Exhaust Set Point Adjustment — The exhaust set point will determine when the exhaust fan runs based on damper position (if accessory power exhaust is installed). The set point is modi- fied with the Exhaust Fan Set Point (EXH SET) potentiometer. See Fig. 32. The set point represents the damper position above which the exhaust fans will be turned on. When there is a call for exhaust, the EconoMi$er IV controller provides a 45 ± 15 second delay before exhaust fan activation to allow the damp- ers to open. This delay allows the damper to reach the appro- priate position to avoid unnecessary fan overload.

Minimum Position Control — There is a minimum damper position potentiometer on the EconoMi$er IV controller. See Fig. 32. The minimum damper position maintains the mini- mum airflow into the building during the occupied period.

When using demand ventilation, the minimum damper po- sition represents the minimum ventilation position for VOC (volatile organic compound) ventilation requirements. The maximum demand ventilation position is used for fully occu- pied ventilation.

When demand ventilation control is not being used, the minimum position potentiometer should be used to set the oc- cupied ventilation position. The maximum demand ventilation position should be turned fully clockwise.

Adjust the minimum position potentiometer to allow the minimum amount of outdoor air, as required by local codes, to enter the building. Make minimum position adjustments with at least 10 F temperature difference between the outdoor and return-air temperatures.

To determine the minimum position setting, perform the following procedure:

1.Calculate the appropriate mixed air temperature using the following formula:

100OA ) + (TR x 100RA TO = Outdoor-Air Temperature OA = Percent of Outdoor Air TR = Return-Air Temperature RA = Percent of Return Air TM = Mixed-Air Temperature

As an example, if local codes require 10% outdoor air during occupied conditions, outdoor-air temperature is 60 F, and return-air temperature is 75 F.

(60 x .10) + (75 x .90) = 73.5 F

2.Disconnect the supply air sensor from terminals T and T1.

3.Ensure that the factory-installed jumper is in place across terminals P and P1. If remote damper positioning is being used, make sure that the terminals are wired according to Fig. 26 and that the minimum position potentiometer is turned fully clockwise.

4.Connect 24 vac across terminals TR and TR1.

5.Carefully adjust the minimum position potentiometer until the measured mixed-air temperature matches the calculated value.

6.Reconnect the supply air sensor to terminals T and T1.

Remote control of the EconoMi$er IV damper is desirable when requiring additional temporary ventilation. If a field-supplied remote potentiometer (Honeywell part number S963B1128) is wired to the EconoMi$er IV controller, the minimum position of the damper can be controlled from a re- mote location.

To control the minimum damper position remotely, remove the factory-installed jumper on the P and P1 terminals on the EconoMi$er IV controller. Wire the field-supplied potentiome- ter to the P and P1 terminals on the EconoMi$er IV controller. See Fig. 36.

Damper Movement — Damper movement from full open to full closed (or vice versa) takes 21/2 minutes.

Thermostats — The EconoMi$er IV control works with con- ventional thermostats that have a Y1 (cool stage 1), Y2 (cool stage 2), W1 (heat stage 1), W2 (heat stage 2), and G (fan). The EconoMi$er IV control does not support space temperature sensors. Connections are made at the thermostat terminal con- nection board located in the main control box.

Occupancy Control — The factory default configuration for the EconoMi$er IV control is occupied mode. Occupied status is provided by the black jumper from terminal TR to terminal N. When unoccupied mode is desired, install a field-supplied timeclock function in place of the jumper between TR and N. See Fig. 26. When the timeclock contacts are closed, the EconoMi$er IV control will be in occupied mode. When the timeclock contacts are open (removing the 24-v signal from terminal N), the EconoMi$er IV will be in unoccupied mode.

Demand Controlled Ventilation (DCV) — When using the EconoMi$er IV for demand controlled ventilation, there are some equipment selection criteria which should be considered. When selecting the heat capacity and cool capacity of the equipment, the maximum ventilation rate must be evaluated for design conditions. The maximum damper position must be cal- culated to provide the desired fresh air.

Typically the maximum ventilation rate will be about 5 to 10% more than the typical cfm required per person, using normal outside air design criteria.

A proportional anticipatory strategy should be taken with the following conditions: a zone with a large area, varied occu- pancy, and equipment that cannot exceed the required ventila- tion rate at design conditions. Exceeding the required ventila- tion rate means the equipment can condition air at a maximum ventilation rate that is greater than the required ventilation rate for maximum occupancy. A proportional-anticipatory strategy will cause the fresh air supplied to increase as the room CO2 level increases even though the CO2 set point has not been reached. By the time the CO2 level reaches the set point, the damper will be at maximum ventilation and should maintain the set point.

In order to have the CO2 sensor control the economizer damper in this manner, first determine the damper voltage out- put for minimum or base ventilation. Base ventilation is the ventilation required to remove contaminants during unoccu- pied periods. The following equation may be used to determine the percent of outside-air entering the building for a given damper position. For best results there should be at least a 10 degree difference in outside and return-air temperatures.

100OA ) + (TR x 100RA TO = Outdoor-Air Temperature OA = Percent of Outdoor Air TR = Return-Air Temperature RA = Percent of Return Air TM = Mixed-Air Temperature

Once base ventilation has been determined, set the mini- mum damper position potentiometer to the correct position.

The same equation can be used to determine the occupied or maximum ventilation rate to the building. For example, an out- put of 3.6 volts to the actuator provides a base ventilation rate of 5% and an output of 6.7 volts provides the maximum venti- lation rate of 20% (or base plus 15 cfm per person). Use Fig. 37 to determine the maximum setting of the CO2 sensor. For ex- ample, a 1100 ppm set point relates to a 15 cfm per person de- sign. Use the 1100 ppm curve on Fig. 37 to find the point when the CO2 sensor output will be 6.7 volts. Line up the point on the graph with the left side of the chart to determine that the range configuration for the CO2 sensor should be 1800 ppm. The EconoMi$er IV controller will output the 6.7 volts from the

24

Image 24
Contents Contents Safety ConsiderationsInstallation Roof Curb Details Unit Leveling Tolerances Rigging Details Physical Data Unit Size 50TFQBase Unit Dimensions Make Electrical Connections Electric Heating Capacities Electrical Data Units Without Electrical Convenience OutletSIZE† Electrical Data Units With Electrical Convenience Outlet 81/2 TonsOFM IFM Heat SIZE† Unit Size Adjust Factory-Installed Options Heat Anticipator Settings 208/230 460 575Stage Outdoor-Air Hood Details PremierLink Sensor Usage PremierLink ControllerPremierLink Controller Installed For Differential EconoMi$er IV Component Locations Outdoor-Air Hood Construction EconoMi$er2 with 4 to 20 mA Control Wiring Supply Air Sensor Temperature Resistance Values EconoMi$er IV Sensor UsageEconoMi$er IV Controller Potentiometer LED Locations Enthalpy Changeover Set Points Page CO2 Sensor Standard Settings UrationTypical Belt-Drive Motor Mounting for Size Size 008 Fan Motor PerformanceFan Rpm at Motor Pulley Settings Electric Heater Static Pressure* in. wg 50TFQ008-012External Static Pressure in. wg Rpm Bhp Watts 2250 511 5382300 519 567 2400 534 630Rpm Bhp Watts 2250 511 538 591 697 660 864 2300 519 567 597 729 666 9002400 534 630 611 798 678 974 2500 550 698 624 872Airflow Rpm Bhp Watts 2550 557 733 631 910 38003900 4000 4100 4200 4250 Rpm Bhp Watts 25503100 646 1217 711 1428 770 1645 825 1869 3200 662 1324 726 1542 784 1765 838 19943300 679 1438 741 1663 798 1892 851 2126 3400 695 1558 756 1790 812 2025Rpm Bhp Watts 3000 556 604 623 748 684 891 3100 569 656 636 8053200 583 712 648 865 3300 597 770 661 9293600 639 967 700 1140 754 1312 805 1484 3700 654 1040 713 1218 767 1395 817 15713800 668 1116 726 1299 779 1481 828 1662 3900 683 1197 739 1385 792 1572 840 17583500 625 898 687 1066 742 1233 794 1400 3900 683 1197 739 1385 792 15724200 726 1462 780 1665 1132 3555 4500Rpm Bhp Watts 2250 465 459 555 621 2300 471 483 560 6482400 483 534 570 705 2500 495 588 581 767Rpm Bhp Watts 2250 465 459 555 621 629 786 2300 471 483 560 648 634 8172400 483 534 570 705 644 880 2500 495 588 581 767 653 948Airflow Rpm Bhp Watts 2550 501 617 586 799 658 983 3800 662 17053900 675 1828 Airflow Rpm Bhp Watts 3000 523 541 592 680 657 825 3100 536 587 603 730 666 8793200 549 637 614 783 676 936 3300 562 689 626 839Airflow General Notes for FAN Performance Data Tables PRE-START-UP START-UPOperating Sequence DX Cooling Temperature Control Example Service Cleaning Outdoor CoilLubrication Troubleshooting Cooling Charging Chart, 50TFQ009Page Typical Unit Wiring Schematic 208/203-3-60 Unit Shown Heating and Cooling Troubleshooting EconoMi$er IV Input/Output Logic Demand Control EnthalpyTerminal† Index Mounting Compressor UnitPage START-UP Checklist Preliminary InformationIII. START-UP