Carrier 50BV020-064 specifications Omnizone Vpac, 02-06-04, Lid, a50-7425ef

Page 43
OMNIZONE VPAC

FUNCTION KEYS

OPERATIVE KEYS

OMNIZONE VPAC

 

 

12:00

 

02-06-04

 

 

EXPN

1

2

3

SRVC

TEST

STAT

ALRM

EDIT

 

 

 

 

SET SCHD

4

5

6

HIST ALGO

 

7

8

9

CLEAR

– 0 . ENTER

NUMERIC KEYS

Fig. 32 — LID

a50-7425ef

FUNCTION

KEYS

OPERATIVE

KEYS

23.The control forces CMP2 (compressor 2) on then waits 5 seconds.

If CSMUX is not in range, the red LED will go on and the test will stop.

If CSMUX is in range, the red LED blinks once and the test continues.

24.The control forces CMP2 off.

25.The control forces CMP3 (compressor 3) on, if config- ured, then waits 5 seconds.

If CSMUX is not in range, the red LED will go on and the test will stop.

If CSMUX is in range, the red LED blinks once and the test continues.

26.The control forces CMP3 off.

27.The control forces CMP4 (compressor 4) on, if config- ured, then waits 5 seconds.

The LID display shows: Factory/Field Test Stop

Both the yellow and red LEDs will go off.

28.The control forces CMP4 off.

29.The run test is complete.

CHECK VFD — The VFD is factory wired and programmed for proper operation with the unit controls; no installation or service adjustments are normally required. At unit start-up, the VFD’s LED will display “0.0 Hz.” Refer to Fig. 33.

POWER UP LID DISPLAY — After completing the auto- matic run test, perform the following procedures to change the controller password, set the controller clock, configure sched- ules, set parameters, view settings, and view alarm history.

1.Set the Remote/Local/Off switch on the front of the unit to the OFF position. This prevents operation of the fan and compressors while still providing power to the unit controls.

NOTE: When the switch is in the OFF position, the red alarm LED will be lit; this is normal.

2.If the unit access panel (for power and controls) is still on the unit, remove it in order to view the control modules during start-up.

3.Switch the main unit power disconnect to ON.

When power is applied to the Omnizone™ system control panel, the red LED on the top front of the processor module will flash at a rapid pace (about twice a second) for the first 30 to 60 seconds. This rapid flash will then be replaced by a slower pace of about once per second.

The green LED below the red LED will start flashing. The green LED indicates input/output communications for accesso- ry input output modules and the LID display.

The yellow LED will flash when the controller is broadcast- ing CCN messages to a laptop or other computer.

The third LED from the bottom of the controller (PCB1) will light.

The LID display will show the controller identification, time and date as shown below.

OMNIZONE VPAC hh:mm mm-dd-yy

LOG ON TO THE LID DISPLAY — To log on to the LID display, perform the following procedure:

1.Press 3 and then SET . The LID display will show: Controller Password

2.Press ENTER . The LID display will show: Log in to Controller

Enter Password

NOTE: The LID display has two modes: Edit mode and Status/Maintenance mode. Edit mode allows the user to change settings on the configurations screens. Status/ Maintenance mode only allows the user to look at the settings.

43

Image 43
Contents CONTENTS Installation, Start-Upand Service InstructionsSAFETY CONSIDERATIONS GENERAL MAJOR SYSTEM COMPONENTS Constant Volume CV Unitsa50-7257ef INSTALLATIONStep 1 - Complete Pre-InstallationChecks Table 2 - Modular Unit Shipping TableFig. 2 - 50BVC,J,Q020-034Dimensions Fig. 3 - 50BVE,K020-034Dimensions a50-8201 Fig. 4 - 50BVT,V,W034 High-BoyDimensionsFig. 5 - 50BVT,V,W034 Low-BoyDimensions Fig. 6 - 50BVT,V,W044-064 High-BoyDimensions Fig. 7 - 50BVT,V,W044-064 Low-BoyDimensions Fig. 8 - 50BVU,X034 High-BoyDimensions Fig. 9 - 50BVU,X034 Low-BoyDimensions Fig. 10 - 50BVU,X044-064 High-BoyDimensions Fig. 11 - 50BVU,X044-064 Low-BoyDimensions a50-7306ef NOTES 1.Dimensions in inches mma50-7307ef NOTES 1.Dimensions in inches mma50-8235 Shipping Weights lbSize 034 Units Size 044-064Units Table 3A - Physical Data - 50BVC,E,J,K,Q Table 3B - Physical Data - 50BVT,U,V,W,X Multiple Fan Units Fig. 15 - Typical Fan Discharge Connections fora50-7267ef a50-7138efFig. 16 - Duct Static Pressure Probe P/N 39EK20462Fig. 18 - DHS Pressure Limit Location Fig. 19 - DHS Limit Switch P/NStep 4 - Make Piping Connections a50-825350BVT,V,W Units Table 5A - Condenser Pressure Drop50BVC,J,Q Units Table 5B - Condenser Pressure Drop50BVT,U,V,W,X Units Table 6A - Hot Water Pressure Drop50BVC,E,J,K,Q Units Table 6B - Hot Water Pressure Dropa50-7270ef Step 5 - Complete Electrical ConnectionsTable 7B - Economizer Pressure Drop Curve ft wg, 50BVT,U,V,W,X UnitsTable 9A - Electrical Data - 50BVC,E,J,K,Q Table 9B - Electrical Data - 50BVT,U,V,W,X a50-7272ef Fig. 24 - Typical Wiring 18 to 30 Ton UnitsTwo-StageCooling Units Fig. 26 - Field Terminal Block a50-7273efTable 10 - Recommended Cables a50-7164tfa39-1867t Installation Unit Discharge Locationa50-7275ef Fig. 27 - Modular Unit VAV Control Panel10 Kilo- ohm START-UPTable 11 - Thermistor Resistance vs Temperature Values for Supply-AirTemperature SensorTable 13 - Fan Performance - 50BVC,E,Q020 CV Unit Start-UpTable 14 - Fan Performance - 50BVC,E,Q024 Table 15 - Fan Performance - 50BVC,E,Q028 Table 16 - Fan Performance - 50BVC,E,Q034 Table 17 - Fan Performance - 50BVT,U,V034 Table 17 - Fan Performance - 50BVT,U,V034 cont Table 18 - Fan Performance - 50BVT,U,V044 Table 19 - Fan Performance - 50BVT,U,V054 Table 19 - Fan Performance - 50BVT,U,V054 cont Table 20 - Fan Performance - 50BVT,U,V064 Table 20 - Fan Performance - 50BVT,U,V064 cont VAV Unit Start-Up a50-7425ef OMNIZONE VPAC02-06-04 Fig. 32 - LIDFig. 33 - 50BV VFD Display The LID display will show Year Table 22 - Controller Hardware Points Table 21 - Controller Set PointsTable 23 - Software Points Table 24 - Configuration Parameters Unoccupied space or return air temperature demand MAINTENANCE SERVICEFig. 35 - Forced Circulation Method a50-186tfFig. 34 - Gravity Flow Method a50-187tfa50-7135tf Evaporator Fan Performance AdjustmentTROUBLESHOOTING Charging the SystemPOSSIBLE CAUSE PROBLEMPOSSIBLE CAUSE Table 28 - Unit TroubleshootingPROBLEM CORRECTION PROCEDURETable 30 - Forcing an Input or Output Table 29 - CV Units LED Diagnostic CodesTable 31 - Clearing a Forced Input or Output Page Page Page Page UNIT WIRING FIELD WIRINGPage TRANS-1 FIELD WIRINGWIRE LEGEND a50-7282efPCB2 J1 FIELD WIRINGUNIT WIRING FIELD WIRINGPCB1 PCB1 FIELD WIRINGLEGEND AND NOTES FOR FIG 10-08 Copyright 2008 Carrier CorporationCatalog No Form 50BV-3SICONTROLS START-UPCHECKLISTI. PRELIMINARY INFORMATION II. PRE-START-UPIII.START-UP