Table 7B — Economizer Pressure Drop Curve
(ft wg), 50BVT,U,V,W,X Units
FLOW RATE | SIZE 034 | SIZE 044 | SIZE 054 | SIZE 064 |
(gpm) |
| Pressure | Drop (ft wg) |
|
60 | 13.1 | — | — | — |
70 | 17.9 | — | — | — |
80 | 23.5 | 5.8 | — | — |
90 | 29.8 | 7.3 | — | — |
100 | 36.9 | 9.1 | 9.0 | — |
110 | 44.8 | 11.0 | 11.0 | — |
120 | 53.4 | 13.1 | 13.1 | 13.1 |
130 | — | 15.4 | 15.4 | 15.4 |
140 | — | 17.9 | 17.9 | 17.9 |
150 | — | 20.6 | 20.6 | 20.6 |
160 | — | 23.5 | 23.5 | 23.5 |
170 | — | — | 26.6 | 26.5 |
180 | — | — | 29.8 | 29.8 |
190 | — | — | 33.3 | 33.2 |
200 | — | — | 36.9 | 36.8 |
210 | — | — | — | 40.7 |
220 | — | — | — | 44.7 |
230 | — | — | — | 48.9 |
240 | — | — | — | 53.3 |
LEGEND
GPM — Flow Rate
TRAP (MUST BE
ABOVE TOP OF
CONDENSER COIL)
SLOPE
TOWARD
CONDENSER
LIQUID
LINE
HOT GAS
LINE
50BV
UNIT
REMOTE
CONDENSER
a50-7270ef
PD — Pressure Drop (ft wg)
REMOTE REFRIGERANT PIPING (Remote
Table 8 — Recommended Condenser Matches
for 50BVE,K,U,X Units
50BV | NO. OF | CONDENSER(S) | CONDENSER | |
CKTS | CIRCUITING | |||
|
| |||
020 | 2 | 09DK020 (1) | 50/50% | |
024 | 2 | 09DK024 (1) | 50/50% | |
028 | 2 | 09DK028 (1) | 50/50% | |
034 | 2 | 09DK034 (1) | 50/50% | |
044 | 4 | 09DK024 (2) | 50/50% (each) | |
054 | 4 | 09DK028 (2) | 50/50% (each) | |
064 | 4 | 09DK034 (2) | 50/50% (each) |
Install the
Remote
Fig. 22 — System with Condenser
Above Evaporator
a50-7271ef
50BV
UNIT
HOT GAS
LINE
LIQUID
LINE
SLOPE TOWARD
CONDENSER
REMOTE
CONDENSER
Fig. 23 — System with Evaporator
Above Condenser
Step 5 — Complete Electrical Connections —
Verify that electrical requirements listed on the unit nameplate match available power supply. The unit voltage must be within the range shown in Tables 9A and 9B and phases must be balanced within 2%. Contact the local power company for line voltage corrections. Never operate a motor where a phase im- balance in supply voltage is greater than 2%.
24