Carrier 50BV020-064 specifications B - Electrical Data - 50BVT,U,V,W,X

Page 26

Table 9B — Electrical Data — 50BVT,U,V,W,X

 

 

NOMINAL

VOLTAGE

 

 

COMPRESSOR

 

INDOOR FAN MOTOR

POWER

DISCONNECT

UNIT SIZE

RANGE

 

No. 1 / No. 2

No. 3 / No. 4

SUPPLY

SIZE

VOLTAGE

 

 

 

 

50BVT,U,V,W,X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(3 Ph, 60 Hz)

Min

Max

 

RLA

LRA

RLA

 

LRA

Qty

HP

FLA

MCA

MOCP

FLA

 

 

 

 

 

 

 

 

 

(ea)

(ea)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.5

19.4

159.4

200

143.8

 

 

208/230

187

253

 

62.2

376

 

1

10

25.8

165.8

225

150.2

 

 

 

 

15

38.6

178.6

225

163.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

49.6

189.6

250

174.0

 

 

 

 

 

 

 

 

 

 

 

 

7.5

9.7

71.8

90

64.9

 

034

460

414

506

 

27.6

178

 

1

10

12.9

75.0

100

68.1

 

 

 

15

19.3

81.4

100

74.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

24.8

86.9

110

80.0

 

 

 

 

 

 

 

 

 

 

 

 

7.5

7.8

53.9

70

48.8

 

 

575

518

633

 

20.5

148

 

1

10

10.3

56.4

70

51.3

 

 

 

 

15

15.4

61.5

80

56.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

19.8

65.9

80

60.8

 

 

 

 

 

 

 

 

 

 

 

 

7.5

19.4

217.3

250

206.8

 

 

208/230

187

253

 

42.0

239

42.0

 

239

2

10

25.8

230.1

250

219.6

 

 

 

 

 

 

 

 

 

 

 

 

15

38.6

255.7

250

245.2

 

 

 

 

 

 

 

 

 

 

 

 

7.5

9.7

101.0

110

96.2

 

044

460

414

506

 

19.2

125

19.2

 

125

2

10

12.9

107.4

125

102.6

 

 

 

 

 

 

 

 

 

 

 

 

15

19.3

120.2

125

115.4

 

 

 

 

 

 

 

 

 

 

 

 

7.5

7.8

68.3

80

65.2

 

 

575

518

633

 

12.4

80

12.4

 

80

2

10

10.3

73.3

80

70.2

 

 

 

 

 

 

 

 

 

 

 

 

15

15.4

83.5

90

80.4

 

 

 

 

 

 

 

 

 

 

 

 

7.5

19.4

239.0

250

227.2

 

 

208/230

187

253

 

47.1

318

47.1

 

318

2

10

25.8

251.8

250

240.0

 

 

 

 

15

38.6

277.4

300

265.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

49.6

299.4

300

287.6

 

 

 

 

 

 

 

 

 

 

 

 

7.5

9.7

115.5

125

109.8

 

054

460

414

506

 

22.6

158

22.6

 

158

2

10

12.9

121.9

125

116.2

 

 

 

15

19.3

134.7

150

129.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

24.8

145.7

150

140.0

 

 

 

 

 

 

 

 

 

 

 

 

7.5

7.8

89.1

100

84.8

 

 

575

518

633

 

17.3

125

17.3

 

125

2

10

10.3

94.1

110

89.8

 

 

 

 

15

15.4

104.3

110

100.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

19.8

113.1

125

108.8

 

 

 

 

 

 

 

 

 

 

 

 

7.5

19.4

303.2

350

287.6

 

 

208/230

187

253

 

62.2

376

62.2

 

376

2

10

25.8

316.0

350

300.4

 

 

 

 

15

38.6

341.6

400

326.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

49.6

363.6

400

348.0

 

 

 

 

 

 

 

 

 

 

 

 

7.5

9.7

136.7

150

129.8

 

064

460

414

506

 

27.6

178

27.6

 

178

2

10

12.9

143.1

150

136.2

 

 

 

15

19.3

155.9

150

149.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

24.8

166.9

175

160.0

 

 

 

 

 

 

 

 

 

 

 

 

7.5

7.8

102.7

110

97.6

 

 

575

518

633

 

20.5

148

20.5

 

148

2

10

10.3

107.7

125

102.6

 

 

 

 

15

15.4

117.9

125

112.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

19.8

126.7

125

121.6

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

 

FLA

Full Load Amps

MCA

Minimum Circuit Amps

 

 

 

 

 

 

 

HP

Horsepower

MOCP

Maximum Overcurrent Protection

 

 

 

 

 

LRA

Locked Rotor Amps

RLA

Rated Load Amps

 

 

 

 

 

 

 

26

Image 26
Contents SAFETY CONSIDERATIONS Installation, Start-Upand Service InstructionsCONTENTS MAJOR SYSTEM COMPONENTS Constant Volume CV Units GENERALTable 2 - Modular Unit Shipping Table INSTALLATIONStep 1 - Complete Pre-InstallationChecks a50-7257efFig. 2 - 50BVC,J,Q020-034Dimensions Fig. 3 - 50BVE,K020-034Dimensions Fig. 4 - 50BVT,V,W034 High-BoyDimensions a50-8201Fig. 5 - 50BVT,V,W034 Low-BoyDimensions Fig. 6 - 50BVT,V,W044-064 High-BoyDimensions Fig. 7 - 50BVT,V,W044-064 Low-BoyDimensions Fig. 8 - 50BVU,X034 High-BoyDimensions Fig. 9 - 50BVU,X034 Low-BoyDimensions Fig. 10 - 50BVU,X044-064 High-BoyDimensions Fig. 11 - 50BVU,X044-064 Low-BoyDimensions NOTES 1.Dimensions in inches mm a50-7306efNOTES 1.Dimensions in inches mm a50-7307efSize 034 Units Size 044-064Units Shipping Weights lba50-8235 Table 3A - Physical Data - 50BVC,E,J,K,Q Table 3B - Physical Data - 50BVT,U,V,W,X Fig. 15 - Typical Fan Discharge Connections for Multiple Fan UnitsP/N 39EK20462 a50-7138efFig. 16 - Duct Static Pressure Probe a50-7267efa50-8253 Fig. 19 - DHS Limit Switch P/NStep 4 - Make Piping Connections Fig. 18 - DHS Pressure Limit LocationTable 5B - Condenser Pressure Drop Table 5A - Condenser Pressure Drop50BVC,J,Q Units 50BVT,V,W UnitsTable 6B - Hot Water Pressure Drop Table 6A - Hot Water Pressure Drop50BVC,E,J,K,Q Units 50BVT,U,V,W,X Unitsft wg, 50BVT,U,V,W,X Units Step 5 - Complete Electrical ConnectionsTable 7B - Economizer Pressure Drop Curve a50-7270efTable 9A - Electrical Data - 50BVC,E,J,K,Q Table 9B - Electrical Data - 50BVT,U,V,W,X Two-StageCooling Units Fig. 24 - Typical Wiring 18 to 30 Ton Unitsa50-7272ef a50-7164tf a50-7273efTable 10 - Recommended Cables Fig. 26 - Field Terminal BlockFig. 27 - Modular Unit VAV Control Panel Installation Unit Discharge Locationa50-7275ef a39-1867tValues for Supply-AirTemperature Sensor START-UPTable 11 - Thermistor Resistance vs Temperature 10 Kilo- ohmCV Unit Start-Up Table 13 - Fan Performance - 50BVC,E,Q020Table 14 - Fan Performance - 50BVC,E,Q024 Table 15 - Fan Performance - 50BVC,E,Q028 Table 16 - Fan Performance - 50BVC,E,Q034 Table 17 - Fan Performance - 50BVT,U,V034 Table 17 - Fan Performance - 50BVT,U,V034 cont Table 18 - Fan Performance - 50BVT,U,V044 Table 19 - Fan Performance - 50BVT,U,V054 Table 19 - Fan Performance - 50BVT,U,V054 cont Table 20 - Fan Performance - 50BVT,U,V064 Table 20 - Fan Performance - 50BVT,U,V064 cont VAV Unit Start-Up Fig. 32 - LID OMNIZONE VPAC02-06-04 a50-7425efFig. 33 - 50BV VFD Display The LID display will show Year Table 23 - Software Points Table 21 - Controller Set PointsTable 22 - Controller Hardware Points Table 24 - Configuration Parameters Unoccupied space or return air temperature demand SERVICE MAINTENANCEa50-187tf a50-186tfFig. 34 - Gravity Flow Method Fig. 35 - Forced Circulation MethodCharging the System Evaporator Fan Performance AdjustmentTROUBLESHOOTING a50-7135tfPROBLEM POSSIBLE CAUSECORRECTION PROCEDURE Table 28 - Unit TroubleshootingPROBLEM POSSIBLE CAUSETable 31 - Clearing a Forced Input or Output Table 29 - CV Units LED Diagnostic CodesTable 30 - Forcing an Input or Output Page Page Page Page FIELD WIRING UNIT WIRINGPage a50-7282ef FIELD WIRINGWIRE LEGEND TRANS-1FIELD WIRING PCB2 J1PCB1 FIELD WIRINGUNIT WIRING FIELD WIRING PCB1LEGEND AND NOTES FOR FIG Form 50BV-3SI Copyright 2008 Carrier CorporationCatalog No 10-08II. PRE-START-UP START-UPCHECKLISTI. PRELIMINARY INFORMATION CONTROLSIII.START-UP