a50-7135tf
Fig. 36 — Sheave Alignment
Evaporator Fan Performance Adjustment —
To change fan speeds from factory settings:
1.Shut off unit power supply.
2.Loosen nuts on the 4 carriage bolts in the mounting base. Using adjusting bolts and plate, slide the motor and remove the belt.
3.Loosen
4.Screw the movable flange toward the fixed flange to increase speed, and away from the fixed flange to decrease speed. Increasing the fan speed increases the load on the motor. Do not exceed the maximum speed specified in Tables 3A and 3B.
5.Set the movable flange at nearest keyway of the pulley hub and tighten the setscrew. (See Tables 3A and 3B for speed change for each full turn of pulley flange.)
6.Replace and tighten the belts (see Belt Tension Adjust- ment section).
7.Restore power to the unit.
To align fan and motor pulleys:
1.Loosen fan pulley setscrews.
2.Slide fan pulley along fan shaft.
3.Make angular alignment by loosening motor from mounting plate.
4.Restore power to unit.
BELT TENSION ADJUSTMENT — Using a gage, apply 4 lb of force to the center of the belt and adjust the tension until a deflection of
Ideal belt tension is the lowest value under which belt slip will not occur at peak load conditions.
LB FORCE
DEFLECTION
a50-7136ef
Fig. 37 — Fan Belt Tension
Charging the System
REMOTE
To evacuate the system, refer to GTAC II, Module 4, Dehy- dration for Proper Evacuation and Dehydration Techniques.
To charge the 50BVE,K,U,X systems:
1.Add an initial minimum refrigerant charge after evacu- ation to allow the unit to start. Refer to Tables 25A and 25B. Additional refrigerant will be added based on the length of interconnecting piping and vertical separa- tion between the indoor unit and the condenser(s).
Table 25A — Minimum Operating Charge (lb), 50BVE,K Units Matched with 09DK Condensers
UNIT SIZE | 020 | 024 | 028 | 034 | |||||
Circuit 1... | 2 | 8.1... | 8.1 | 9.1... | 9.1 | 9.1... | 9.1 | 18... | 18 |
Table 25B — Minimum Operating Charge (lb), 50BVU,X Units Matched with 09DK Condensers
UNIT SIZE | 034 | 044 | 054 | 064 | |||||
Circuit 1... | 2 | 18 | ...18 | 10... | 10 | 18... | 18 | 18... | 18 |
Circuit 3... | 4 |
| - | 10... | 10 | 18... | 18 | 18... | 18 |
2.To finish charging the system, make sure the unit is running at
3.Add 10 lb of
4.Alternately, and as a
Compressor Oil — All units are factory charged with oil. It is not necessary to add oil unless compressor(s) is re- moved from the unit. If necessary, oil can be removed/charged via Schrader fitting. Operate the system at high evaporator tem- perature prior to oil recharge to assist oil return to the compres- sor(s) from other system components. If necessary, recharge the system as shown in Table 26.
Table 26 — Oil Recharge
50BV |
|
| OIL | OIL | PART | |
SIZE | COMPRESSOR | RECHARGE | ||||
UNIT | TYPE | NUMBER | ||||
|
| (oz) | ||||
|
|
|
|
| ||
| 020 | ZR94KC | 81 |
|
| |
C,E, | 024 | ZR108KC | 106 |
|
| |
Q,J,K | 028 | ZR144KC | 106 | 3GS 150 |
| |
| 034 | ZR19M3 | 137 | viscosity |
| |
|
|
|
| yellow | ||
| 034 | ZR19M3 | 137 | |||
| mineral |
| ||||
T,U, | 044 | ZR125KC | 106 | oil |
| |
V,W,X | 054 | ZR16M3 | 137 |
|
| |
| 064 | ZR19M3 | 137 |
|
|
TROUBLESHOOTING
Refer to Tables
51