Carrier 50BV020-064 specifications Fan Performance - 50BVC,E,Q034

Page 34
Table 16 — Fan Performance — 50BVC,E,Q034

Table 16 — Fan Performance — 50BVC,E,Q034

AIRFLOW

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

(cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

9,000

639

1187

1.36

693

1334

1.53

745

1490

1.71

795

1646

1.89

843

1802

2.07

9,500

665

1362

1.56

717

1518

1.74

766

1674

1.92

814

1839

2.11

861

2004

2.30

10,000

693

1555

1.78

743

1720

1.97

791

1894

2.17

836

2058

2.36

881

2232

2.56

10,500

721

1775

2.03

769

1949

2.23

815

2122

2.43

859

2296

2.63

902

2478

2.84

11,000

749

2004

2.30

795

2186

2.51

840

2369

2.71

882

2551

2.92

924

2742

3.14

11,500

777

2259

2.59

822

2451

2.81

864

2642

3.03

906

2833

3.25

946

3024

3.47

12,000

805

2533

2.90

848

2733

3.13

889

2933

3.36

929

3133

3.59

968

3333

3.82

12,500

835

2842

3.26

877

3042

3.49

917

3251

3.73

955

3460

3.97

993

3668

4.20

13,000

865

3169

3.63

905

3378

3.87

944

3596

4.12

981

3813

4.37

1018

4021

4.61

13,500

894

3514

4.03

933

3741

4.29

971

3958

4.54

1007

4184

4.80

14,000

924

3895

4.46

961

4121

4.72

998

4356

4.99

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

(cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

9,000

890

1958

2.24

936

2122

2.43

982

2296

2.63

1026

2460

2.82

1071

2642

3.03

9,500

906

2168

2.48

950

2341

2.68

994

2515

2.88

1037

2688

3.08

1079

2870

3.29

10,000

925

2405

2.76

967

2578

2.96

1009

2760

3.16

1051

2942

3.37

1092

3124

3.58

10,500

944

2660

3.05

986

2842

3.26

1026

3024

3.47

1066

3215

3.68

1105

3405

3.90

11,000

965

2924

3.35

1004

3115

3.57

1043

3315

3.80

1082

3505

4.02

1120

3705

4.25

11,500

985

3224

3.69

1024

3414

3.91

1062

3614

4.14

1099

3813

4.37

1136

4021

4.61

12,000

1006

3532

4.05

1044

3732

4.28

1080

3940

4.52

1117

4148

4.75

1152

4356

4.99

12,500

1030

3877

4.44

1066

4085

4.68

1102

4302

4.93

13,000

1053

4239

4.86

 

 

 

 

 

 

13,500

 

 

 

14,000

LEGEND

Bhp — Brake Horsepower Input to Supply Fan

Watts — Input Power to Supply Fan Motor

NOTES:

1.Unit is available with 5 HP standard drive only. The drive range is 967 to 1290 rpm.

2.Italics indicates field-supplied drive required.

3.Manual backgroundManual background Do not operate in shaded area.

4.Static pressure losses must be applied to external static pres- sure before entering the fan performance table.

5.Interpolation is permitted, extrapolation is not.

6.Fan performance is based on filter, unit casing and wet coil losses.

7.Bhp values are per fan. Watts values are per motor. Unit has 2 supply fans and 2 motors.

34

Image 34
Contents CONTENTS Installation, Start-Upand Service InstructionsSAFETY CONSIDERATIONS MAJOR SYSTEM COMPONENTS Constant Volume CV Units GENERALTable 2 - Modular Unit Shipping Table INSTALLATIONStep 1 - Complete Pre-InstallationChecks a50-7257efFig. 2 - 50BVC,J,Q020-034Dimensions Fig. 3 - 50BVE,K020-034Dimensions Fig. 4 - 50BVT,V,W034 High-BoyDimensions a50-8201Fig. 5 - 50BVT,V,W034 Low-BoyDimensions Fig. 6 - 50BVT,V,W044-064 High-BoyDimensions Fig. 7 - 50BVT,V,W044-064 Low-BoyDimensions Fig. 8 - 50BVU,X034 High-BoyDimensions Fig. 9 - 50BVU,X034 Low-BoyDimensions Fig. 10 - 50BVU,X044-064 High-BoyDimensions Fig. 11 - 50BVU,X044-064 Low-BoyDimensions NOTES 1.Dimensions in inches mm a50-7306efNOTES 1.Dimensions in inches mm a50-7307efa50-8235 Shipping Weights lbSize 034 Units Size 044-064Units Table 3A - Physical Data - 50BVC,E,J,K,Q Table 3B - Physical Data - 50BVT,U,V,W,X Fig. 15 - Typical Fan Discharge Connections for Multiple Fan UnitsP/N 39EK20462 a50-7138efFig. 16 - Duct Static Pressure Probe a50-7267efa50-8253 Fig. 19 - DHS Limit Switch P/NStep 4 - Make Piping Connections Fig. 18 - DHS Pressure Limit LocationTable 5B - Condenser Pressure Drop Table 5A - Condenser Pressure Drop50BVC,J,Q Units 50BVT,V,W UnitsTable 6B - Hot Water Pressure Drop Table 6A - Hot Water Pressure Drop50BVC,E,J,K,Q Units 50BVT,U,V,W,X Unitsft wg, 50BVT,U,V,W,X Units Step 5 - Complete Electrical ConnectionsTable 7B - Economizer Pressure Drop Curve a50-7270efTable 9A - Electrical Data - 50BVC,E,J,K,Q Table 9B - Electrical Data - 50BVT,U,V,W,X a50-7272ef Fig. 24 - Typical Wiring 18 to 30 Ton UnitsTwo-StageCooling Units a50-7164tf a50-7273efTable 10 - Recommended Cables Fig. 26 - Field Terminal BlockFig. 27 - Modular Unit VAV Control Panel Installation Unit Discharge Locationa50-7275ef a39-1867tValues for Supply-AirTemperature Sensor START-UPTable 11 - Thermistor Resistance vs Temperature 10 Kilo- ohmCV Unit Start-Up Table 13 - Fan Performance - 50BVC,E,Q020Table 14 - Fan Performance - 50BVC,E,Q024 Table 15 - Fan Performance - 50BVC,E,Q028 Table 16 - Fan Performance - 50BVC,E,Q034 Table 17 - Fan Performance - 50BVT,U,V034 Table 17 - Fan Performance - 50BVT,U,V034 cont Table 18 - Fan Performance - 50BVT,U,V044 Table 19 - Fan Performance - 50BVT,U,V054 Table 19 - Fan Performance - 50BVT,U,V054 cont Table 20 - Fan Performance - 50BVT,U,V064 Table 20 - Fan Performance - 50BVT,U,V064 cont VAV Unit Start-Up Fig. 32 - LID OMNIZONE VPAC02-06-04 a50-7425efFig. 33 - 50BV VFD Display The LID display will show Year Table 22 - Controller Hardware Points Table 21 - Controller Set PointsTable 23 - Software Points Table 24 - Configuration Parameters Unoccupied space or return air temperature demand SERVICE MAINTENANCEa50-187tf a50-186tfFig. 34 - Gravity Flow Method Fig. 35 - Forced Circulation MethodCharging the System Evaporator Fan Performance AdjustmentTROUBLESHOOTING a50-7135tfPROBLEM POSSIBLE CAUSECORRECTION PROCEDURE Table 28 - Unit TroubleshootingPROBLEM POSSIBLE CAUSETable 30 - Forcing an Input or Output Table 29 - CV Units LED Diagnostic CodesTable 31 - Clearing a Forced Input or Output Page Page Page Page FIELD WIRING UNIT WIRINGPage a50-7282ef FIELD WIRINGWIRE LEGEND TRANS-1FIELD WIRING PCB2 J1UNIT WIRING FIELD WIRINGPCB1 FIELD WIRING PCB1LEGEND AND NOTES FOR FIG Form 50BV-3SI Copyright 2008 Carrier CorporationCatalog No 10-08II. PRE-START-UP START-UPCHECKLISTI. PRELIMINARY INFORMATION CONTROLSIII.START-UP