Oil (oz)

 

45 ea

 

 

54 ea

 

 

54 ea

REFRIGERANT TYPE

 

 

 

 

R-22

 

 

 

Operating Charge (lb-oz)

 

 

 

 

 

 

 

 

 

Circuit 1

 

5-14

 

 

8- 6

 

 

7-14

 

 

 

Circuit 2

 

5-13

 

 

8-13

 

 

8- 3

OUTDOOR COIL

 

Enhanced Copper Tubes, Aluminum Lanced Fins, Acutrol™ Feed Device

Rows...Fins/in.

 

1...17

 

 

2...17

 

 

2...17

 

 

 

Total Face Area (sq ft)

 

20.50

 

 

18.00

 

 

18.30

OUTDOOR FAN

 

 

 

 

Propeller Type

 

 

 

Nominal Cfm

 

6500

 

 

6500

 

 

6500

 

 

 

Quantity...Diameter (in.)

 

2...22

 

 

2...22

 

 

2...22

Motor Hp...Rpm

 

1/4...1100

 

 

1/4...1100

 

 

1/4...1100

Watts Input (Total)

 

500

 

 

500

 

 

500

INDOOR COIL

 

Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Acutrol Feed Device

Rows...Fins/in.

 

3...15

 

 

3...15

 

 

3...15

 

 

 

Total Face Area (sq ft)

 

8.0

 

 

8.0

 

 

11.1

INDOOR FAN

 

 

 

 

Centrifugal Type

 

 

 

Quantity...Size (in.)

Std

1...15 x 15

 

 

1...15 x 15

 

 

1...15 x 15

 

 

 

 

Alt

1...15 x 15

 

 

 

 

1...15 x 15

 

High-Static

1...15 x 15

 

 

1...15 x 15

 

 

1...15 x 15

Type Drive

Std

Belt

 

 

Belt

 

 

Belt

 

Alt

Belt

 

 

 

 

Belt

Nominal Cfm

High-Static

Belt

 

 

Belt

 

 

Belt

 

3000

 

 

3600

 

 

4000

Maximum Continuous Bhp

Std

2.40

 

 

2.40

 

 

2.40

 

Alt

2.40

 

 

 

2.90

 

High-Static

3.70

 

 

3.70

 

 

5.25

Motor Frame Size

Std

56

 

 

56

 

 

56

 

Alt

56

 

 

 

56

 

High-Static

56

 

 

56

 

 

56

Nominal Rpm

Std

 

 

 

 

 

Alt

 

 

 

 

 

High-Static

1725

 

 

1725

 

 

1725

Fan Rpm Range

Std

590- 840

 

 

685- 935

 

 

685- 935

 

Alt

685- 935

 

 

 

835-1085

Motor Bearing Type

High-Static

860-1080

 

 

860-1080

 

 

830-1130

 

Ball

 

 

Ball

 

 

Ball

Maximum Allowable Rpm

 

2100

 

 

2100

 

 

2100

Motor Pulley Pitch Diameter Min/Max (in.)

Std

2.4/3.4

 

 

2.8/3.8

 

 

2.8/3.8

 

Alt

2.8/3.8

 

 

 

3.4/4.4

 

High-Static

4.0/5.0

 

 

4.0/5.0

 

 

2.8/3.8

Nominal Motor Shaft Diameter (in.)

Std

5/8

 

 

5/8

 

 

5/8

 

Alt

5/8

 

 

 

7/8

Fan Pulley Pitch Diameter (in.)

High-Static

7/8

 

 

7/8

 

 

7/8

Std

7.0

 

 

7.0

 

 

7.0

 

Alt

7.0

 

 

 

7.0

 

High-Static

8.0

 

 

8.0

 

 

5.8

Belt, Quantity...Type...Length (in.)

Std

1...A...53

 

 

1...A...48

 

 

1...A...49

 

Alt

1...A...49

 

 

 

 

1...A...51

 

High-Static

1...A...65

 

 

1...A...53

 

 

1...BX...48

Pulley Center Line Distance (in.)

Std

16.75-19.25

 

 

16.75-19.25

 

 

15.85-17.50

 

Alt

16.75-19.25

 

 

 

15.85-17.50

 

High-Static

16.75-19.25

 

 

16.75-19.25

 

 

15.85-17.50

Speed Change per Full Turn of

Std

50

 

 

50

 

 

50

Moveable Pulley Flange (rpm)

Alt

50

 

 

 

50

 

High-Static

60

 

 

60

 

 

60

Moveable Pulley Maximum Full Turns

Std

5

 

 

5

 

 

5

From Closed Position

Alt

5

 

 

 

5

 

High-Static

5

 

 

5

 

 

6

Factory Setting

Std

5

 

 

5

 

 

5

 

Alt

5

 

 

 

5

 

High-Static

5

 

 

5

 

 

5

Factory Speed Setting (rpm)

Std

590

 

 

685

 

 

685

 

Alt

685

 

 

 

835

Fan Shaft Diameter at Pulley (in.)

High-Static

860

 

 

880

 

 

887

 

1

 

 

1

 

 

1

HIGH-PRESSURE SWITCH (psig)

 

 

 

 

 

 

 

 

 

Standard Compressor Internal Relief (Differential)

 

 

450 ± 50

 

 

 

 

Cutout

 

 

428

 

 

 

 

Reset (Auto.)

 

 

320

 

 

 

 

LOSS-OF-CHARGE (LOW-PRESSURE) SWITCH (psig)

 

 

 

 

 

 

 

 

 

Cutout

 

 

7 ± 3

 

 

 

 

Reset (Auto.)

 

 

22 ± 5

 

 

 

 

FREEZE PROTECTION THERMOSTAT (F)

 

 

 

 

 

 

 

 

 

Opens

 

 

30 ± 5

 

 

 

 

Closes

 

 

45 ± 5

 

 

 

 

OUTDOOR-AIR INLET SCREENS

 

 

 

 

Cleanable.

 

 

 

 

 

Screen quantity and size vary based on options selected.

RETURN-AIR FILTERS

 

 

 

 

Throwaway

 

 

 

Quantity...Size (in.)

 

4...16 x 20 x 2

 

 

4...16 x 20 x 2

 

 

 

4...20 x 20 x 2

 

 

 

 

 

 

LEGEND

 

*Weight of 14-in. roof curb.

 

 

 

Bhp — Brake Horsepower

 

 

 

 

 

 

 

 

 

5

Image 5
Contents Installation ContentsSafety Considerations Roof Curb Details Unit Leveling Tolerances Rigging Details Unit Size 50TFQ Physical DataBase Unit Dimensions Make Electrical Connections Electrical Data Units Without Electrical Convenience Outlet Electric Heating CapacitiesSIZE† 81/2 Tons Electrical Data Units With Electrical Convenience OutletOFM IFM Heat SIZE† Unit Size Adjust Factory-Installed Options Stage Heat Anticipator Settings208/230 460 575 Outdoor-Air Hood Details PremierLink Controller PremierLink Sensor UsagePremierLink Controller Installed For Differential EconoMi$er IV Component Locations Outdoor-Air Hood Construction EconoMi$er2 with 4 to 20 mA Control Wiring EconoMi$er IV Sensor Usage Supply Air Sensor Temperature Resistance ValuesEconoMi$er IV Controller Potentiometer LED Locations Enthalpy Changeover Set Points Page Uration CO2 Sensor Standard SettingsSize 008 Fan Motor Performance Typical Belt-Drive Motor Mounting for SizeElectric Heater Static Pressure* in. wg 50TFQ008-012 Fan Rpm at Motor Pulley SettingsRpm Bhp Watts 2250 511 538 External Static Pressure in. wg2300 519 567 2400 534 6302300 519 567 597 729 666 900 Rpm Bhp Watts 2250 511 538 591 697 660 8642400 534 630 611 798 678 974 2500 550 698 624 872Airflow 3800 Rpm Bhp Watts 2550 557 733 631 9103900 4000 4100 4200 4250 Rpm Bhp Watts 25503200 662 1324 726 1542 784 1765 838 1994 3100 646 1217 711 1428 770 1645 825 18693300 679 1438 741 1663 798 1892 851 2126 3400 695 1558 756 1790 812 20253100 569 656 636 805 Rpm Bhp Watts 3000 556 604 623 748 684 8913200 583 712 648 865 3300 597 770 661 9293700 654 1040 713 1218 767 1395 817 1571 3600 639 967 700 1140 754 1312 805 14843800 668 1116 726 1299 779 1481 828 1662 3900 683 1197 739 1385 792 1572 840 17583900 683 1197 739 1385 792 1572 3500 625 898 687 1066 742 1233 794 14004200 726 1462 780 1665 1132 3555 45002300 471 483 560 648 Rpm Bhp Watts 2250 465 459 555 6212400 483 534 570 705 2500 495 588 581 7672300 471 483 560 648 634 817 Rpm Bhp Watts 2250 465 459 555 621 629 7862400 483 534 570 705 644 880 2500 495 588 581 767 653 948Airflow 3900 675 1828 Rpm Bhp Watts 2550 501 617 586 799 658 9833800 662 1705 Airflow 3100 536 587 603 730 666 879 Rpm Bhp Watts 3000 523 541 592 680 657 8253200 549 637 614 783 676 936 3300 562 689 626 839Airflow General Notes for FAN Performance Data Tables START-UP PRE-START-UPOperating Sequence DX Cooling Temperature Control Example Cleaning Outdoor Coil ServiceLubrication Cooling Charging Chart, 50TFQ009 TroubleshootingPage Typical Unit Wiring Schematic 208/203-3-60 Unit Shown Heating and Cooling Troubleshooting Terminal† EconoMi$er IV Input/Output LogicDemand Control Enthalpy Mounting Compressor Unit IndexPage III. START-UP START-UP ChecklistPreliminary Information