Carrier 50BV020-064 specifications CV Unit Start-Up, Fan Performance - 50BVC,E,Q020

Page 31
CV Unit Start-Up

when it starts. Also, no cooling will be produced at the evaporator. If any of these conditions occurs, refer to the Service section to correct the compressor rotation before continuing.

INTERNAL WIRING — Check all electrical connections in unit control boxes; tighten as required.

RETURN-AIR FILTERS — Check that correct filters are installed in filter tracks (see Tables 3A and 3B). Do not operate unit without return-air filters.

COMPRESSOR MOUNTING — Compressors are internal- ly spring mounted. Do not loosen or remove compressor hold- down bolts.

REFRIGERANT SERVICE PORTS — Each refrigerant system has a total of 2 Schrader-type service gage ports per circuit. One port is located on the suction line, and one on the compressor discharge line. Be sure that caps on the ports are tight.

CV Unit Start-Up

EVAPORATOR FAN — Fan belt and variable pitch motor pulleys are factory installed. See Tables 13-20 for fan perfor- mance data. Be sure that fans rotate in the proper direction.

COOLING — Set the space thermostat to OFF position. Turn on unit power. Set space thermostat to COOL and the fan to AUTO. Adjust the thermostat temperature setting below room temperature. Compressor 1 starts on closure of contactor (com- pressors 1 and 2 on 4-circuit units with 2-stage thermostat).

Adjust the thermostat to an even lower setting until the ther- mostat energizes Y2 (the second cooling stage). Compressor 2 starts on closure of contactor (compressors 3 and 4 on 4-circuit units with 2-stage thermostat).

Adjust the thermostat temperature to a setting just below room temperature. The second stage of cooling should turn off.

Set the thermostat temperature above room temperature. All compressors and the unit fan should now be off.

HEATING (Heat Pump Units Only) — Follow the same se- quence as for cooling (above), except set the space thermostat to HEAT, and instead of adjusting the thermostat below room temperature, adjust it above. Verify that the compressors turn on and the unit runs in reverse cycle mode.

Set the thermostat below room temperature and confirm that the compressors and fan turn off.

Table 13 — Fan Performance — 50BVC,E,Q020

AIRFLOW

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

(cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

4500

623

459

0.52

5000

638

545

0.61

5500

655

641

0.72

725

755

0.85

6000

608

641

0.72

676

755

0.85

742

878

0.99

807

1001

1.13

6500

636

755

0.85

699

878

0.99

761

1010

1.14

821

1142

1.29

7000

604

774

0.87

666

906

1.02

726

1029

1.16

784

1170

1.32

841

1311

1.48

7500

634

916

1.03

693

1057

1.19

750

1189

1.34

805

1330

1.50

858

1480

1.67

8000

667

1085

1.22

723

1226

1.38

777

1377

1.55

829

1526

1.72

880

1676

1.89

8500

700

1273

1.43

753

1423

1.60

804

1573

1.77

853

1732

1.95

902

1836

2.13

9000

735

1480

1.67

785

1638

1.84

833

1745

2.02

881

1908

2.21

927

2071

2.40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

(cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

4500

5000

5500

6000

6500

881

1283

1.44

7000

897

1451

1.63

951

1601

1.80

7500

911

1629

1.83

963

1727

2.00

1014

1881

2.18

8000

930

1781

2.07

979

1935

2.24

1028

2098

2.43

1076

2260

2.62

1124

2422

2.81

8500

950

1989

2.31

997

2152

2.50

1043

2323

2.69

1089

2485

2.88

1134

2697

3.09

9000

973

2233

2.59

1018

2404

2.79

1062

2576

2.99

1106

2779

3.18

1149

2960

3.39

LEGEND

Bhp — Brake Horsepower Input to Supply Fan

Watts — Input Power to Supply Fan Motor

NOTES:

1.Units are available with the following motor and drive combina- tions: 1.5, 2, 3, 5 HP standard drive; 1.5, 2, 3 HP medium static drive.

For 1.5, 2, 3 HP standard drives, the drive range is 753 to 952 rpm. For medium static drives, the drive range is 872 to 1071 rpm. For 5 HP standard drives, the drive range is 967 to 1290 rpm.

2.Italics indicates field-supplied drive required.

3.Table 13 — Fan Performance — 50BVC,E,Q020Manual background Do not operate in shaded area.

4.Static pressure losses must be applied to external static pres- sure before entering the fan performance table.

5.Interpolation is permitted, extrapolation is not.

6.Fan performance is based on filter, unit casing and wet coil losses.

7.Bhp values are per fan. Watts values are per motor. Unit has 2 supply fans and 2 motors.

31

Image 31
Contents CONTENTS Installation, Start-Upand Service InstructionsSAFETY CONSIDERATIONS GENERAL MAJOR SYSTEM COMPONENTS Constant Volume CV Unitsa50-7257ef INSTALLATIONStep 1 - Complete Pre-InstallationChecks Table 2 - Modular Unit Shipping TableFig. 2 - 50BVC,J,Q020-034Dimensions Fig. 3 - 50BVE,K020-034Dimensions a50-8201 Fig. 4 - 50BVT,V,W034 High-BoyDimensionsFig. 5 - 50BVT,V,W034 Low-BoyDimensions Fig. 6 - 50BVT,V,W044-064 High-BoyDimensions Fig. 7 - 50BVT,V,W044-064 Low-BoyDimensions Fig. 8 - 50BVU,X034 High-BoyDimensions Fig. 9 - 50BVU,X034 Low-BoyDimensions Fig. 10 - 50BVU,X044-064 High-BoyDimensions Fig. 11 - 50BVU,X044-064 Low-BoyDimensions a50-7306ef NOTES 1.Dimensions in inches mma50-7307ef NOTES 1.Dimensions in inches mma50-8235 Shipping Weights lbSize 034 Units Size 044-064Units Table 3A - Physical Data - 50BVC,E,J,K,Q Table 3B - Physical Data - 50BVT,U,V,W,X Multiple Fan Units Fig. 15 - Typical Fan Discharge Connections fora50-7267ef a50-7138efFig. 16 - Duct Static Pressure Probe P/N 39EK20462Fig. 18 - DHS Pressure Limit Location Fig. 19 - DHS Limit Switch P/NStep 4 - Make Piping Connections a50-825350BVT,V,W Units Table 5A - Condenser Pressure Drop50BVC,J,Q Units Table 5B - Condenser Pressure Drop50BVT,U,V,W,X Units Table 6A - Hot Water Pressure Drop50BVC,E,J,K,Q Units Table 6B - Hot Water Pressure Dropa50-7270ef Step 5 - Complete Electrical ConnectionsTable 7B - Economizer Pressure Drop Curve ft wg, 50BVT,U,V,W,X UnitsTable 9A - Electrical Data - 50BVC,E,J,K,Q Table 9B - Electrical Data - 50BVT,U,V,W,X a50-7272ef Fig. 24 - Typical Wiring 18 to 30 Ton UnitsTwo-StageCooling Units Fig. 26 - Field Terminal Block a50-7273efTable 10 - Recommended Cables a50-7164tfa39-1867t Installation Unit Discharge Locationa50-7275ef Fig. 27 - Modular Unit VAV Control Panel10 Kilo- ohm START-UPTable 11 - Thermistor Resistance vs Temperature Values for Supply-AirTemperature SensorTable 13 - Fan Performance - 50BVC,E,Q020 CV Unit Start-UpTable 14 - Fan Performance - 50BVC,E,Q024 Table 15 - Fan Performance - 50BVC,E,Q028 Table 16 - Fan Performance - 50BVC,E,Q034 Table 17 - Fan Performance - 50BVT,U,V034 Table 17 - Fan Performance - 50BVT,U,V034 cont Table 18 - Fan Performance - 50BVT,U,V044 Table 19 - Fan Performance - 50BVT,U,V054 Table 19 - Fan Performance - 50BVT,U,V054 cont Table 20 - Fan Performance - 50BVT,U,V064 Table 20 - Fan Performance - 50BVT,U,V064 cont VAV Unit Start-Up a50-7425ef OMNIZONE VPAC02-06-04 Fig. 32 - LIDFig. 33 - 50BV VFD Display The LID display will show Year Table 22 - Controller Hardware Points Table 21 - Controller Set PointsTable 23 - Software Points Table 24 - Configuration Parameters Unoccupied space or return air temperature demand MAINTENANCE SERVICEFig. 35 - Forced Circulation Method a50-186tfFig. 34 - Gravity Flow Method a50-187tfa50-7135tf Evaporator Fan Performance AdjustmentTROUBLESHOOTING Charging the SystemPOSSIBLE CAUSE PROBLEMPOSSIBLE CAUSE Table 28 - Unit TroubleshootingPROBLEM CORRECTION PROCEDURETable 30 - Forcing an Input or Output Table 29 - CV Units LED Diagnostic CodesTable 31 - Clearing a Forced Input or Output Page Page Page Page UNIT WIRING FIELD WIRINGPage TRANS-1 FIELD WIRINGWIRE LEGEND a50-7282efPCB2 J1 FIELD WIRINGUNIT WIRING FIELD WIRINGPCB1 PCB1 FIELD WIRINGLEGEND AND NOTES FOR FIG 10-08 Copyright 2008 Carrier CorporationCatalog No Form 50BV-3SICONTROLS START-UPCHECKLISTI. PRELIMINARY INFORMATION II. PRE-START-UPIII.START-UP