Carrier 50TFQ008-012 specifications Make Electrical Connections

Page 7

Step 5 — Make Electrical Connections

Unit cabinet must have an uninterrupted, unbroken electri- cal ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control com- partment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code) ANSI (American National Standards Institute)/ NFPA (National Fire Protection Association) 70 latest year and local electrical codes. Failure to follow this warning could result in the installer being liable for personal injury of others.

FIELD POWER SUPPLY — All units except 208/230-v units are factory-wired for the voltage shown on the unit name- plate. If the 208/230-v unit is to be connected to a 208-v power supply, the transformer must be rewired by disconnecting the black wire from the 230-v 1/4-in. male spade terminal on the transformer and connecting it to the 208-v 1/4-in. male spade terminal from the transformer.

Refer to the unit label diagram for additional information. Pigtails are provided for field wire connections. Use factory- supplied splices or a UL (Underwriters’ Laboratories) approved copper/aluminum connector.

When installing units, provide a disconnect per the NEC.

All field wiring must comply with the NEC and local re- quirements. In Canada, electrical connections must be made in accordance with CSA (Canadian Standards Association) C22.1 Canadian Electrical Code Part One.

Install field wiring as follows:

1.Install conduit through the side panel openings. For units without electric heat, install conduit between the discon- nect and control box.

2.Install power lines to terminal connections as shown in Fig. 7.

3.For units with electric heat, refer to Table 2 and Accessory Installation Instructions.

During operation, voltage to compressor terminals must be within range indicated on unit nameplate (see Tables 3A and 3B). On 3-phase units, voltages between phases must be bal- anced within 2%, and the current within 10%. Use the formula shown in Tables 3A and 3B, Note 2 on page 11 to determine the percentage of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such opera- tion would invalidate any applicable Carrier warranty.

208/230-3-60575-3-60 460-3-60

LEGEND

CContactor COMP — Compressor

IFC

Indoor-Fan Contactor

NEC

National Electrical Code

TB

Terminal Block

 

 

Field Wiring

 

 

Factory Wiring

 

 

Splice Connection

 

 

(Factory-Supplied)

Fig. 7 — Power Wiring Connections

7

Image 7
Contents Safety Considerations ContentsInstallation Roof Curb Details Unit Leveling Tolerances Rigging Details Unit Size 50TFQ Physical DataBase Unit Dimensions Make Electrical Connections Electrical Data Units Without Electrical Convenience Outlet Electric Heating CapacitiesSIZE† 81/2 Tons Electrical Data Units With Electrical Convenience OutletOFM IFM Heat SIZE† Unit Size Adjust Factory-Installed Options 208/230 460 575 Heat Anticipator SettingsStage Outdoor-Air Hood Details PremierLink Controller PremierLink Sensor UsagePremierLink Controller Installed For Differential EconoMi$er IV Component Locations Outdoor-Air Hood Construction EconoMi$er2 with 4 to 20 mA Control Wiring EconoMi$er IV Sensor Usage Supply Air Sensor Temperature Resistance ValuesEconoMi$er IV Controller Potentiometer LED Locations Enthalpy Changeover Set Points Page Uration CO2 Sensor Standard SettingsSize 008 Fan Motor Performance Typical Belt-Drive Motor Mounting for SizeElectric Heater Static Pressure* in. wg 50TFQ008-012 Fan Rpm at Motor Pulley Settings2400 534 630 External Static Pressure in. wgRpm Bhp Watts 2250 511 538 2300 519 5672500 550 698 624 872 Rpm Bhp Watts 2250 511 538 591 697 660 8642300 519 567 597 729 666 900 2400 534 630 611 798 678 974Airflow Rpm Bhp Watts 2550 Rpm Bhp Watts 2550 557 733 631 9103800 3900 4000 4100 4200 42503400 695 1558 756 1790 812 2025 3100 646 1217 711 1428 770 1645 825 18693200 662 1324 726 1542 784 1765 838 1994 3300 679 1438 741 1663 798 1892 851 21263300 597 770 661 929 Rpm Bhp Watts 3000 556 604 623 748 684 8913100 569 656 636 805 3200 583 712 648 8653900 683 1197 739 1385 792 1572 840 1758 3600 639 967 700 1140 754 1312 805 14843700 654 1040 713 1218 767 1395 817 1571 3800 668 1116 726 1299 779 1481 828 16621132 3555 4500 3500 625 898 687 1066 742 1233 794 14003900 683 1197 739 1385 792 1572 4200 726 1462 780 16652500 495 588 581 767 Rpm Bhp Watts 2250 465 459 555 6212300 471 483 560 648 2400 483 534 570 7052500 495 588 581 767 653 948 Rpm Bhp Watts 2250 465 459 555 621 629 7862300 471 483 560 648 634 817 2400 483 534 570 705 644 880Airflow 3800 662 1705 Rpm Bhp Watts 2550 501 617 586 799 658 9833900 675 1828 Airflow 3300 562 689 626 839 Rpm Bhp Watts 3000 523 541 592 680 657 8253100 536 587 603 730 666 879 3200 549 637 614 783 676 936Airflow General Notes for FAN Performance Data Tables START-UP PRE-START-UPOperating Sequence DX Cooling Temperature Control Example Cleaning Outdoor Coil ServiceLubrication Cooling Charging Chart, 50TFQ009 TroubleshootingPage Typical Unit Wiring Schematic 208/203-3-60 Unit Shown Heating and Cooling Troubleshooting Demand Control Enthalpy EconoMi$er IV Input/Output LogicTerminal† Mounting Compressor Unit IndexPage Preliminary Information START-UP ChecklistIII. START-UP