C O Y1 Y2 R G
| UNIT MODULE ‘A’ |
|
C | O Y1 Y3 R | G |
PR1
PR2
UNIT MODULE ‘B’
C O Y2 Y4 R G
LEGEND
FC — Fan Contactor
PR — Pilot Relay
PR2
PR1
a50-7273ef
Remote Condenser Units Only
(#1) | ||
|
| PR1 |
(#2) | ||
|
| PR2 |
Fig. 25 — Typical Wiring 40 to 60 Ton Units
Table 10 — Recommended Cables
MANUFACTURER | PART NUMBER |
Alpha | 2413 or 5463 |
American | A22503 |
Belden | 8772 |
Columbia | 02525 |
NOTE: Conductors and drain wire must be at least 20 AWG (American Wire Gage), stranded, and tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon®*, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of
The communication bus shields must be tied together at each system element. If the communication bus is entirely within one building, the resulting continuous shield must be connected to ground at only one single point. If the communi- cation bus cable exits from one building and enters another building, the shields must be connected to the grounds at a lightning suppressor in each building (one point only).
Wiring Control Devices — Standard controls require no field wiring.
Standard controls for VAV applications include: duct static pressure (DSP), duct high static limit switch (DHS), compres- sor status (CSMUX), supply fan start/stop (SF), and supply fan speed (SPEED).
*Teflon is a registered trademark of E.I. du Pont de Nemours and Company.
SUPPLY AIR TEMPERATURE SENSOR (SAT) — The sup- ply air temperature sensor (Fig. 29) is used to measure the temperature of the air leaving the unit. The sensor should be located in the supply air duct, about 1 ft from the unit discharge connection (Fig. 30). On units with 2 fans, locate the sensor ap- proximately 5 duct diameters downstream from “pair of pants” duct connection, allowing for adequate mixing of supply air.
Mount the sensor as follows:
1.Remove the cover of the sensor junction box.
2.Drill a
3.Install the sensor through the hole and secure using 2 no. 8 screws (provided). Do not overtighten.
4.Connect the sensor to the control box. Use an 18 or 20 AWG, 2 conductor, twisted pair cable. This cable is suitable for distances of up to 500 feet.
Connect the field wires to the supply air sensor using wire nuts or closed end style crimp connectors. Do not cut the sensor leads. Use the full length of lead supplied on the sensor.
In the control box, remove the jacket from the cable. Route the sensor wires over to the right hand side of the field terminal block (TB2). Strip the insulation back about
a50-7164tf
Fig. 26 — Field Terminal Block
28