Table 11 — Thermistor Resistance vs Temperature
Values for Supply-Air Temperature Sensor
(10 Kilo- ohm)
TEMP | TEMP | RESISTANCE |
(C) | (F) | (Ohms) |
335,651 | ||
242,195 | ||
176,683 | ||
130,243 | ||
96,974 | ||
5 | 72,895 | |
14 | 55,298 | |
23 | 42,315 | |
0 | 32 | 32,651 |
5 | 41 | 25,395 |
10 | 50 | 19,903 |
15 | 59 | 15,714 |
20 | 68 | 12,494 |
25 | 77 | 10,000 |
30 | 86 | 8,056 |
35 | 95 | 6,530 |
40 | 104 | 5,325 |
45 | 113 | 4,367 |
50 | 122 | 3,601 |
55 | 131 | 2,985 |
60 | 140 | 2,487 |
65 | 149 | 2,082 |
70 | 158 | 1,752 |
SMOKE DETECTOR/FIRE ALARM SHUTDOWN (FSD) — To allow a smoke detector to shut the 50BV down, remove the jumper from FSD to C and wire these terminals to a set of normally closed contacts on the smoke detector.
ALARM (ALARM) AND WARNING (WARN) OUT- PUTS — Two dry contacts output a discrete signal when the alarm and warning lights on the display are lit. To pick up the alarm output signal, wire between the ALARM and
0.50
2.25
O0.187
65º
a50-7274ef
8.00
1.00
0.25
0.22
0.81 1.25
O0.187 (2 HOLES)
REMOTE OCCUPANCY (ROCC) — The 50BV unit may be commanded by another control system or a twist timer to become occupied and run when a set of dry contacts close. In order for this to occur, wire the contacts to ROCC and C and set the Local/Off/Remote switch to REMOTE.
RETURN AIR TEMPERATURE SENSOR (RAS) — The return/mixed air temperature sensor is a 5 kiloohm temperature sensor used as the space control point. For every degree that the RAS is below the set point, the supply air set point will be reset by the configured value in the custom configured RESET RATIO. Refer to Table 12 and Fig. 31.
Table 12 — Thermistor Resistance vs Temperature
Values for Return-Air Temperature
Sensor (5 kiloohm)
TEMP | TEMP | RESISTANCE |
(C) | (F) | (Ohms) |
167,835 | ||
121,098 | ||
88,340 | ||
65,121 | ||
48,487 | ||
5 | 36,447 | |
14 | 27,648 | |
23 | 21,157 | |
0 | 32 | 16,325 |
5 | 41 | 12,697 |
10 | 50 | 9,952 |
15 | 59 | 7,857 |
20 | 68 | 6,247 |
25 | 77 | 5,000 |
30 | 86 | 4,028 |
35 | 95 | 3,265 |
40 | 104 | 2,662 |
45 | 113 | 2,183 |
50 | 122 | 1,801 |
55 | 131 | 1,493 |
60 | 140 | 1,244 |
65 | 149 | 1,041 |
70 | 158 | 876 |
75 | 167 | 740 |
80 | 176 | 628 |
NOTE: All dimensions are in inches.
Fig. 31 — Return Air Temperature Sensor
(P/N HH79NZ079)
Wire the sensor to PCB1 connector J3, terminals 15 and 16. Change custom configuration as instructed in Configure the Custom Programming Selections section. Changing this con- figuration to YES changes the EWT input to be used as return air temperature input.
START-UP
General — Complete the
CRANKCASE HEATERS — The
Wait 24 hours before starting the compressors to permit warming by the crankcase heaters.
AFTER 24 hours, continue with the procedures below.
CONFIRM THE INPUT POWER PHASE SEQUENCE — The input power phase rotation sequence must be
IMPORTANT: On VAV units, fan rotation direction can NOT be used for the phase sequence check; fan rotation for VAV units with a variable speed drive is independent of the unit input wiring sequence.
If the compressor is rotating in the wrong direction, it may: emit increased noise; shut down due to internal overload protection; have only a small decrease in suction pressure when it starts; or have only a small increase in discharge pressure
30