Carrier 50BV020-064 specifications Problem, Possible Cause

Page 52

Table 27 — Run Test Troubleshooting (VAV Units Only)

PROBLEM

POSSIBLE CAUSE

Control modules do not have lights when unit power is on.

Transformer open. Circuit breaker open. Power wiring open. Module failure.

Control display does not light up when unit power is on.

Connection location. Interface cable open. Display failure.

Run test will not start.

Pre-existing ALARM (red)? Not “Logged in” with password.

 

Switch not in local.

WARN (yellow) LED does not light during run test.

Wiring open. Lamp failure. Control module failure.

ALARM (red) LED does not light during run test.

Wiring open. Lamp open. Control module failure.

Run test stops, ALARM (red) LED light is lit after it blinks once.

Bypass switch to LINE. Mode switch to OFF. Duct high

 

pressure switch open. Fire shutdown input or jumper open.

 

Supply air temp out of range. Duct static pressure sensor out of range.

 

Compressor resistor board wiring error or failure.

Fan does not start/ALARM (red) LED blinks 2 times.

Fan relay failure.

Run test stop, ALARM (red) LED is lit after blinking 3 times.

Wiring open. VFD connection error. VFD setup error. Fan relay failure.

 

Current isolator failure. Control module failure.

Run test stop, ALARM (red) LED is lit after it blinks 4 times.

VFD connection error. VFD setup error.

Fan does not increase speed.

Current isolator load adjustment too low.

Fan does not stop after ALARM (red) LED blinks 5 times.

Fan relay failure.

Fan rotation is backwards.

VFD to motor wiring sequence error. VFD setup error.

Run test stop, ALARM (red) LED is lit after blinking 6 times.

Wiring open. Compressor resistor board wiring error or failure.

Compressor 1 does not start.

High pressure switch, low pressure switch, coil frost switch,

 

or compressor protection module open. Compressor relay failure.

 

Contactor failure. Control module failure. No refrigerant charge.

Run test stop, ALARM (red) LED is lit after blinking 7 times.

Wiring open. Compressor resistor board wiring error or failure.

Compressor 2 does not start.

High pressure switch, low pressure switch, coil frost switch,

 

or compressor protection module open. Compressor relay failure.

 

Contactor failure. Control module failure. No refrigerant charge.

Run test stop, ALARM (red) LED is lit after blinking 8 times.

Wiring open. Compressor resistor board wiring error or failure.

Compressor 3 does not start.

High pressure switch, low pressure switch, coil frost switch,

 

or compressor protection module open. Compressor relay failure.

 

Contactor failure. Control module failure. No refrigerant charge.

Run test stop, ALARM (red) LED is lit after blinking 9 times.

Wiring open. Compressor resistor board wiring error or failure.

Compressor 4 does not start.

High pressure switch, low pressure switch, coil frost switch,

 

or compressor protection module open. Compressor relay failure.

 

Contactor failure. Control module failure. No refrigerant charge.

Compressor rotation is backwards.

Field power wiring sequence error. Compressor power wiring sequence error.

“C” message in I/O status display.

No input signal or communication failure.

“Service” message in I/O status display.

Value is forced from 6400 keypad entry.

“Supervisor” message in I/O status display.

Value is forced from network communication (i.e., PC).

ALARM (red) LED always on, will not enter run test.

SAT, DSP, CSMUX, DHS, or PHASE input values. Mode switch OFF.

NOTE: For more information on VAV controls, refer to the 50BV,XJ Controls Operation and Troubleshooting Manual.

52

Image 52
Contents CONTENTS Installation, Start-Upand Service InstructionsSAFETY CONSIDERATIONS MAJOR SYSTEM COMPONENTS Constant Volume CV Units GENERALINSTALLATION Step 1 - Complete Pre-InstallationChecksTable 2 - Modular Unit Shipping Table a50-7257efFig. 2 - 50BVC,J,Q020-034Dimensions Fig. 3 - 50BVE,K020-034Dimensions Fig. 4 - 50BVT,V,W034 High-BoyDimensions a50-8201Fig. 5 - 50BVT,V,W034 Low-BoyDimensions Fig. 6 - 50BVT,V,W044-064 High-BoyDimensions Fig. 7 - 50BVT,V,W044-064 Low-BoyDimensions Fig. 8 - 50BVU,X034 High-BoyDimensions Fig. 9 - 50BVU,X034 Low-BoyDimensions Fig. 10 - 50BVU,X044-064 High-BoyDimensions Fig. 11 - 50BVU,X044-064 Low-BoyDimensions NOTES 1.Dimensions in inches mm a50-7306efNOTES 1.Dimensions in inches mm a50-7307efa50-8235 Shipping Weights lbSize 034 Units Size 044-064Units Table 3A - Physical Data - 50BVC,E,J,K,Q Table 3B - Physical Data - 50BVT,U,V,W,X Fig. 15 - Typical Fan Discharge Connections for Multiple Fan Unitsa50-7138ef Fig. 16 - Duct Static Pressure ProbeP/N 39EK20462 a50-7267efFig. 19 - DHS Limit Switch P/N Step 4 - Make Piping Connectionsa50-8253 Fig. 18 - DHS Pressure Limit LocationTable 5A - Condenser Pressure Drop 50BVC,J,Q UnitsTable 5B - Condenser Pressure Drop 50BVT,V,W UnitsTable 6A - Hot Water Pressure Drop 50BVC,E,J,K,Q UnitsTable 6B - Hot Water Pressure Drop 50BVT,U,V,W,X UnitsStep 5 - Complete Electrical Connections Table 7B - Economizer Pressure Drop Curveft wg, 50BVT,U,V,W,X Units a50-7270efTable 9A - Electrical Data - 50BVC,E,J,K,Q Table 9B - Electrical Data - 50BVT,U,V,W,X a50-7272ef Fig. 24 - Typical Wiring 18 to 30 Ton UnitsTwo-StageCooling Units a50-7273ef Table 10 - Recommended Cablesa50-7164tf Fig. 26 - Field Terminal BlockInstallation Unit Discharge Location a50-7275efFig. 27 - Modular Unit VAV Control Panel a39-1867tSTART-UP Table 11 - Thermistor Resistance vs TemperatureValues for Supply-AirTemperature Sensor 10 Kilo- ohmCV Unit Start-Up Table 13 - Fan Performance - 50BVC,E,Q020Table 14 - Fan Performance - 50BVC,E,Q024 Table 15 - Fan Performance - 50BVC,E,Q028 Table 16 - Fan Performance - 50BVC,E,Q034 Table 17 - Fan Performance - 50BVT,U,V034 Table 17 - Fan Performance - 50BVT,U,V034 cont Table 18 - Fan Performance - 50BVT,U,V044 Table 19 - Fan Performance - 50BVT,U,V054 Table 19 - Fan Performance - 50BVT,U,V054 cont Table 20 - Fan Performance - 50BVT,U,V064 Table 20 - Fan Performance - 50BVT,U,V064 cont VAV Unit Start-Up OMNIZONE VPAC 02-06-04Fig. 32 - LID a50-7425efFig. 33 - 50BV VFD Display The LID display will show Year Table 22 - Controller Hardware Points Table 21 - Controller Set PointsTable 23 - Software Points Table 24 - Configuration Parameters Unoccupied space or return air temperature demand SERVICE MAINTENANCEa50-186tf Fig. 34 - Gravity Flow Methoda50-187tf Fig. 35 - Forced Circulation MethodEvaporator Fan Performance Adjustment TROUBLESHOOTINGCharging the System a50-7135tfPROBLEM POSSIBLE CAUSETable 28 - Unit Troubleshooting PROBLEMCORRECTION PROCEDURE POSSIBLE CAUSETable 30 - Forcing an Input or Output Table 29 - CV Units LED Diagnostic CodesTable 31 - Clearing a Forced Input or Output Page Page Page Page FIELD WIRING UNIT WIRINGPage FIELD WIRING WIRE LEGENDa50-7282ef TRANS-1FIELD WIRING PCB2 J1UNIT WIRING FIELD WIRINGPCB1 FIELD WIRING PCB1LEGEND AND NOTES FOR FIG Copyright 2008 Carrier Corporation Catalog NoForm 50BV-3SI 10-08START-UPCHECKLIST I. PRELIMINARY INFORMATIONII. PRE-START-UP CONTROLSIII.START-UP