Carrier 50BV020-064 specifications Configuration Parameters

Page 47
Table 24 — Configuration Parameters

DISPLAY ALARM HISTORY — If the controller is indicat- ing there are alarms, the user can view the alarm history by pressing the HIST button. The LID display will show “Alarm

History.” Press ENTER . The LID display will show the date

and type of alarm.

As an example, if the LID display shows: ALARM — 10:55 02-11-04

SFS

That display indicates that on 02-11-04 at 10:55 a.m. the supply fan was either on when it had not been commanded on or was off when it was commanded on.

The user can view other stored alarms by pressing the up and down arrows. The twenty-four most recent alarms are stored.

CONFIGURE CUSTOM PROGRAMMING SELEC- TIONS — To configure the custom programming selections, perform the following procedure:

1.Press 37 ALGO . The LID display will show: Custom Program

2.Press ENTER . The LID display will show: 2.0 Global Dictionary

OMNIZONE

3.Press ENTER . The display indicates “No Data.” Press CLEAR then press EXPN/EDIT . Press ENTER again. The LID display should now show:

Compressor Stages

2.00(sizes 020-034)

4.00(sizes 044-064)

4.Press Manual background 7 times. The display will show:

0 = RAT, 1 = MAT 2 = NONE

5.Press 2 then ENTER . The display will show:

0 = RAT, 1 = MAT 2 = NONE

6.If RAS is installed at EWT input, press Manual background 3 times. The display will show:

EWT Reset 0 = NO, 1 = YES

7.Press 1 then ENTER . The display will now show: EWT Reset 0 - NO, 1 = YES

8.Use the down and up arrows to select the other configura- tion parameters as required. See Table 24 for a list of con- figuration parameters.

Table 24 — Configuration Parameters

DESCRIPTION

VALUE

UNITS

NAME

Compressor Stages

2.00

 

NUM_CMP

Reset Ratio

3.00

dF

RSET_RTO

CDWF 0=NO,1=YES

0.00

 

CDFW_SWT

*ECON 0=NO,1=YES

0.00

 

EWT_SNS

EWT Reset 0=NO,1=YES

0.00

 

EWT_RST

*MOD.VLV 0=NO,1=YES

0.00

 

MOD_ECON

*0=CONST.,1=VARIABLE

0.00

 

FLOW_TYP

0=RAT,1=MAT 2=NONE

2.00

 

MARA_SNS

PHASE 0=NO,1=YES

0.00

 

PHAS_SWT

*FREEZ 0=NO,1=YES

0.00

 

FREZ_SWT

*ENABLE ECON.

68.00

dF

ECON_SET

SPT 0=NO,1=YES

0.00

 

SPT_SNS

PRES 0=NO,1=YES

0.00

 

PRES_SNS

TWR 0=NO,1=YES

0.00

 

TWR_SNS

LWT 0=NO,1=YES

0.00

 

LWT_SNS

IAQ 0=NO,1=YES

0.00

 

IAQ_SNS

IRH 0=NO,1=YES

0.00

 

IRH_SNS

BSP 0=NO,1=YES

0.00

 

BSP_SNS

BSP Range

1.00

in. H2O

BSP_RNG

BSP LOW VALUE

–0.50

in. H2O

BSP_LOW

*Not used.

SET CONTROLLER ADDRESS — To set the address of the Omnizone™ system control panel controller, perform the fol- lowing procedure:

1.Press 7 and then SRVC . Press ENTER and then EXPN/EDIT .

2.Type in the CCN element number and press ENTER .

3.

Press the

button. Type in the CCN bus number and

 

press ENTER .

LOG OFF FROM CONTROLLER — To log off from the OMNIZONE system control panel controller Press 3 and then SET . The controller password will be displayed.

1. Press ENTER . The display should show:

Log in to Controller Logged in

If this is not displayed, Press EXPN/EDIT until it is dis- played.

2.Press the Manual background button. The LID display will show: Log out of Controller

Press 1. Press ENTER to log off.

Sequence of Operation (CV Only) — The follow- ing sequence applies to constant volume units only.

Cooling is initiated when the set point in the remote thermo- stat is not met (space temperature is higher than set point). The unit sequence of operation is as follows:

The 50BV units can be remotely authorized to be controlled by the thermostat through the optional energy management system relay (EMS). The coil is powered by the energy man- agement (building automation) system whose contacts are in series with the ‘R’ 24-v ac terminal with potential across ‘C’ (transformer common). With this terminal open, power will be interrupted to the thermostat. Closure of this contact will allow the 50BV unit to operate from the thermostat.

Contact closure at the ‘G’ terminal will provide power to the supply fan contactor, energizing the supply fan. The supply fan will be off during unoccupied schedule, depending upon the features of the thermostat used. The ‘O’ terminal energizes the reversing valve (heat pump units only). Typically ‘Y1’ will also be energized at this time for cooling operation. During the second stage of cooling, ‘Y2’ will be initialized after a mini- mum run time and after there is a differential from set point plus a deadband or a proportional plus integral calculation, which is based upon demand and the length of time space- temperature is greater than set point. Additional assurance is provided by a delay on make timer in the second stage com- pressor contactor circuit to avoid dual compressor in-rush start- ing current.

For 4 compressor units, a call for the first stage of cooling will turn on compressors 1 and 2. The second stage of cooling will turn on compressors 3 and 4.

Heating mode (heat pump models only) follows the same sequence as above except that the reversing valve is not energized.

WATER ECONOMIZER COOLING — The unit diverts condenser inlet waterflow through an optional economizer coil to precool evaporator entering airflow. If the entering water temperature is colder than the setting on the aquastat, and the return-air temperature is warmer than the setting on the return- air thermostat, the 3-way diverting valve will direct water to the economizer coil.

Economizer water flow is in series with the condensers allowing compressor operation while the economizer is operating.

47

Image 47
Contents SAFETY CONSIDERATIONS Installation, Start-Upand Service InstructionsCONTENTS GENERAL MAJOR SYSTEM COMPONENTS Constant Volume CV Unitsa50-7257ef INSTALLATIONStep 1 - Complete Pre-InstallationChecks Table 2 - Modular Unit Shipping TableFig. 2 - 50BVC,J,Q020-034Dimensions Fig. 3 - 50BVE,K020-034Dimensions a50-8201 Fig. 4 - 50BVT,V,W034 High-BoyDimensionsFig. 5 - 50BVT,V,W034 Low-BoyDimensions Fig. 6 - 50BVT,V,W044-064 High-BoyDimensions Fig. 7 - 50BVT,V,W044-064 Low-BoyDimensions Fig. 8 - 50BVU,X034 High-BoyDimensions Fig. 9 - 50BVU,X034 Low-BoyDimensions Fig. 10 - 50BVU,X044-064 High-BoyDimensions Fig. 11 - 50BVU,X044-064 Low-BoyDimensions a50-7306ef NOTES 1.Dimensions in inches mma50-7307ef NOTES 1.Dimensions in inches mmSize 034 Units Size 044-064Units Shipping Weights lba50-8235 Table 3A - Physical Data - 50BVC,E,J,K,Q Table 3B - Physical Data - 50BVT,U,V,W,X Multiple Fan Units Fig. 15 - Typical Fan Discharge Connections fora50-7267ef a50-7138efFig. 16 - Duct Static Pressure Probe P/N 39EK20462Fig. 18 - DHS Pressure Limit Location Fig. 19 - DHS Limit Switch P/NStep 4 - Make Piping Connections a50-825350BVT,V,W Units Table 5A - Condenser Pressure Drop50BVC,J,Q Units Table 5B - Condenser Pressure Drop50BVT,U,V,W,X Units Table 6A - Hot Water Pressure Drop50BVC,E,J,K,Q Units Table 6B - Hot Water Pressure Dropa50-7270ef Step 5 - Complete Electrical ConnectionsTable 7B - Economizer Pressure Drop Curve ft wg, 50BVT,U,V,W,X UnitsTable 9A - Electrical Data - 50BVC,E,J,K,Q Table 9B - Electrical Data - 50BVT,U,V,W,X Two-StageCooling Units Fig. 24 - Typical Wiring 18 to 30 Ton Unitsa50-7272ef Fig. 26 - Field Terminal Block a50-7273efTable 10 - Recommended Cables a50-7164tfa39-1867t Installation Unit Discharge Locationa50-7275ef Fig. 27 - Modular Unit VAV Control Panel10 Kilo- ohm START-UPTable 11 - Thermistor Resistance vs Temperature Values for Supply-AirTemperature SensorTable 13 - Fan Performance - 50BVC,E,Q020 CV Unit Start-UpTable 14 - Fan Performance - 50BVC,E,Q024 Table 15 - Fan Performance - 50BVC,E,Q028 Table 16 - Fan Performance - 50BVC,E,Q034 Table 17 - Fan Performance - 50BVT,U,V034 Table 17 - Fan Performance - 50BVT,U,V034 cont Table 18 - Fan Performance - 50BVT,U,V044 Table 19 - Fan Performance - 50BVT,U,V054 Table 19 - Fan Performance - 50BVT,U,V054 cont Table 20 - Fan Performance - 50BVT,U,V064 Table 20 - Fan Performance - 50BVT,U,V064 cont VAV Unit Start-Up a50-7425ef OMNIZONE VPAC02-06-04 Fig. 32 - LIDFig. 33 - 50BV VFD Display The LID display will show Year Table 23 - Software Points Table 21 - Controller Set PointsTable 22 - Controller Hardware Points Table 24 - Configuration Parameters Unoccupied space or return air temperature demand MAINTENANCE SERVICEFig. 35 - Forced Circulation Method a50-186tfFig. 34 - Gravity Flow Method a50-187tfa50-7135tf Evaporator Fan Performance AdjustmentTROUBLESHOOTING Charging the SystemPOSSIBLE CAUSE PROBLEMPOSSIBLE CAUSE Table 28 - Unit TroubleshootingPROBLEM CORRECTION PROCEDURETable 31 - Clearing a Forced Input or Output Table 29 - CV Units LED Diagnostic CodesTable 30 - Forcing an Input or Output Page Page Page Page UNIT WIRING FIELD WIRINGPage TRANS-1 FIELD WIRINGWIRE LEGEND a50-7282efPCB2 J1 FIELD WIRINGPCB1 FIELD WIRINGUNIT WIRING PCB1 FIELD WIRINGLEGEND AND NOTES FOR FIG 10-08 Copyright 2008 Carrier CorporationCatalog No Form 50BV-3SICONTROLS START-UPCHECKLISTI. PRELIMINARY INFORMATION II. PRE-START-UPIII.START-UP