Carrier 50BV020-064 specifications Typical Fan Discharge Connections for, Multiple Fan Units

Page 19
Fig. 15 — Typical Fan Discharge Connections for

ACOUSTICAL CONSIDERATIONS — Proper acoustical considerations are a critical part of every system’s design and operation. Each system design and installation should be reviewed for its own unique requirements. For job specific requirements, contact an acoustical consultant for guidance and recommendations.

In general, to reduce noise, consider the following:

Locate mechanical room and ducts away from noise sensitive locations. Whenever possible, work with the architect to locate the equipment rooms around the perimeters of restrooms, hallways, fire escapes, stair wells, etc., to reduce noise transmission. This allows not only for isolation from radiated sound but also enables the contractor to route duct systems around sensitive locations.

Construct the equipment room of concrete block or use a double offset stud wall with interwoven insulation. Seal all penetrations.

Design the system for low total static pressure.

Use suitable vibration isolation pads or isolation springs according to the design engineer's specifications.

A flexible canvas duct connector is recommended on both the supply and return air sides of units to be connected to system ductwork.

Use a minimum of 15 ft of return ductwork between the last air terminal or diffuser and the unit.

Insulate supply and return ducts with 2-in., 3-lb density insulation.

Round duct is recommended. If rectangular ductwork is used, keep aspect ratios as small as possible (i.e., as close to square as possible).

Avoid any direct line of sight from return air grilles into the unit's return. If return air is to be ducted to an equipment room, an elbow should be installed within the equipment room.

Running a return air drop to near the floor of the room will aid in sound attenuation.

Do not exceed the recommended supply duct velocity of 2,000 fpm.

Do not exceed the recommended return duct velocity of 1,000 fpm.

Use turning vanes on 90-degree elbows.

Place isolation springs under each corner and under each compressor if utilized.

ASSEMBLING MODULAR UNITS — 50BVT,U,V,W,X 30 to 60 ton units ship in the number of pieces shown in Table

2.Reassemble the unit. Use the loose hardware provided in the main air-conditioning section and the instructions below.

1.The filter/economizer section ships bolted to the main air- conditioning section and can be removed in the field. When reattaching the filter/economizer section to the main air-conditioning section, place the filter side of the filter/economizer section facing out and away from the main air conditioning section.

2.If the unit has 2 filter/economizer and 2 main air- conditioning sections (40 through 60 ton units), bolt the remaining filter/economizer section and main air- conditioning section together, as in Step 1.

3.For units with 2 filter/economizer and 2 main air- conditioning sections, use the provided unions to assem- ble the water connections between the 2 additional sections joined in Step 2.

4.For units with multiple air conditioning sections, connect the condensate drain hoses from the “B” side of the unit to the drain manifold on the “A” side of the unit.

5.For unit sizes 044-064, connect power wiring from the main terminal block in the “A” side of the unit to the power terminal block in the “B” side of the unit.

6.For VAV units only, connect the plenum tubing, coiled behind the VAV control panel, to the bulkhead fittings located in the discharge of the supply fan. This connects the high pressure supply to the high side of the duct high static pressure switch.

Multiple Fan Units CAUTION

Remove all shipping blocks, if any, under blower housing or damage to the fan may occur.

Step 3 — Install Ductwork — The VAV units must use a “pair of pants” configuration as shown in Fig. 15. Refer to the Carrier System Design Manual or ASHRAE (American Society of Heating, Refrigerating and Air Conditioning Engi- neers) standards for the recommended duct connection to unit with 2 fans.

A

B

NOTE: A = 11/2 to 21/2B

a50-8357.eps

 

Fig. 15 — Typical Fan Discharge Connections for

Multiple Fan Units

A supply air outlet collar and return air duct flange are pro- vided on all units to facilitate duct connections. Refer to dimen- sional drawings (Fig. 2-14) for connection sizes and locations.

A flexible canvas duct connector is recommended on both supply and return air sides of the units to be connected to the system ductwork.

All metal ductwork should be adequately insulated to avoid heat loss or gain and to prevent condensation from forming on the duct walls. Uninsulated ductwork is not recommended, as the unit's performance will be adversely affected.

Do not connect discharge ducts directly to the blower outlet(s). The factory filter should be left in place on a free return system.

If the unit will be installed in a new installation, the duct system should be designed in accordance with the System De- sign Manual, Part 2 and with ASHRAE (American Society of Heating, Refrigeration and Air Conditioning Engineers) proce- dures for duct sizing. If the unit will be connected to an existing duct system, check that the existing duct system has the capaci- ty to handle the required airflow for the unit application at an

19

Image 19
Contents CONTENTS Installation, Start-Upand Service InstructionsSAFETY CONSIDERATIONS GENERAL MAJOR SYSTEM COMPONENTS Constant Volume CV Unitsa50-7257ef INSTALLATIONStep 1 - Complete Pre-InstallationChecks Table 2 - Modular Unit Shipping TableFig. 2 - 50BVC,J,Q020-034Dimensions Fig. 3 - 50BVE,K020-034Dimensions a50-8201 Fig. 4 - 50BVT,V,W034 High-BoyDimensionsFig. 5 - 50BVT,V,W034 Low-BoyDimensions Fig. 6 - 50BVT,V,W044-064 High-BoyDimensions Fig. 7 - 50BVT,V,W044-064 Low-BoyDimensions Fig. 8 - 50BVU,X034 High-BoyDimensions Fig. 9 - 50BVU,X034 Low-BoyDimensions Fig. 10 - 50BVU,X044-064 High-BoyDimensions Fig. 11 - 50BVU,X044-064 Low-BoyDimensions a50-7306ef NOTES 1.Dimensions in inches mma50-7307ef NOTES 1.Dimensions in inches mma50-8235 Shipping Weights lbSize 034 Units Size 044-064Units Table 3A - Physical Data - 50BVC,E,J,K,Q Table 3B - Physical Data - 50BVT,U,V,W,X Multiple Fan Units Fig. 15 - Typical Fan Discharge Connections fora50-7267ef a50-7138efFig. 16 - Duct Static Pressure Probe P/N 39EK20462Fig. 18 - DHS Pressure Limit Location Fig. 19 - DHS Limit Switch P/NStep 4 - Make Piping Connections a50-825350BVT,V,W Units Table 5A - Condenser Pressure Drop50BVC,J,Q Units Table 5B - Condenser Pressure Drop50BVT,U,V,W,X Units Table 6A - Hot Water Pressure Drop50BVC,E,J,K,Q Units Table 6B - Hot Water Pressure Dropa50-7270ef Step 5 - Complete Electrical ConnectionsTable 7B - Economizer Pressure Drop Curve ft wg, 50BVT,U,V,W,X UnitsTable 9A - Electrical Data - 50BVC,E,J,K,Q Table 9B - Electrical Data - 50BVT,U,V,W,X a50-7272ef Fig. 24 - Typical Wiring 18 to 30 Ton UnitsTwo-StageCooling Units Fig. 26 - Field Terminal Block a50-7273efTable 10 - Recommended Cables a50-7164tfa39-1867t Installation Unit Discharge Locationa50-7275ef Fig. 27 - Modular Unit VAV Control Panel10 Kilo- ohm START-UPTable 11 - Thermistor Resistance vs Temperature Values for Supply-AirTemperature SensorTable 13 - Fan Performance - 50BVC,E,Q020 CV Unit Start-UpTable 14 - Fan Performance - 50BVC,E,Q024 Table 15 - Fan Performance - 50BVC,E,Q028 Table 16 - Fan Performance - 50BVC,E,Q034 Table 17 - Fan Performance - 50BVT,U,V034 Table 17 - Fan Performance - 50BVT,U,V034 cont Table 18 - Fan Performance - 50BVT,U,V044 Table 19 - Fan Performance - 50BVT,U,V054 Table 19 - Fan Performance - 50BVT,U,V054 cont Table 20 - Fan Performance - 50BVT,U,V064 Table 20 - Fan Performance - 50BVT,U,V064 cont VAV Unit Start-Up a50-7425ef OMNIZONE VPAC02-06-04 Fig. 32 - LIDFig. 33 - 50BV VFD Display The LID display will show Year Table 22 - Controller Hardware Points Table 21 - Controller Set PointsTable 23 - Software Points Table 24 - Configuration Parameters Unoccupied space or return air temperature demand MAINTENANCE SERVICEFig. 35 - Forced Circulation Method a50-186tfFig. 34 - Gravity Flow Method a50-187tfa50-7135tf Evaporator Fan Performance AdjustmentTROUBLESHOOTING Charging the SystemPOSSIBLE CAUSE PROBLEMPOSSIBLE CAUSE Table 28 - Unit TroubleshootingPROBLEM CORRECTION PROCEDURETable 30 - Forcing an Input or Output Table 29 - CV Units LED Diagnostic CodesTable 31 - Clearing a Forced Input or Output Page Page Page Page UNIT WIRING FIELD WIRINGPage TRANS-1 FIELD WIRINGWIRE LEGEND a50-7282efPCB2 J1 FIELD WIRINGUNIT WIRING FIELD WIRINGPCB1 PCB1 FIELD WIRINGLEGEND AND NOTES FOR FIG 10-08 Copyright 2008 Carrier CorporationCatalog No Form 50BV-3SICONTROLS START-UPCHECKLISTI. PRELIMINARY INFORMATION II. PRE-START-UPIII.START-UP